9113
Temperature /
mA Converter
No. 9113V106-UK
Product version: 9113-004

1503
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturudsving,
og alle produkter opfylder de strengeste internationale standarder.
Vores motto »Signals the Best« er indbegrebet af denne filosofi – og
din garanti for kvalitet.
PR electronics A/S oers a wide range of analog and digital
signal conditioning devices for industrial automation. The product
range includes Isolators, Displays, I.S. Interfaces, Temperature
Transmitters, and Universal Devices. You can trust our products in
the most extreme environments with electrical noise, vibrations and
temperature fluctuations, and all products comply with the most
exacting international standards. »Signals the Best« is the epitome
of our philosophy – and your guarantee for quality.
PR electronics A/S ore une large gamme de produits pour le
traitement des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux acheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et fluctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsgeräte für die in-
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Übereinstimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
DK
UK
FR
DE

9113 - Product Version 9113-004 1
TEMPERATURE / mA CONVERTER
9113
CONTENTS
Warning....................................................................................................... 2
Symbol identification............................................................................ 2
Safety instructions................................................................................. 2
How to demount system 9000 ........................................................ 4
Advanced features................................................................................. 5
Application................................................................................................. 5
Technical characteristics...................................................................... 5
Applications............................................................................................... 6
PR 4501 display / programming front........................................... 7
Mounting / demounting the PR 4501/4511............................... 8
Ordering codes for 9113B................................................................... 9
Accessories ............................................................................................... 9
Electrical specifications........................................................................ 9
Configuration of sensor error check................................................ 14
Input signal outside range.............................................................. 14
Sensor error detection...................................................................... 14
Error indications................................................................................... 14
Connections .............................................................................................. 16
Block diagram........................................................................................... 17
Signal error and cable fault indications
without display front......................................................................... 18
Configuration / operating the function keys............................... 19
Routing diagram...................................................................................... 22
Routing diagram, Advanced settings (ADV.SET)........................ 24
Scrolling help texts in display line 3............................................... 25
Appendix.................................................................................................... 26
IECEx Installation Drawing.............................................................. 27
ATEX Installation Drawing............................................................... 30
FM Installation Drawing ................................................................... 33
INMETRO Installation Drawing ...................................................... 36
Safety Manual....................................................................................... 39

2 9113 - Product Version 9113-004
SYMBOL IDENTIFICATION
Triangle with an exclamation mark: Read the manual before installation
and commissioning of the device in order to avoid incidents that could lead
to personal injury or mechanical damage.
The CE mark proves the compliance of the device with the essential
requirements of the directives.
The double insulation symbol shows that the device is protected by
double or reinforced insulation.
Ex devices have been approved according to the ATEX directive for use in
connection with installations in explosive areas.
SAFETY INSTRUCTIONS
DEFINITIONS
Hazardous voltages have been defined as the ranges: 75...1500 Volt DC, and
50...1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also
troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate
the knobs or potentiometers during normal operation.
WARNING
The following operations should only be carried out on a discon-
nected device and under ESD-safe conditions:
General mounting, connection and disconnection of wires.
Troubleshooting the device.
Repair of the device and replacement of circuit breakers must
be done by PR electronics A/S only.
WARNING
Do not open the front plate of the device as this will cause dama-
ge to the connector for the display / programming front PR 4501.
This device contains no DIP-switches or jumpers.

9113 - Product Version 9113-004 3
RECEIPT AND UNPACKING
Unpack the device without damaging it. The packing should always follow the
device until this has been permanently mounted.
Check at the receipt of the device whether the type corresponds to the one
ordered.
ENVIRONMENT
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
The device must be installed in pollution degree 2 or better.
The device is designed to be safe at least under an altitude up to 2 000 m.
MOUNTING
Only technicians who are familiar with the technical terms, warnings, and instruc-
tions in the manual and who are able to follow these should connect the device.
Should there be any doubt as to the correct handling of the device, please contact
your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com
The use of stranded wires is not permitted for mains wiring except when wires
are fitted with cable ends.
Descriptions of input / output and supply connections are shown in the block
diagram and on the side label.
The device is provided with field wiring terminals and shall be supplied from
a Power Supply having double / reinforced insulation. A power switch shall be
easily accessible and close to the device. The power switch shall be marked as
the disconnecting device for the device.
For installation on Power Rail 9400 the power is supplied by Power Control
module 9410.
Year of manufacture can be taken from the first two digits in the serial number.
CALIBRATION AND ADJUSTMENT
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.

4 9113 - Product Version 9113-004
NORMAL OPERATION
Operators are only allowed to adjust and operate device that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means
there is no electrical shock hazard, and the device is easily accessible.
CLEANING
When disconnected, the device may be cleaned with a cloth moistened with
distilled water.
LIABILITY
To the extent the instructions in this manual are not strictly observed, the
customer cannot advance a demand against PR electronics A/S that would
otherwise exist according to the concluded sales agreement.
HOW TO DEMOUNT SYSTEM 9000
Picture 1:
By lifting the bottom lock, the device
is detached from the DIN rail.

