P 2/2 SW_IN_TC-169-1_test-lamp_for-210_series_flame_detectors_v1.docx
4. First use
1. Remove the cover of the battery compartment (on the top of the Test Lamp).
2. Take and place the battery back into the battery compartment in such a way
that the terminals of the 12 V battery are making contact with the terminals of
the lamp. Press the battery sufficiently to enable easy mounting of the cover.
3. Mount the cover of the battery compartment in the original position. Charge
the battery (see chapter 6) until the status LED is continuous green.
Remark:
The battery is charged when leaving the factory. However, the battery should be
charged immediately after purchase.
5. Operation
Before a test is carried out make sure the Flame Detector is switched on and the alarm outputs are in override.
Please avoid unwanted alarm signals as a result of your test. Use in safe areas only.
The test lamp will turn on/off by pressing/releasing the trigger. When pressing the trigger the status LED is
continuous green, provided the test lamp battery is fully charged.
1. Point at the Flame Detector within the test distance and on the central axis of the cone of vision of the detector.
2. Press the trigger and wait until the Flame Detector is activated. The Test Lamp will deactivate automatically after
30 seconds. The 210-series Flame Detector should always come into alarm within this time period.
3. Wait at least 30 seconds after each test before performing the next test.
6. Charging
1. Plug in the charger and apply the charger cable to the Test Lamp. During charging the status LED is either
steady Yellow or blinking Green.
2. Charge until the status LED is continuous green. When the green LED is steady after about 4 hours the battery is
fully charged.
3. The Test Lamp must be fully charged when stored. Every 3 months the unit should be recharged.
4. When the charger is removed after the charging, the status LED is switched off.
7. Battery replacement
1. Remove the cover from the battery compartment.
2. Slide the new battery in the battery compartment. Make sure that the poles are heading in the direction of the
terminals of the test lamp.
3. Place the cover of the battery compartment in the original position.
4. Charge the new battery (see chapter 6) until the green LED is continuous green.
Battery specifications: