Schleifenbauer V2.62 Manual de usuario

V2.62 Schleifenbauer PDU
User manual

Table of Content
Overview 5
What’s new 5
Introduction 6
Power distribution meets intelligence 6
Interfaces 6
Accessories 6
Colored housing 7
Measurements 7
Part I - Installation of hardware 8
Safety warnings 8
Expert personnel 8
Technical installation requirements 8
Visual inspection 8
Testing 9
Cleaning 9
Contents of the package 9
Additionally needed tools for installation 9
Mounting the PDU in cabinets 9
How to mount a PDU horizontally (19 inch)? 9
How to mount a PDU vertically (= 0U)? 10
How to install on a flat surface? Table top mount 10
How to prevent hot spots in a cabinet? Sunken installation 10
How to mount a PDU without tools? 10
How to achieve maximum mounting flexibility? Mounting with profile clamps 10
Cabling the PDU: ethernet, databus and sensors 11
How to connect the PDU to LAN? 11
How to connect a databus? 11
How to connect sensors to a PDU? 11
How to connect a NO/NC contact on Classic PDU and ethernet PDU? 12
How to connect NO/NC contact on a G3 PDU? 12
Part II - User manual 13
How to maintain a PDU? 13
How to be sure the status of switchable outlets will not change during firmware upgrade or restarting of the
controller? 13
Life-Supporting Policy 13
Part IIA - Locally monitoring: device display 14
How to change settings locally via PDU display? 14
How to stop a blinking display? Local alert reset 15
Why do alerts occur? 15
How to check the load balance, the temperature / humidity or the status of the NO/NC contact? 15
How to get back to the first page? 16
How to check an outlet status locally? 16
How to check input and/or outlet measurements? 16
Page 2 of 58
V262_User manual
Schleifenbauer PDU

How to read measurements of optional sensors and what options are possible? 17
Option 1: load page 17
Option 2: sensor pages 17
How to read Branch Residual Current measurements? 18
Data center practice: Residual Current Monitoring in relation to Residual Current Devices 18
Where to measure residual current? 18
How to find the PDUs unit address, tag, name or location? 18
How to view PDU connection information? 19
How can I check in which mode and with what protocol the PDU is running? 19
How to check the installed firmware version? 20
How to check for traceability information ? 20
Part IIB - Remote operating and monitoring: Web interface 21
Introduction 21
Login 21
How to select English or German language? 21
How to enlarge a pane in L sized screens? 21
User interface 22
How to change and save settings in the web interface? 22
Dashboard – tab 23
System status 23
Load 25
Interfaces 26
Sensors – tab 27
Inputs – tab 28
Outlets – tab 29
System – tab 31
Identification 32
Configuration 33
Reset 33
Settings 34
Locate 36
Interfaces – tab 37
Part III - Administrator manual 38
Specific manuals 38
How to change SNMPv3 settings? 39
How to use the ‘device list’ section in the web interface? 40
How to add new devices on an existing ring? How to solve duplicate devices? 40
How to configure login profiles, usernames and passwords? 41
How to change factory passwords? 42
How to change the Ethernet link settings? 42
Network configurations 43
DHCP and default address 43
How to change the hostname? 43
How to configure the IP settings manually? 43
How to setup IPv6? 44
Page 3 of 58
V262_User manual
Schleifenbauer PDU

IPv6 Autoconfigure (SLAAC) 44
Static IP 44
How to configure IPv6? 45
How to set up IPv6 address filtering? 46
Configure SSL certificates 47
Key Generation 47
TLS Cipher Suites Supported: 47
Note on self-signed certificates 48
Certificate Generation 48
How to send SNMP Traps with IPv6? 49
How to stop alert signaling? (auto reset alert) 50
Firmware downgrade / upgrade 50
How to upgrade the firmware? Using SPST 50
How to upgrade the firmware? Using USB 51
Schleifenbauer databus: what is it? 52
How to prevent data losses because of cable cuts? Ring redundancy 53
How to create a databus using Schleifenbauer Gateway? 54
How to connect the databus to LAN without a Gateway? Using a PDU! 55
PART IV - Problem Solving 56
How to perform a “Software reset”? And why? 56
Remotely 56
Locally 56
How to perform a “Factory reset”? 56
How to reset peak current? And other dips or peaks 57
Recycling 58
PRODUCT SPECIFICATIONS 58
SERVICE AND SUPPORT 58
Page 4 of 58
V262_User manual
Schleifenbauer PDU