9113 - Product Version 9113-004 5
TEMPERATURE / mA CONVERTER
9113
• Input for RTD, TC and mA
• Active / passive mA output
• 1 or 2 channels
• Can be supplied separately or installed on power
rail, PR type 9400
• SIL 2-certified via Full Assessment
Advanced features
• Configurationandmonitoringbywayofdetachabledisplayfront(PR4501);
process calibration and signal simulation.
• Copyingoftheconfigurationfromonedevicetoothersofthesametypevia
the display front.
• TCinputscanuseeithertheinternalCJCoraterminalwithabuilt-inPt100
sensor (PR 5910Ex, channel 1 / PR 5913Ex, channel 2) for higher accuracy.
• Thedeviceautomaticallydetectswhetheritmustsupplyanactiveorapassive
current signal.
• Advancedmonitoringofinternalcommunicationandstoreddata.
• SIL2functionalityisoptionalandmustbeactivatedinamenupoint.
Application
• Thedevicecanbemountedinthesafeareaandinzone2/cl.1div.2and
receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/
III, Div. 1, Gr. A-G.
• Conversionandscalingoftemperature(Pt,NiandTC)andactivecurrent
signals.
• The9113hasbeendesigned,developedandcertifiedforuseinSIL2
applications according to the requirements of IEC 61508.
Technical characteristics
• 1greenand2redfrontLEDsindicateoperationstatusandmalfunction.
• 2.6kVACgalvanicisolationbetweeninput,outputandsupply.

mA
mA
mA
mA
*
*
-
+
-
+
+
+
-
+
-
+
44
43
42
41
44
43
42
41
14
13
12
11
31
32
33
34
54
53
52
51
6 9113 - Product Version 9113-004
APPLICATIONS
Input signals:
Rail, +24 VDC
Rail, Gnd.
Power rail
Error signal
Analogue, 0/4...20 mA
Output signals:
Device status
Device status
Gnd.
Supply +19.2...31.2 VDC
N.C.
Power connection:
*Orderseparately:CJC
connetor 5910Ex/5913Ex
Zone 2 / Cl. 1, div. 2, gr. A-D or safe area
No connection
No connection
Channel 2:
Supply via
power rail
RTD
Connection,
wires
Current
TC
2-wire supply -
2-wire supply -
Ch. 1:
Ch. 2:
*Orderseparately:CJC
connetor 5910Ex/5913Ex
Zone 0, 1, 2,
20, 21, 22, M1 &
Cl. I/II/III, Div. 1
gr. A-G
Channel 1:
RTD
Connection,
wires
Current
TC

9113 - Product Version 9113-004 7
PR 4501 DISPLAY / PROGRAMMING FRONT
Functionality
The simple and easily understandable menu structure and the
explanatory help texts guide you effortlessly and automatically
through the configuration steps, thus making the product very
easy to use. Functions and configuration options are described
in the section ”Configuration / operating the function keys”.
Application
• Communicationsinterfaceformodificationofoperationalparametersin9113.
• Canbemovedfromone9113devicetoanotheranddownloadthe
configuration of the first unit to subsequent units.
• Whenmountedintheprocess,thedisplayshowsprocessvaluesanddevice
status.
Technical characteristics
• LCDdisplaywith4lines;Line1(H=5.57mm)showsinputstatus,line2and3
(H=3.33mm)showanalogueinput/outputvalueorTAGno.andunits,andline
4 shows status for communication and whether the device is SIL-locked. Static
dot=SIL-lockedandflashingdot=notSIL-locked.
• Programmingaccesscanbeblockedbyassigningapassword.Thepassword
is saved in the device in order to ensure a high degree of protection against
unauthorised modifications to the configuration.

OK
4501
1
3
4
2
3
8 9113 - Product Version 9113-004
MOUNTING / DEMOUNTING THE PR 4501/4511
1: Insert the taps of 4501/4511 into the holes at the top of the device.
2: Swing 4501/4511 into place.
Demounting of 4501/4511
3: Push the release button on the bottom of 4501/4511 and swing 4501/4511
up
Este manual sirve para los siguientes modelos
3
Tabla de contenidos
Otros manuales de Convertidor de medios de PR

PR
PR 9116 Series Guía del usuario

PR
PR PREASY 4222 Hoja de instrucciones

PR
PR 9113 Series Manual de usuario

PR
PR 5225 Manual de usuario

PR
PR PRecon 5223 Manual de usuario

PR
PR 9116 Series Manual de usuario

PR
PR 9113 Series Guía del usuario

PR
PR 6 MM Series Manual de usuario

PR
PR 3100 Series Manual de usuario

PR
PR 9116 Series Manual de usuario