8
www.prolumia.com
Wall mounting detection area (Unit: m)
Suggested installation height: 1 - 1.8m
Ceiling mounting detection area (Unit: m)
Suggested installation height: 2.5 - 6m
Art.no. LED type Input
power Lumen
switchable Lumen Emer-
gency mode Sensor Mode of
operation Duration Battery
40010021 SMD2835 7.5W 600Lm / 300Lm 200Lm - (Non) maintained
(switchable) 1h Ni-CD 2/3AA450mAhHT 7.2V
40010031 SMD2835 8.5W 600Lm / 300Lm 200Lm Yes (Non) maintained
(switchable) 1h Ni-CD 2/3AA450mAhHT 7.2V
ATTENTION
CAUTION
TECHNICAL DATA
TECHNICAL INFORMATION
1. The product must be installed by qualied technicians.The power supply must be cut before installation.
2. The installation wiring must be 2 x 1.0 mm² at least and wired in accordance with the latest IEE electrical regulations or the national requirements.
3. Cut the power supply before replacing battery.
4. Do not touch the electronic circuit and its components.
5. When xture is unable to maintain the 1 hour duration under battery operation, then the battery must be replaced.
6. Contact an authorised technical service center for the replacement of the battery and use only original manufacturer spare parts for any other
repairs.
7. Code for identication of battery production date: ex.1810 --- 2018, week10.
8. Do not touch the LEDs while installing or maintaining.
9. This product contains a light source of energy eciency class D.
10. The charge of the battery will decrease by self-discharge if not connected to mains supply. Prolonged periods without voltage can damage the
battery. Battery warranty claims, as a result of such abuse, are specically EXCLUDED from warranty terms.
11. On many building sites, power circuits may be cut o in an uncontrolled and repetitive basis during construction. As a result, any unit on these
circuits, will have their batteries discharged or ‘cycled’. Excessive battery cycling will reduce through-life performance and may lead to premature
battery failure. Battery warranty claims, as a result of such abuse, are specically EXCLUDED from warranty terms.
Supply voltage: AC 220-240V 50/60Hz
Light source: LED SMD2835
Batteries: Ni-Cd Duration: 1h
Operating temperature: -20°C - +50°C
Electrical safety class: Class II
Please read the following instructions carefully to ensure that mounting operation will be carried out correctly.These instructions
should be properly preserved for future reference.
MICROWAVE SENSOR DESCRIPTION
Detection zone max. (d x h): 14m x 6m
Detection sensitivity: 25% - 100%, adjustable
Hold time: 5sec - 30min, adjustable
Daylight 1: 5 - 15Lux, adjustable or disable
Daylight 2: 35 - 150Lux, adjustable or disable
(with daylight priority)
Hold time: 5 - 30sec - 1 - 5 - 15 - 30min (adjustable)
Hold time orientation lighting:
0 - 10 - 20 - 30 - 60 - ∞ min (adjustable)
Mounting height: 6m max.
Motion detection: 0.5 ~ 3m/s
Detection angle: 150° (wall installation),
360° (ceiling installation)
NLENCZ FRDE