Outputs:
NPNTTL PNP
TC Resistance, 2-wireRTD, 3- / 4-wireRTD, 2-wire
Inputs:
2-wire transmitter Current
Potentiometer
Resistance,
3- / 4-wire
Voltage
Gnd+ 5 V Gnd Gnd + 24 V
Wiring Diagrams
Configuring a new unit
• Mount the unit on a 35mm DIN rail and connect supply, input and output wires to the
appropriate terminals based on the connection diagrams in this Quick Start Guide.
• Snap the SCU-PDM2 Programming Module on the front of the unit.
• Power up the unit.
• The unit should display the configuration menu similar to the figure below. If
not, press ;once.
• Press ;to begin configuration. Press .or ,to scroll through
options on each step. Press ;to confirm an option and move to the next
step.
• Press and hold ;to step backwards through the configuration menu.
Abbreviations used on the SCU-PDM2 display
Note: Help text for each abbreviation will scroll across the SCU-PDM2
FL.CO = flash memory error
CJ.ER = CJC sensor defect
NO.CO = connection error with SCU-PDM2
IN.ER = error levels on input
TY.ER = configuration in SCU-PDM2
doesn’t match this product
ADV.SET = advanced settings
IN TYPE = input type
V.RANGE = voltage range
I.RANGE = current range
CONNEC. = connecting wires
Pt TYPE = Platinum RTD type
Ni TYPE = Nickel RTD type
TC.TYPE = thermocouple type
DEC.P = decimal place location
SE.BR = a sensor wire is not connected
DECR = decreasing
ACT.DIR = action direction
DISP.LO = display range low
DISP.HI = display range high
OU.UN = set Hz or pulse output
f.min = set 0% frequency input
f.max = set 100% frequency input
CUT.OFF = set cut off frequency
O.TYPE = output pulse type
t.PULSE = pulse time in milliseconds
P.min = set 0% pulse
P.max = set 100% pulse
f.ERR = output frequency on input error
RESP = response time in seconds
OUT.ERR = output action on error
OUT.LO = temp for low output
OUT.HI = temp for high output
EN.PASS = enable password
NEW.PAS = new password
CAL.LO = calibrate input low to process value?
CAL.HI = calibrate input high to process value?
USE.CAL = Use process calibration value?
Convert a potentiometer position to a 0-100 percentage frequency signal.
• In the configuration menu Press .or ,until POTM is displayed for IN.TYPE. Press ;.
• Select input units. Press .or ,until %is displayed for UNIT. Press ;.
• Select decimal point location. Press .or ,until 111.1 is displayed for DEC.P. Press ;.
• Set display value for minimum input. Press .or ,until 0.0 is displayed for DISP.LO. Press
;.
• Set display value for maximum input. Press .or ,until 100.0 is displayed for DISP.HI.
Press ;.
• Select output unit. Press .or ,until Hz is displayed for OU.UN. Press ;.
• Select output minimum frequency. Press .or ,until 0is displayed for F.MIN. Press ;.
• Select output maximum frequency. Press .or ,until 10.00 kHZ is displayed for F.MAX.
Press ;.
• Select output cutoff frequency. Press .or ,until 0is displayed for CUT.OFF. Press ;.
• Select no output error frequency. Press .or ,until NO is displayed for OUT.ERR. Press ;.
• Set frequency output response time. Press .or ,until 0.4 is displayed for RESP. Press ;.
• Wait while the settings are stored and the unit switches to run mode.
The SCU-2200 will provide no signal when the potentiometer is turned to zero % and 10kHz at
100%.
Application Example - Potentiometer Input to Frequency Output
Application Example - 10VDC Input from DC Current
Transducer to Frequency Output
Monitoring 10VDC output from a DC current transducer monitoring DC amperage into a
pulse/frequency input on a PLC.
• In the configuration menu press .or ,until VOLT is displayed for IN.TYPE. Press
;.
• Select input range. Press .or ,until ~0-10 is displayed for V.RANGE. Press ;.
