This appliance has to be installed in an environment defined in pollution
degree 2 / Overvoltage category II or better for a max. altitude of 2000 m.
Before any installation or maintenance work, make sure the power supply
of the instrument is cut.
When the instrument is permanently connected to a dangerous voltage, it
is necessary to add a means of sectionalizing on the power supply (switch,
fuse or circuit breaker) near to the product, to make it easy of access and
to mark it as being the means for cutting the instrument.
This sectionalizing means should cut all the conductors leading the
current.
The accessible part is the communication port (µUSB).
The person who has designed the system (electrical installation including
the instrument) is sole responsible for the safety and must make sure it
has been designed according to the current safety standards.
The device is an Open Type Listed Process Control Equipment. To prevent
any injury resulting from accessibility to live parts the equipment must be
installed in a cabinet.
This appliance contains electronic components and
should not be disposed of with the domestic waste.
It should be collected with the WEEE (Waste Elec-
trical and Electronic Equipment), according to the
current regulation.
The instrument may be connected to dangerous electrical
voltages.
It must be mounted, connected and implemented respecting
the current specific regulations, by a qualified technician, trai-
ned to the safety regulations, who will have read this manual.
1. INTRODUCTION
The products DASv10 and DASCv10 are setpoint detectors, fully programmable
either with the µconsole or by PC via the configuration software and a standard USB/
µUSB cable.
The rear-lit tactile graphical LCD allows the visualisation of all the following informa-
tion concerning the instrument:
- the value of the measure with its unit,
- the name of the product (TAG),
- the status of the relay outputs.
Scrolling message for programming help (programmable in several languages).
Programming protected by code (0000 on factory exit).
Programmable keys for direct access to some functions.
• Input features
- A bidirectional DC current or voltage input:
±100 mV, ±1V, ±10V, ±270V, ±20mA.
- Thermocouple inputs (J, K, B, R, S, T, E, N, L, W, W3, WRE5)
- Sensor inputs: Pt100, Ni 100 (2, 3 or 4 wire), ∆Pt100
- Resistive sensors: caliber 0-400 Ω and 0-10 kΩ
- Potentiometers: from 100 Ω to 10 kΩ
- Relay output:
2 relays - Mode setpoint or mode window.
Recording of the alarms.
Time delay and hysteresis adjustable on each setpoint.
Alarm messages.
- Option F (specify on order):
- Fast acquisition allowing a response time < 25ms on the relays.
Coding
Version:
DASv10: without display
DASCv10: with display
Type
Option: F fast version
DAS(C)v 10 (F)
• CJC terminal (option): reference B1CSF-4
• Standard programming cable USB type A male to µUSB type B male:
reference C1-µUSB