Ramtech WES3 Manual de usuario

Page 1 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
WES3
User Guide and
Operation Manual
Visit the Members Area on
www.wesre.com
for ‘How To’ videos

Page 2 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
Contents
System Units
Unit Diagrams
System Overview
CONNECT
Base Station
Call Point
Heat Detector
Smoke Detector
Link
Interface
Basic System Setup
Health and Safety
Manual Handling, Storage and Transportation
Service and Maintenance
Battery Replacement
Damaged Units
Installation Procedure
WES3 CONNECT - Basic System Setup
Initial CONNECT Setup
Language Selection
Inspection Delay
Pre Alarm Mode
Creating a network
Allocate unit numbers
Adding units to an existing group
Position units on site
Securelyxtheunitsinplace
Test the system
Raising the alarm
Silencing the alarm
Resetting a Call Point
Raising a Medical Alert
Cancelling a Medical Alert
LED Indications
Unit Alive Indication
Amber LED Indication
Red LED Indication
System Tests
Initiating a System Test
Cancelling a System Test
System Integrity Test (Polling)
6
6
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
9
10
10
10
11
11
11
12
12
12
12
13
13
14
14
14
15
15
15
15
15
15
16
16

Page 3 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
Moving a unit on site
Removing a unit from site
CONNECT Operation
Menu Overview
Alarm
Warning Code Guide
CONNECT Pad Controls
Soft Keys
System Logs
Settings
Change Access Code
Unit Numbering
Unit Numbering LED indications
Date and Time
Back Light
Mobile Base
Communications
User Phone Details
Test Phone Number
GSM Status
SIM Card Information
Network Scan
Change Site Name
Power Off
WES3Base Station - Basic System Setup
Initial Base Station Setup
Language Selection
Inspection Delay
Pre Alarm Mode
Creating a network
Allocate unit numbers
Add units to an existing group
Position units on site
Securelyxtheunitsinplace
Test the System
Raising the Alarm
Manual Activation
Automatic Activation
16
16
17
17
18
19
19
19
20
20
20
21
21
22
22
22
22
22
23
23
23
24
24
24
25
26
26
26
26
27
27
28
28
28
28
29
29
29

Page 4 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
Silencing the Alarm
Resetting a Call Point
Raising a Medical Alert
Cancelling a Medical Alert
LED Indications
Unit Alive Indication
Amber LED Indication
Red LED Indication
System Tests
Initiating a System Test
Cancelling a System Test
System Integrity Test (Polling)
Moving a Unit on Site
Removing a Unit from the Site
Base Station Operation
Menu Overview
Alarm
System Warnings
WES Warning Code Guide
Base Station Controls
Home Screen
System Logs
Settings
Change Access Code
Unit Numbering
Unit Numbering LED Indications
Date and Time
Backlight
Mobile Base
Communications
Change Site Name
User Phone Details
Test Phone Number
GSM Status
SIM Card Information
Text Message
Network Scan
29
29
30
30
30
30
30
30
31
31
31
31
32
32
33
33
34
34
35
35
35
36
37
37
37
38
38
38
38
39
39
39
40
40
41
41
41

Page 5 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
Call Point Technical Data
CONNECT Technical Data
Base Station Technical Data
Heat Detector Technical Data
Smoke Detector Technical Data
Interface Technical Data
Link Technical Data
Heat Detector Maintenance
Routine Inspection
Operational Test
Function Test
Cleaning
Smoke Detector Maintenance
Routine Inspection
Operational Test
Function Test
Cleaning
Contact Us
42
45
47
49
52
55
58
61
61
61
61
61
62
62
62
62
62
63

Page 6 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
Guide to all WES3system units available
System Units
Sounder and Strobe
LED Indicators
Call Point
Heat Dectector
LED Indicators
LCD Display
Navigation Pad
Smoke
Detector
Cable Gland
CONNECT
Heat Detector Units
Link
Base Station
Smoke Detector Units
Interface
Antenna
Antenna
Antenna
LED Indicators
Colour LCD Display
Key Pad
USB input
Call Point
NEW IMAGE TO FOLLOWNEW IMAGE TO FOLLOW