• Select input units. Press .or ,until Ais displayed for UNIT. Press ;.
• Select decimal point location. Press .or ,until 111.1 is displayed for DEC.P. Press ;.
• Set display value for minimum input. Press .or ,until 0.0 is displayed for DISP.LO.
Press ;.
• Set display value for maximum input. Press .or ,until 100.0 is displayed for DISP.
HI. Press ;.
• Select output unit. Press .or ,until Hz is displayed for OU.UN. Press ;.
• Select output minimum frequency. Press .or ,until 0is displayed for F.MIN. Press
;.
• Select output maximum frequency. Press .or ,until 3.000 kHz is displayed for
F.MAX. Press ;.
• Select output cutoff frequency. Press .or ,until 0is displayed for CUT.OFF. Press
;.
• Select output error response. Press .or ,until 0.4 is displayed for RESP. Press ;.
• Wait while the settings are stored and the unit switches to run mode.
The SCU-2200 will provide no output at 0A and a 3kHz output at 100A (10V).
• In the configuration menu press .or ,until TEMP is displayed for IN.TYPE. Press ;.
• Select temperature sensor type. Press .or ,until Pt is displayed for SENSOR. Press ;.
• Select RTD type. Press .or ,until 100 is displayed for Pt.TYPE. Press ;.
• Select RTD connection type. Press .or ,until 4W is displayed for CONNEC. Press ;.
• Select temperature unit. Press .or ,until °Cis displayed for UNIT. Press ;.
• Select frequency output. Press .or ,until Hz is displayed for OU.UN. Press ;.
• Select output minimum. Press .or ,until 0is displayed for F.MIN. Press ;.
• Select output maximum. Press .or ,until 5.000 kHz is displayed for F.MAX. Press ;.
• Select output cutoff frequency. Press .or ,until 0is displayed for CUT.OFF. Press ;.
• Select no output error frequency. Press .or ,until NO is displayed for OUT.ERR. Press
;.
• Set frequency output response time. Press .or ,until 1.0 is displayed for RESP. Press ;.
• Select temperature for low frequency output. Press .or ,until 0is displayed for OUT.LO.
Press ;.
• Select temperature for high frequency output. Press .or ,until 100 is displayed for
OUT.HI. Press ;.
• Wait while the settings are stored and the unit switches to run mode.
The SCU-2200 will provide a frequency output that correlates to the temperature sensed by the
RTD from 0 Hz to 5 kHz representing a temperature range of 0 to 100 C.
Application Example - 4-Wire RTD to Frequency Output
Several useful functions are in the Advanced Settings Menu. To get to the Advanced Settings
Menu, Press .or ,until YES is displayed for the first screen of the configuration menu
that looks like this:
The configuration of the SCU-2200 can be saved into the SCU-PDM2. The SCU-PDM2 can
then be moved to another unit (must be the same part number) and the configuration loaded into
the new unit.
• Enter Advanced Settings menu and then press .or ,until MEM is displayed for SETUP.
Press ;.
• To save the configuration into the SCU-PDM2. Press .or ,until SAVE is displayed for
MEMORY. Press ;.
• To load the configuration from the SCU-PDM2 into the SCU-2200. Press .or ,until LOAD
is displayed for MEMORY. Press ;.
Password Protection allows the user to create a 4-digit password
(0000-9999) to prevent tampering with configuration settings if the SCU-PDM2 is left mounted
to the front of the signal conditioner.
• Enter Advanced Settings menu and then press .or ,until PASS is displayed for SETUP.
Press ;.
• To enable password protection. Press .or ,until YES is displayed for EN.PASS. Press ;.
• To set a password. Press .or ,until the desired code is displayed for NEW.PAS. Press ;.
Advanced Operations
Additional Help and Support
• For product support, specifications, installation and
troubleshooting, a Hardware User Manual can be
downloaded from the On-line Documentation area of the
AutomationDirect web site.