Server Technology 4805-XLS-16B Manual de usuario

Instructions
This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in
the literature accompanying the appliance.
Dangerous Voltage
This symbol is intended to alert the user to the presence of un-insulated dangerous voltage within the product’s enclosure
that may be of sufficient magnitude to constitute a risk of electric shock to persons.
Protective Grounding Terminal
This symbol indicates a terminal that must be connected to earth ground prior to making any other connections to the
equipment.
Life-Support Policy
As a general policy, Server Technology does not recommend the use of any of its products in the following situations:
life-support applications where failure or malfunction of the Server Technology product can be reasonably expected to cause
failure of the life-support device or to significantly affect its safety or effectiveness.
direct patient care.
Server Technology will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory
to Server Technology that:
the risks of injury or damage have been minimized,
the customer assumes all such risks, and
the liability of Server Technology is adequately protected under the circumstances.
The term life-support device includes but is not limited to neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia,
pain relief or other purposes), auto-transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers,
hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators (for adults or infants), anesthesia
ventilators, infusion pumps, and any other devices designated as “critical” by the U.S. FDA.
Notices
301-4800-1 Rev H (082214)
Copyright © 2003-2014 Server Technology, Inc. All rights reserved.
1040 Sandhill Drive
Reno, Nevada 89521 USA
All Rights Reserved
This publication is protected by copyright and all rights are reserved. No part of it may be reproduced or transmitted by any means or
in any form, without prior consent in writing from Server Technology.
The information in this document has been carefully checked and is believed to be accurate. However, changes are made
periodically. These changes are incorporated in newer publication editions. Server Technology may improve and/or change
products described in this publication at any time. Due to continuing system improvements, Server Technology is not responsible for
inaccurate information which may appear in this manual. For the latest product updates, consult the Server Technology website at
www.servertech.com. In no event will Server Technology be liable for direct, indirect, special, exemplary, incidental or consequential
damages resulting from any defect or omission in this document, even if advised of the possibility of such damages.
In the interest of continued product development, Server Technology reserves the right to make improvements in this document and
the products it describes at any time, without notices or obligation.
The Globe logo is a trademark of Server Technology, Inc., registered in the US. Use of the logos for commercial purposes without
the prior written consent of Server Technology may constitute trademark infringement and unfair competition in violation of federal
and state laws.
Server Technology, the Globe logo, Switched CDU and CDU are trademarks of Server Technology, Inc., registered in the US.
Sentry, Cabinet Distribution Unit, Environmental Monitor, Pass-Thru, Post-On, and SMARTER Technical Support are trademarks of
Server Technology, Inc.
Other trademarks and trade names can be used in this document to refer to either the entities claiming the marks and names or their
products. Server Technology, Inc. disclaims any proprietary interest in trademarks and trade names other than its own
Please Recycle
Shipping materials are recyclable. Please save them for later use, or dispose of them appropriately.

Table of Contents
CHAPTER 1: INTRODUCTION 4
Quick Installation Checklist............................................................................................................. 4
Technical Support............................................................................................................................ 4
About the -48 VDC Products........................................................................................................... 5
Model 4805-XLS-16B..................................................................................................................... 6
Model 48DCWB-12-2x100-A1NB.................................................................................................. 8
Model 48DCWB-08-2x100-BONB............................................................................................... 10
Model 48DCWB-04-2x100-DONB............................................................................................... 12
Model 48DCWB-04-4x070-DONB............................................................................................... 14
Torque Specifications for Sentry -48 VDC Products..................................................................... 16
IPv6 and Sentry Products............................................................................................................... 17
CHAPTER 2: INSTALLATION 20
Standard Accessories..................................................................................................................... 20
Optional Accessories ..................................................................................................................... 20
Additional Required Items............................................................................................................. 20
Safety Precautions ......................................................................................................................... 21
Mounting ....................................................................................................................................... 22
Attaching the Expansion Module................................................................................................... 22
Connecting to the Power Source.................................................................................................... 22
Connecting Devices....................................................................................................................... 22
Connecting to the Unit................................................................................................................... 23
CHAPTER 3: OPERATIONS 25
Interfaces ....................................................................................................................................... 26
Web Interface................................................................................................................................. 27
Command Line Interface ............................................................................................................... 64
CHAPTER 4: ADVANCED OPERATIONS 105
SSL .............................................................................................................................................. 106
SSH.............................................................................................................................................. 108
SNMP/Thresholds........................................................................................................................ 109
LDAP........................................................................................................................................... 123
TACACS+ ................................................................................................................................... 133
RADIUS ...................................................................................................................................... 139
Logging........................................................................................................................................ 143
Upload/Download........................................................................................................................ 147
Remote Shutdown........................................................................................................................ 149
CHAPTER 5: APPENDICES 152
Appendix A: Resetting to Factory Defaults................................................................................. 152
Appendix B: Uploading Firmware............................................................................................... 153
Appendix C: Technical Specifications......................................................................................... 154
Appendix D: Warranty, Product Registration, and Support......................................................... 158

