XDesignerPlus Ver2.0 외부 장치 접속 매뉴얼
4.2 Setting TOP Main Menu
[In to the Main Menu] While the power of TOP is turned on and the buzzer beeps once, Touch the
screen’s upper part under the TOP logo on the front sheet.
Note: When turn on the power while pressing the touch, it does not convert into the Menu mode.
When the buzzer sound is unable to confirm because of the noise surroundings, the power of
touch shall be allowed while continuously press and off on the lower part of the logo.
■[Main Menu > Comm. Setup]
1. COM2 Serial Baud Rate : 38400 [BPS]
2 COM2 Serial Data Bit : 8 [BIT]
3 COM2 Serial Stop Bit : 1 [BIT]
4 COM2 Serial Parity Bit : NONE [BIT]
5 COM2 Serial Signal Level : RS-232C
6 COM2 Station Num. In Diag.(0~31) : 00
7 COM2 Time Out : 10 * 100 [mSec]
8 COM2 Send Wait : 00* 10 [mSec]
9 COM1 Serial Baud Rate : 38400 [BPS]
10. COM1 Serial Data Bit : 8 [BIT]
11. COM1 Serial Stop Bit : 1 [BIT]
12. COM1 Serial Parity Bit : NONE [BIT]
13. COM1 Serial Signal Level (0~31) : 00
14. COM1 Time Out : 10 * 100 [mSec]
15. COM1 Send Wait : 00* 10 [mSec]
17. N:1 Station Number (0~31) : 00
Setting N:1 communication
18. N:1 Max Machine (2~31) : 02
■Setting communication Interface
Setup [communications Baud rate] of PLC connected with COM2/1 port.
Setup [Data Bit] of PLC connected with COM2/1 port.
Setup [Stop Bit] of PLC connected with COM2/1 port.
Setup [Parity Bit] of PLC connected with COM2/1 port.
Setup signal level(RS-232C/422/485) of PLC connected with COM2/1 port.
Setup [Time Out] of PLC connected with COM2/1 port. (Timeout:: waiting time for answer of PLC)
Setup [Send Wait] of PLC connected with COM2/1 port.
(Send Wait: communicate after waiting setting time when touch screen requires communications.)
Station Num. In Diag [0~31]
Setup [Station Number] (when use communications diagnosis) of PLC connected with COM2/1 port.
■Setting N:1 communication Interface
Decide if use function of [N:1] function.
[N:1] is the communications between multiple Touch machines and one PLC.
If set [No], setup of No.17 and 18 below are to be ignored.
N:1 Station Number (0~31)
Setup [Station Number] when use [N:1] function.
Setup number of touch machine when use [N:1] function.