Page 7 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
maintained (see Heat Detector Maintenance section) and installed in
line with current local legislation. If proper maintenance is not carried
out, there is a likelihood of malfunction, including false alarms, which
could disrupt operation on site.
Heat Detectors are intended for internal use in enclosed spaces.
Detectors will not function correctly if installed in open spaces without
ceilings, walls etc.
Smoke Detectors
WES3Smoke Detectors are silent but communicate with sounding
units automatically to raise the alarm if smoke is detected.
All Smoke Detectors are sensitive to dust and steam - use the WES3
Smoke Detector in dusty areas, or a WES3 Heat Detector in areas
exposed to excessive levels of dust or steam. If a detector has raised
thealarm,itsredLEDindicatorwillashfor30minutesoruntilthe
alarm is reset.
WES3Smoke Detectors should be securely mounted to the ceiling and
should be regularly maintained (see Smoke Detector Maintenance
section) and installed in line with current local legislation. If proper
maintenance is not carried out, there is a likelihood of malfunction,
including false alarms, which could disrupt operation on site. Smoke
Detectors are intended for internal use in enclosed spaces. Detectors
will not function correctly if installed in open spaces without ceilings,
walls etc.
Link
WES3Link units are used solely to relay WES3radio messages on
large or complex sites if there is no need for additional Fire Points. Link
units should be securely wall mounted.
Interface
WES3Interface units allow input or output devices to be connected to
or via the WES3 network. They can also take an input from an external
trigger and set off the alarm on the WES3system.
System Overview
All WES3units have three indicator LEDs, plus two push buttons,
labelled A and B. Some units have additional buttons and features.
At least one CONNECT unit or Base Station needs to be included in a
WES3networkastheyconguretheWES3network.
Unitsshouldbesecurelyxedusingthetwointegratedmounting
points. We recommend that you use M4 x 50mm pan head screws
andwallplugsorotherxingssuitablefortheparticularwall/ceiling
material.
The tamper switch on the rear of each unit must be in contact with the
wall or ceiling for the unit to function correctly.
All WES3units relay all WES3radio messages for the relevant site.
CONNECT
WES CONNECT includes a alphanumeric key pad, colour LCD display
and a 4G GSM module to include a 4G-enabled sim card.
CONNECT units can be used as mobile units (see Mobile Base
section).
Base Station
WES3Base Stations include a buzzer, an LCD display, a navigation
pad, and if the 3G GSM model has been selected, a modem to allow
SMS message sending.
Base Stations can be used as mobile units (see Mobile Base section).
Call Point
WES3FirePointunitsincludeamanualcallpointusedtoraisethere
alarmwhennecessary,arstaidbuttontoraiseanalertformedical
assistance, and a loud alarm sounder (with optional strobe light).
Fire Points should be securely mounted approximately 1.4 metres
abovetheoor,orinaccordancewithspecicclient-orsite-
requirements.
Heat Detectors
WES3Heat Detectors automatically raise the alarm if the temperature
rises above a safe level. Heat Detectors are silent, but communicate
with Fire Points and Base Stations to raise an audible alarm. If a
detectorhasraisedthealarm,itsredLEDindicatorwillashfor30
minutes or until the alarm is reset.
Heat Detectors should be securely mounted to the ceiling and regularly
WES3System Units

