SKALMEX Sp. z o.o.
ul. Boczkowska 7, Skalmierzyce 63-460 Nowe Skalmierzyce tel. (0-62) 762-10-39 Strona 7
2. Product description
The smoke removal system control panel the SCP-03 gate or airlock
control is designed for use in smoke removal systems and the control
of the gate or airlock cutting off hazardous rooms.
The Alarm state can be issued by signals from: sensors, manual
smoke exhaust buttons, manual call points, external fire protection
systems.
The control panel monitors the line continuity:
- electromagnetic brakes for fire gate engines,
- smoke exhaust damper,
- fire detector,
- manual smoke exhaust button (both set and reset),
- manual call point,
- external SAP fire signal input.
The battery voltage and the presence of the mains supply are also
checked, in the event of a power outage there is an automatic,
uninterrupted power supply switching to the backup (battery) mode.
The battery condition is checked, if the battery resistance is too high
(above 1.2 Ohm), the control panel will report an error of battery
damage or wear by flashing the Battery diode.
The control panel is signaling of the device status by diodes on the
housing cover and has a multiplied output of these signals which can
be displayed e.g. in a manual smoke exhaust button.
Basic signaling:
−network (mains operation),
−battery (operation from batteries if it is on, battery damage if it is
flashing),
−alarm (control panel alarm status),
−failure (failure status if lit, testing status if flashing).
Additional signaling:
The diodes located on the control panel board indicate the type of
error that occurs.