Polyaire Zonemaster Unipoint RF Manual de usuario

UNIPOINT RF DAMPER CONTROL SYSTEM
Owner’s Manual & Setup Guide

Liability
Please read the instructions before installing this Zonemaster Zoning Control System.
Polyaire Pty Ltd does not accept any responsibility for loss or damage that may occur as
a result of the installation of this Zoning Control System.

Page 1
OWNERS MANUAL Page 2
1) Remote handset layout Page 2
2) Manual on/off control mode Page 2-3
3) Programming mode – on/off time control Page 3
a) Set time and day Page 4
b) Adjust program time Page 4-5
c) Select a program for a particular zone Page 5
4) Safety/spill system Page 6
5) Turbo feature Page 6
6) Information sheet Page 7
SETUP GUIDE Page 8
1) Features Page 8
2) Application Page 8
3) Components Page 9
4) Conguration Page 10
5) Spill/bypass modes air setpoint Page 11
6) Installation Page 12
a) Zone address and allocation Page 12
b) Initiating and exiting the setting process Page 13
c) Setting system code Page 13-14
d) Number of zones in the system Page 14
e) Supply air safety high & low limits Page 14
f) Turbo Page 15
g) Naming zones Page 15
h) Balancing zones Page 16
i) Damper on/off test Page 16
6) Information sheet Page 17
7) Troubleshooting guide Page 17
8) Specications Page 18
INDEX

ZONEMASTER UNIPOINT RF DAMPER CONTROL SYSTEM - Owner’s Manual Page 2
1) Remote handset layout
The remote handset has a LCD screen with nine buttons as shown in
Figure 1. The LCD screen will normally display clock time, Zonemaster RF
logo and the battery status.
2) Manual on/off control mode
In sleep mode, as shown on the right gure, there
are two ways to enter into zoning mode. The rst
way is to press or button; the other one is
to press button to get into the function
selection mode, and then press button again
after selecting zoning by using or button.
1) In Zoning mode, the handset displays zone
name and the on/off status of up to six zones
as shown on the right gure.
2) Use the or button to select a zone to be
controlled. The on/off status of the zone will be
highlighted.
3) Press button to turn the zone on or off.
The zone will be changed from ON to OFF or
vice versa.
OWNERS MANUAL
FIGURE 1

ZONEMASTER UNIPOINT RF DAMPER CONTROL SYSTEM - Owner’s Manual Page 3
4) NOTE: The action will not happen immediately.
The RF signal will be sent to the main control
module by pressing button, and the damper
of the selected zone will then change its status.
5) Repeat step 2) to 4) to select another zone to turn
it on or off.
6) Pressing button will exit the zoning mode.
Alternatively, it will return to the sleep mode itself
in 15 seconds with no key being pressed.
3) Programming mode - On/off time control
Programmable on/off time control for each zone is an important feature of
the Zonemaster UniPoint RF system. This system has a 5-1-1 program
capability that means the system has an individual program for weekdays
(Monday to Friday), Saturdays and Sundays respectively.
The system allows you to create 4 separate programs and then allocate
any one of these to each of the (up to 8) zones.
Each of the 4 main programmes has 4 sub-programmable events per day:
On time 1, Off time 1, On time 2 and Off time 2. Each program event can
be enabled/disabled and their times can be adjusted as desired. All 4 sets
of sub-programs are disabled in the factory default with identical settings
as listed in the following table.
On time 1 Off time 1 On time 2 Off time 2
Monday to Friday 6.30AM 8.00AM 5.30PM 10.00PM
Saturday 7.30AM 12.30PM 6.00PM 11.30PM
Sunday 7.30AM 12.30PM 6.00PM 11.30PM

ZONEMASTER UNIPOINT RF DAMPER CONTROL SYSTEM - Owner’s Manual Page 4
3a) Set time and day
1) Press the button once to enter into the
‘Function’ Screen.
2) Use the or button to select the ‘Clock’,
and then press button to enter into the sub
menu of the clock setting.
3) Use and button to select hours, minutes
and weekdays. Press and button to
change hours, minutes and weekdays.
4) Pressing button can exit the clock and
week setting mode. Alternatively, it will return to
the sleep mode itself in 15 seconds with no key
being pressed.
3b) Adjust program time
1) Press the button once to enter into the
‘Function’ Screen.
2) Use the or button to select the program
to be modied, and then press button to
enter into its sub menu.
3) Use the or button to select Monday-Fri
day, Saturday or Sunday program. Then press
button to enter into its sub menu.
4) Press button to enable the setting for
ON/OFF times. The LCD will show the start
time of the rst turning on event of the
program.
5) Press and button to change its ON1
settings.
6) Press the or button to select other
ON/OFF settings. Follow steps 4) to 5) to set
the off time or disable the event.