Page 8 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
A basic system is made up of a minimum of three WES3units, at least
one being a WES3CONNECT or Base Station (depending on what you
have ordered). Call Points are essential to all systems if an audible
evacuation alarm is required on site.
Health and Safety
As with all site practices, working safely must be a priority when
installing the WES3system. It is important to observe appropriate
health and safety legislation on site, including national regulatory
obligations,aswellasanylocalsite-orclient-specicrequirements.
Prior to installation of WES3equipment, an appropriate risk
assessment must be carried out and all reasonable efforts to remove
risk put in place. The following notes are intended as general guidance
only. Consideration must be given to design criteria, site conditions and
other trades operating in the area during installation.
Prolongedorrepeatedexposuretoloudnoisesuchasrealarm
sirens may potentially lead to hearing damage. Ensure that protective
measures are taken that are appropriate to the exposure levels
expected on site.
WES3units are not ATEX rated and have not been tested for use in
explosive atmospheres. WES3is not recommended for use in ATEX
applications.
Manual Handling, Storage and
Transportation
Whilst WES3units are lightweight and designed to be easily handled
on-site, it is important that appropriate manual handling practices are
followed. Particular care should be taken when carrying units at height
orwhenascending/descendingelevatedplatforms,scaffoldingor
ladders.
Units are normaly stored and transported in boxes of 8. Refer to
Product Datasheets for full details of unit weights. Unopened boxes
should be stacked no more than 10 high, on a solid, stable surface.
Individual unboxed units should not be stacked on top of one another.
To avoid damage or injury during transit, ensure units are packaged
securely and restricted from moving around.
Service and Maintenance
Under normal conditions, WES3units will function for up to three years
with the need for routine maintenance. A full range of servicing options
are available for aged units. Contact WES Customer Support for
details.
Basic System Setup
WES3units are classed as a ‘Service Access Area’ under EN 60950-1.
It is essential that testing, repairs and servicing are carried out by
WES3Engineersorapproved,qualiedpartners.Modifyinganypart
of the unit can prevent correct functionality, even if the unit appears to
be working.
Battery Replacement
The battery pack within WES is not intended to be user replaced.
When your device signals low battery condition (see page 14, LED
indication), please contact Ramtech or your Distributor to discuss
battery replacement.
Damaged Units
Should a unit be dropped or impacted during installation, operation or
decommissioning, it should be inspected for signs of damage. Even if
no external damage is visible, the internal components may have been
affected. Test the unit for operation and if in doubt, remove the unit
from the network and contact WES Customer Support.
Installation Procedure
WES3units are only compatible with other WES3 units. It is not possible
to create a network using other versions of the WES product e.g.
WES1 or WES+. Ensure that all units intended to be used on site are
the WES3units.
Installing WES3 on your site is easy. You will need to activate each unit
and add the units to the group so that they can communicate with each
other.

Page 9 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
Fire Pont Technical DataWES3CONNECT
Basic System Setup
The following pages (10-26) detail
the setup of a network using a
WES3CONNECT unit.

Page 10 WES3Installation and Operations Manual V2.0 Ramtech Electronics Limited 2020
1. Initial CONNECT Setup
To activate the WES3CONNECT, hold down ‘A’ and press ‘B’ three
timesinquicksuccession.AllthreeLEDswillbrieyilluminateandthen
theamberLEDwillash.
Initial setup of the CONNECT is through a series of on-screen options
such as Language, Inspection Delay and Pre-Alarm mode options.
Language Selection
Select language, available options are English, German, French,
Spanish, Italian and Swedish. Select using the arrows to the side of
thescreen-theselectedlanguagewillbehighlighted.Conrmusing
the ‘tick’ button. Language settings can be changed at any time via the
menus within the CONNECT unit.
Inspection Delay
The Inspection Delay setting allows an optional delay period between
triggering a call point and the site wide alarm being raised. This can
allow time for the incident to be validated on site, and a decision to be
made to either
i)conrmalarmisgenuine,raisesitewidealarmand
evacuate site, or
ii)conrmfalseactivation,cancelthealarmandreturnto
normal (non-alarm) state.
Default setting is 0 minutes (ie no delay), but can be set in 1 minute
incrementsuptoamaximum10minutes.Aconrmationscreenwill
be displayed to validate the setting and prevent accidental activation.
Select using the arrows to the side of the screen.
Analscreenwillthenappearconrmingyourselection,thenusethe
‘tick’buttontoconrm.
Note that Inspection Delay can only be set during the initial
network setup process. Once set, the Inspection Delay can only
be set or changed by turning off all networked units, which resets the
network. This will clear any existing unit numbering and other network
settings from the network.
b
Basic System Setup - CONNECT
Otros manuales para WES3
3
Tabla de contenidos