INTRODUCTION & SPECIFICATIONS
Congratulations and thank you for your purchase of the H2O Drive®control panel. This manual
explains the features and operations of the controller which was designed to operate one well
pump in a pressure control application. The controller automatically controls the operation and
speed of the pump based on the signal from the pressure transducer.
GENERAL
• One Variable Frequency Drive well pump pressure controller
• Operates using a 0-150 PSI pressure transducer (4-20mA)
• HMI - Rotary selector for menu navigation and editing settings
• HMI - High-Brightness 2.4” color graphic LCD display, 240X320 pixel resolution
PUMP CONTROL AND PROTECTION
• Pump run indication
• Pump speed (Hz) and Amps (A) indication
• Pump motor overload protection
• High- and low-pressure alarms
• Pump dry run alarm and well recharge timer
• Floor water sensor and low level switch alarm/shutdown
SYSTEM
• Pump run time
ELECTRICAL SPECIFICATIONS
• Input voltage: 240V nominal
- 200-240V 50Hz/60Hz, single phase for RD150 & RD300
- 200-240V 50Hz/60Hz, three phase/single phase for RD500
- 200-240V 50Hz/60Hz, three phase for RD750
• Output 0-240V, three phase, 0-60Hz capable of operating up to 80Hz
Note: The output voltage cannot exceed the input voltage.
DEDICATED I/Os
• Pressure transducer input, 4-20mA, two wire
• 2 Auxiliary alarm inputs (Low level, Floor water sensor) Dry contact only
• 1 alarm relay output (N.O). 230V, 0.3A Max
ENVIRONMENT
• Surrounding air temperature: 14°F to 104°F (-10°C to 40°C)
• Panel internal temperature: 14°F to 122°F (-10°C to 50°C)
• Storage temperature -4°F to 131°F (-20°C to 55°C)
• Altitude: Maximum of 3280 ft (1000m) above sea level
• Outdoor rated enclosure (UL Type 3R)
SJE Rhombus® 4 H2O Drive®Panel Operation Manual