OVERVIEW
The Schleifenbauer Power Distribution Unit (PDU) is fully configurable and allows customers to connect a variety of power
appliances. Furthermore, the PDU allows remote management through a number of protocols which allow users to
monitor metered sockets and receive alarms on custom thresholds. This manual is split in four sections:
Users can focus on the section that fulfills their need when installing, operating and/or managing the PDU. The “Problem
Solving” section is meant to guide users in resolving problems. It is not necessary to read the complete manual.
WHAT’S NEW
●Added choice of DHCP hostname: serial number or sysname.
●Added locate function that blinks PDU display at request.
●Added devicetype readout (sdbDevIdDeviceType).
Part I
Installation manual
Prepare PDU for use:
●safety issues
●mounting the PDU
●cabling the PDU
Part II
User manual
Operator and user part:
●operating/read out via the PDU-display
●operating/read out via the web interface
●problem solving
Part III
Administrator manual
Admin part:
●configure via the web interface
●set up via the web interface
●problem solving
Part IV
Problem Solving
In this chapter you can find the frequently asked questions
(FAQs).
Page 5 of 58
V262_User manual
Schleifenbauer PDU

INTRODUCTION
POWER DISTRIBUTION MEETS INTELLIGENCE
The Schleifenbauer Intelligent Power Distribution Unit (PDU) is designed to distribute power for many years and without
problems. The PDU is equipped with a specially developed Schleifenbauer databus which makes it possible to read and
manage many PDUs with a single IP address. An ethernet port is added to each PDU so that next to the advantages of a
databus, a whole range of new options has become available. Schleifenbauer PDUs merges the interests between IT and
infrastructures, making it a real bridge builder. Monitoring capabilities will be described in detail within this manual in
upcoming sections.
The PDU may contain:
●metered outlets
●switched outlets
●metered and switched outlets
●passive outlets
Customers can configure the number and types of outlets of their PDU to their requirements by using Schleifenbauers
customization tool when ordering.
INTERFACES
There are several interfaces integrated in the PDU:
In the Admin section of this manual you will find information about the “Interfaces” that describe the technology to
communicate via your LAN (Local Area Network) with the Schleifenbauer databus.
ACCESSORIES
The following accessories can be purchased from Schleifenbauer:
●C14/C20 plugs if C13/C19 outputs are used (please check Outputs on www.schleifenbauer.eu)
●Different types of attachment brackets
o19” rack mounting brackets
oTabletop mounting brackets
oMounting plates for sunken installation
oProfile clamps
oToolless Mounts
●Customer Specific solutions related tools
Please check the Installation Section for more details regarding mounting brackets.
Please check www.schleifenbauer.eu for further details regarding the accessories.
●(embedded) web interface
●Modbus/TCP
●SNMP
(Simple Network Management Protocol)
●(SP)API
(Schleifenbauer Products Application Programming Interface)
Page 6 of 58
V262_User manual
Schleifenbauer PDU

COLORED HOUSING
The default enclosure color of the Schleifenbauer PDUs is black. It is also possible to anodize the enclosure in five other
colors.
MEASUREMENTS
The PDU is capable of measuring a number of quantities, either at the input, output or an optional sensor.
Measurements quantities are shown below:
01. black
02. green
03. orange
04. blue
05. red
06. yellow
Not shown but also available is enclosure color
“natural”
Note:
actual colors may vary!
Measurement
Unit
Remark
Energy
(kWh)
total & subtotal
Voltage
(V)
with voltage dip registration
Current
(A)
with peak value registration and drop detection.
Power factor
(%)
Apparent power
(VA)
Real power
(W)
Temperature
(°C)
optional sensor
Relative humidity
(%)
optional sensor
NO/NC contact
0-2
devices equipped with a USB-port can operate two NO/NC contacts
(see chapter “How to connect a NO/NC contact”)
Page 7 of 58
V262_User manual
Schleifenbauer PDU