ZONEMASTER UNIPOINT RF DAMPER CONTROL SYSTEM - Owner’s Manual Page 5
7) Press the button to go back to program
setting menu.
8) Follow steps 3) to 6) to set the off time or disable
the event for other times in the program.
9) Repeat steps 2) to 8) to set all the time for the
other programs.
10) Pressing button can exit the clock and
programming mode. Alternatively, it will return to
the sleep mode itself in 15 seconds with no key
being pressed.
3c) Select a program for a particular zone
The various zones should have been given names
by your installer that correspond with the particular
rooms in your house. If this has not happened call
your installer to get this rectied.
1) Make sure that at least one of the four
programs is enabled by setting up all the
parameters in the program.
2) Press the button to get into zoning screen,
and then press or button to select the
zone.
3) Use and button to select the enabled
program. The program will be shown at the
bottom of the screen.
4) Repeat steps 2) and 3) to choose programs for
other zones.
5) Pressing button can exit the zone operation
mode. Alternatively, it will return to the sleep mode
itself in 15 seconds with no key being pressed.

ZONEMASTER UNIPOINT RF DAMPER CONTROL SYSTEM - Owner’s Manual Page 6
4) Safety/spill system
The RF UniPoint has a built in safety system to protect
against all the dampers being shut off together
(Causing duct blow off due to high air pressure or more
serious problems).
Your installer will set this for you. Usually it will be set so
20-30% of the dampers will remain open. These will
usually be low numbered zones close to the return air duct
(Zones 1 or 2) that open into frequently used space.
5) Turbo feature
The RF UniPoint allows one zone to be selected as the
‘Turbo’ zone. This will usually be a zone which might
require heavy airow at certain times (due to a rapid inux
of people). The family/dining/games room are examples.
‘Turbo-ing’ a zone will give the zone a full opening while all
the other zones opening positions are reduced by 50%.
This will bring extra air into the zone.

ZONEMASTER UNIPOINT RF DAMPER CONTROL SYSTEM - Owner’s Manual Page 7
PROGRAM 1 On time 1 Off time 1 On time 2 Off time 2
Monday to Friday
Saturday
Sunday
6) Information sheet
Use the following tables to record your settings
PROGRAM 2 On time 1 Off time 1 On time 2 Off time 2
Monday to Friday
Saturday
Sunday
PROGRAM 3 On time 1 Off time 1 On time 2 Off time 2
Monday to Friday
Saturday
Sunday
PROGRAM 4 On time 1 Off time 1 On time 2 Off time 2
Monday to Friday
Saturday
Sunday

ZONEMASTER UNIPOINT RF DAMPER CONTROL SYSTEM - Setup Guide Page 8
SETUP GUIDE
1) Features
• Supports up to 8 zones.
• All dampers are directly connected to the main controller.
• RF remote control handset.
• Manual and time programmable zone on/off control.
• LCD indicator on the handset for zone status and
parameter display.
• Personalised zone labelling.
• 5-1-1 programmable on/off time programs.
• Automatic zone balancing --- each zone’s opening
position can be programmed for balancing purpose.
• One selectable turbo zone.
• Auto spill/bypass --- the designated zones/bypass are
forced open when all zones are turned off.
• Safety system --- Opens all dampers if the supply air
temperature is less than low limit or more than high limit.
• All zones automatically return their original on/off state
once power up.
2) Application
Zonemaster UniPoint RF control system is a fully featured
and engineered system that is well suited to all ducted, reverse
cycle, heating and evaporative air conditioning system for light
commercial, residential or apartment applications.