1 Overview
The EIB / KNX bus power supply is used to provide and monitor the voltage of the EIB / KNX system. The output
has two terminals, including one KNX bus output for EIB bus power supply and signal transmission. One 30V DC
auxiliary output and provides a power supply voltage of 30V DC, 500mA which can be sent to the terminal; the reactor
has been integrated into the bus connection terminal; if a reactor is connected to the 30V DC auxiliary power supply
terminal, it can also be used as a bus power supply terminal and also has a signal transmission function.
In order to facilitate installation into the distribution box, the KNX bus power supply is designed as a modular
installation device that can be mounted on a 35 mm DIN rail. The equipment adopts screw terminals to realize 220V
voltage input and auxiliary power output connection. The EIB bus connection is directly connected through the EIB
terminal (red / black).
The power can be reset by pressing the reset button on the device for 24s.
Functions:
(1)Meet the power supply of KNX / EIB bus equipment;
(2)The yellow-green status LED indicates the current auxiliary power supply status. When the auxiliary output status
LED is constantly on, it indicates that the auxiliary power supply is normal. When the status LED flashes, it indicates
that any of the auxiliary power supply is overloaded.
(3)The red LED is always on to indicate that the KNX bus output exceeds the rated current of 640mA. When the KNX
bus output current exceeds 900mA, the bus output is automatically cut off and the red LED flashes. Press the reset
button to restore.
2 Detailed parameters
Main input 200-240V AC
KNX Bus output 1 way with reactor,21-30V DC
Auxiliary power output 1 way without reactor,30V DC/500mA
Bus powered output current Max.640mA, Short circuit protection
Auxiliary power supply output current Max.500mA
Continuous short-circuit current ≤1.3A
Power-down hold time >200ms
Frequency 50-60Hz
Shell material PA66
Dimension (Lx W x H) 144mm X 90mm X 64mm
Weight (approx.) 0.4KG
Installation method 35mm DIN rail mounting
Operating temperature -5°C-45°C
Storage temperature -20°C-70°C
Relative humidity max 90%