PART I - INSTALLATION OF HARDWARE
Please use the information in this chapter to inspect, install and connect the Schleifenbauer Intelligent PDU and all
optional mentioned accessories.
SAFETY WARNINGS
This manual contains important safety instructions that should be followed during installation and operation of the PDU.
Please read this manual carefully since there may be serious or fatal personal injury and damage to the equipment if the
safety instructions, warnings and directions are not complied with. Please save this document for future use.
EXPERT PERSONNEL
Installation, maintenance and inspection of the Schleifenbauer Intelligent PDU must be carried out by adequately trained
persons according to NEN EN 50110-1, with full observance of the specifications of NEN EN 50110-1 and NEN 3140.
TECHNICAL INSTALLATION REQUIREMENTS
Before installing and using the system, check whether the characteristics of the electrical system to which connection is to
be made correspond to the product specifications.
●The Schleifenbauer Intelligent PDU has been designed for connection to electrical systems that comply with IEC
60364 or in the Netherlands, NEN 1010.
●The voltage, maximum permitted current and the number of phases must be correct. This information is
displayed on the front side of the PDU.
●The maximum permitted power must be taken into account with regard to the maximum length and the diameter
of the connecting lead.
●The values and characteristics of the in-series protective devices must match the PDU and the protective
elements included in it.
●The environmental factors must correspond to the product specifications.
VISUAL INSPECTION
After opening the cardboard box and removing the packaging material, the PDU should be checked visually. The PDU
should not be put into operation if damage is detected in a way that safe and proper operation cannot be guaranteed. In
such cases, please contact Schleifenbauer Products BV.Note that, in the case of PDUs that are equipped with an
overvoltage protection, the overvoltage protection and the respective overcurrent protection (if applicable) must be
inspected on a regular basis.
The PDU must be installed in a restricted access location
Socket-outlet must be installed near the equipment
Socket-outlet must be easily accessible
Installation by expert personnel only
After installation: default passwords / RC4 keys MUST be changed (see: Part III - Administrator manual)
Page 8 of 58
V262_User manual
Schleifenbauer PDU

TESTING
Each Schleifenbauer PDU is individually tested according to the NEN 3140 standard. Test reports are available on request.
CLEANING
The PDU may only be cleaned by wiping off the outside with a clean dry cloth.
CONTENTS OF THE PACKAGE
The Schleifenbauer Intelligent PDUs are shipped in a cardboard box. Where applicable, dispose the packaging material in a
responsible manner, in accordance with local regulations. All of the materials used for packaging can be recycled.
Immediately after receipt, check whether you have received your order in a complete and undamaged state.
The following items are delivered for each PDU:
●fixing materials: these can be attached to the PDU (19’’ or table-mounting brackets), or are delivered separately if
they have been ordered separately;
●the installation manual (one per shipment);
Please note that the PDU User Manual can also be found online at http://schleifenbauer.eu
ADDITIONALLY NEEDED TOOLS FOR INSTALLATION
The following tools are needed to install the PDUs:
●cage-nuts with bolts and washers
●suitable screwdriver.
MOUNTING THE PDU IN CABINETS
How to mount a PDU horizontally (19 inch)?
Each 19’’ rack bracket of a PDU has holes for horizontal mounting in 19” racks. The holes are
positioned so that an appropriate fixing hole is always available for a PDU with a profile height of
1.5 U. Using one or two of the four holes allows mounting without wasting space.
For measurement of insulation resistance, the measuring voltage used must be lower than or equal to the
voltage according to the product specification.
Page 9 of 58
V262_User manual
Schleifenbauer PDU

How to mount a PDU vertically (= 0U)?
In case of a PDU for vertical mounting, the connection lead is fed through a hole in the upper, bottom or front face.
How to install on a flat surface? Table top mount
Gives the profile possibility to be mounted to a flat surface (tabletop).This
arrangement is used for:
●vertical mounting to the bracing beams in the 19” cabinet
●fixing to a mounting plate
●mounting between the 19” uprights: the profile attaches to the front
of the uprights
The holes on the brackets are located as far as possible to the outside so
that it can also fit with enough space to tighten the bolts if a swivel gland
has been placed on the short side.
How to prevent hot spots in a cabinet? Sunken
installation
When power leads might block the flow of hot exhaust air, especially in
case of a 600mm wide cabinet, it is necessary to create additional space
for airflow. This can be done by using the “sunken installation brackets”.
Because of the shape of the bracket, it is possible to ‘partially sink’ the
profile into the cabinet and save space. These mounting plates can be
used for many different cabinets.
How to mount a PDU without tools?
Toolless mounting is created by making attachment points on the rear of
the PDU housing. There is a wide range of cabinet brackets available, all in
which you can hang the PDU without using tools.
Toolless Mounting can be done as single PDU or double PDUs (see image).
Mounting brackets can be custom made by Schleifenbauer.
How to achieve maximum mounting flexibility?
Mounting with profile clamps
The clamps, made of spring steel, can be installed in the position of your
choice. The clamp fits around the PDU profile and is secured with a
fastening screw. Our advice is to use one clamp for every 50 cm of profile
length.
Page 10 of 58
V262_User manual
Schleifenbauer PDU