4Introduction -48 VDC Remote Power Manager
Installation and Operations Manual
Chapter 1: Introduction
Quick Installation Checklist
The following steps are recommended to quickly install and configure your -48 VDC Remote Power Manager
(RPM) for use in the data center equipment cabinet:
1. Mount the -48 VDC Remote Power Manager (RPM).
2. Connect to the power source.
3. Connect the devices.
4. Connect the sensors.
5. Connect to the -48 VDC RPM.
6. Configure the -48 VDC RPM.
Login as the predefined Administrator (admn/admn).
Configure the network settings.
Create new administrative user account.
Configure location and unit names.
Configure sensor names.
Configure new user account(s).
Remove the predefined administrator account (admn/admn).
7. Connect the -48 VDC RPM to the network.
Technical Support
Experience Server Technology's FREE SMARTER Technical Support
Server Technology understands that there are often questions when installing and using a new product. Free Technical
Support is provided from 8:00 a.m. to 5:00 p.m. PST, Monday through Friday. After-hours service is provided to
ensure your requests are handled quickly no matter what time zone or country you are located in.
Server Technology, Inc.
1040 Sandhill Drive Tel: 775.284.2000 Web: www.servertech.com

-48 VDC Remote Power Manager Introduction 5
Installation and Operations Manual
About the -48 VDC Products
The following items have been designed into the current -48 VDC products covered in this user manual:
Sentry firmware version 7.0 is provided with all -48 VDC black units, and with all -48 VDC beige/ivory units with
part numbers ending in “/Q”.
-48 VDC products with Sentry firmware version 7.0 more closely match the feature set of the Server Technology
AC Switched CDUs.
Generally, greater power distribution (greater than one output/outlet for each input/inlet) is provided.
Remote power management (Switched outputs).
Network and Serial RS-232 access.
Per Outlet Current Sensing.
NOTE: The current sensing per outlet in the -48 VDC units is not the same as Per Outlet Power Sensing (POPS) in the AC product
firmware. The -48 VDC units only measure current (amps).
For Environmental Monitoring, each master unit supports two combination temperature/humidity probes.
Over-current protection is provided for each output:
oGMT fuse for low-amp outputs up to 10A.
oTPC fuses for high-amp output up to 125A.
oCircuit breaker protection up to 100A available (with one model).

6Introduction -48 VDC Remote Power Manager
Installation and Operations Manual
Model 4805-XLS-16B
Unit Drawing
The 4805-XLS-16B (master unit, front view):
Product Description
The 4805-XLS-16B has the following characteristics:
2U
16 low-amp outputs up to 10A maximum
oIndividually protected by Bussman GMT fuses
Expansion unit is 4805-XMS-16/Q (beige) and 4805-XMS-16B (black)
100A input block details:
oDual ¼” studs spaced by 5/8”
oMaximum lug width: ¾”
oOnly flat lugs accepted
Low-amp (10A maximum) terminal details:
oAccepts 14AWG maximum, ROJ to 5/8”
Fuses:
oIncludes 16x10A GMT fuses
oMaximum GMT fuse value allows: 10A
oOptional values and spares sold separately
oSTI part number: FUSE-GMT-xxA/G (where “xx” is ¾, 1.0, 1.5, 2, 3, 5, 7.5, or 10.)
oAdditional values are available from alternate sources.

-48 VDC Remote Power Manager Introduction 7
Installation and Operations Manual
o
Terminal Stud Spacing
The 4805-XLS-16B terminal stud spacing:
Mounting Bracket
The 4805-XLS-16B mounting bracket:

8Introduction -48 VDC Remote Power Manager
Installation and Operations Manual
Model 48DCWB-12-2x100-A1NB
Unit Drawing
The 48DCWB-12-2x100-A1NB (master unit, front view):
Product Description
The 48DCWB-12-2x100-A1NB has the following characteristics:
2U
Output terminal block:
oDual #10 studs spaced by ¾” (20mm)
oMaximum compression lug width: 0.57 (14.5mm)
oFlat or 90° lugs accepted.
Fuses:
oIncludes 8 10A GMT fuses (#FUSE-GMT-10A/G)
- Optional STI fuse part number: FUSE-GMT-xxA/G (where “xx” is ¾, 1.0, 1.5, 2, 3, 5, 7.5, or 10.)
oIncludes four TPC fuses at no charge
- IMPORTANT: TPC fuses must be specified as separate line items on the same order at zero cost.
oMaximum TPC value allowed: 75A
oSTI fuse part number: FUSE-TPC-xx (where “xx” is 10, 13, 20, 25, 30, 40, 50, 60, or 75)
oOptional values and spare fuses sold separately

-48 VDC Remote Power Manager Introduction 9
Installation and Operations Manual
Terminal Stud Spacing
The 48DCWB-12-2x100-A1NB terminal stud spacing:
Mounting Bracket
The 48DCWB-12-2x100-A1NB mounting bracket:

10 Introduction -48 VDC Remote Power Manager
Installation and Operations Manual
Model 48DCWB-08-2x100-BONB
Unit Drawing
The 48DCWB-08-2x100-BONB (master unit, front view):
Product Description
The 48DCWB-08-2x100-BONB has the following characteristics:
2U
Dual 100A inputs, A and B
Eight mid-amp outputs up to 20A
oIndividually Bussman TPC-fused at up to 25A maximum
One non-switched non-measured 5A AUX output
Expansion unit is model 48DCXB-08-2x100-BONB
NEBS Level 3 certified
100A input block details:
oDual ¼” studs spaced by 5/8”
oMaximum lug width: ¾”
oOnly flat lugs accepted
20A output block details:
oAccepts #10 ring lug, minimum hole diameter: 0.161” (4.0mm)
oMaximum ring lug width: 7/16” (0.44”, 11.1mm)
Fuses:
oIncludes eight TPC fuses at no charge
oIMPORTANT: Fuses must be specified as separate line items on the same order at zero cost.
oMaximum value allows: 25A
oSpare fuses sold separately
oSTI part number: FUSE-TPC-xx (where “xx” is 10, 15, 20, or 25.)
oAdditional (lower) values are available from alternate sources.
Este manual sirve para los siguientes modelos
9
Tabla de contenidos
Otros manuales de Unidad de distribución de energía de Server Technology

Server Technology
Server Technology Sentry PT22 Guía de instalación

Server Technology
Server Technology CW-16V Manual de usuario

Server Technology
Server Technology switched pro2 Manual de usuario

Server Technology
Server Technology CDUCW-24V4 Manual de usuario

Server Technology
Server Technology switched pro2 Manual de usuario

Server Technology
Server Technology Switched Rack PDU Manual de usuario

Server Technology
Server Technology CDUCW-16V-MX Manual de usuario

Server Technology
Server Technology CW-8H Manual de usuario

Server Technology
Server Technology Sentry CB-12H Series Manual de usuario