Pittway System Sensor PDRP-1001 Manual de usuario

PDRP-1001/PDRP-1001A
DELUGE ■■
■■
■PREACTION CONTROL PANEL
Doc.# 50734 ECN 97-514
ZONE 1
ZONE 2
WATERFLOW
SUPERVISORY
AC POWER
SYSTEM ALARM
RELEASE
SUPERVISORY
SYSTEM
TROUBLE
TONE
SILENCE ALARM
SILENCE ALARM
ACTIVATE RESET
CIRCUIT
TROUBLE
POWER
TROUBLE
ALARM
SILENCED
A Pittway Company

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97
2

PDRP-1001/PDRP-1001A Document 50734 RevB 12/21/97
3
Table of Contents
I NFPA Standards ..............................................................4
II Additional Information ...................................................4
1.0 The PDRP-1001/PDRP-1001A .......................................................5
1.1 Features........................................................................................................ 5
1.2 Circuits.......................................................................................................... 5
1.3 Optional Boards ............................................................................................ 7
1.4 Remote Annunciator ..................................................................................... 8
1.5 Optional Meters............................................................................................. 8
1.6 Specifications................................................................................................ 9
2.0 System Operation .........................................................................11
2.1 System Status LEDs ................................................................................... 11
2.2 Control Switches......................................................................................... 12
2.3 Zone Status LEDs....................................................................................... 12
2.4 Supervisory................................................................................................. 13
2.5 Zone Disable .............................................................................................. 13
2.6 Last Event Recall........................................................................................ 13
3.0 Installation Procedure ..................................................................14
3.1 General ....................................................................................................... 14
3.2 Initiating Device Circuits ............................................................................. 15
3.3 4-Wire Smoke Detector Connections.......................................................... 16
3.4 Output Circuits ............................................................................................ 17
3.5 Power.......................................................................................................... 18
3.6 Optional Modules........................................................................................ 20
3.7 Dip Switch Location and Descriptions ........................................................ 25
3.8 Setting Mode of Operation .......................................................................... 26
Appendix A: Power Calculations......................................................27
Appendix B: Device Compatibility Chart .........................................29
Appendix C: NFPA Standard Specific Requirements ....................33
Troubleshooting Table ........................................................................38

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97
4
INFPA Standards
This control panel complies with the following NFPA standards:
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA16Foam-WaterDelugeandFoam-WaterSpraySystems
NFPA 72 Central Station Signaling Systems (Automatic, Manual, and Waterflow). Protected
PremisesUnit(RequiresNOTI-FIRE911ACDACTorMS5012SlaveCommunicator).*
NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems.
NFPA 72 Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm Systems. (Requires 4XTM.)
NFPA 72 Remote Station (Automatic, Manual, and Waterflow) Fire Alarm Systems. (Requires
4XTM or NOTI•FIRE 911AC DACT.) *
* Applications which require the NOTI-FIRE 911AC is not FM approved.
II Additional Information
Note: Before proceeding, the installer should be familiar with the following documents and standards:
NFPAStandards:
NFPA 13 Installation of Sprinkler Systems
NFPA 15 Water Spray Fixed Systems
NFPA16DelugeFoam-WaterSprinklerandFoam-WaterSpraySystems
NFPA 72 Installation, Maintenance, and Use of Central Station Signaling Systems
NFPA 72 Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems
NFPA 72 Automatic Fire Detectors
NFPA 72 Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems
NFPA 72 Testing Procedures for Signaling Systems
UnderwritersLaboratoriesDocuments:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Alarm Systems
UL 268 Smoke Detectors for Fire Alarm Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Alarm Systems
UL464AudibleSignalingAppliances
UL 521 Heat Detectors for Fire Alarm Systems
UL 864 Standard for Control Units for Fire Alarm Systems
UL 1481 Power Supplies for Fire Alarm Systems
UL1638 VisualSignalingAppliances
UL1971SignalingDevicesfortheHearingImpaired
CAN/ULC-S524-M91Standard forInstallationof FireAlarmSystems
CAN/ULC-S527-M87StandardforControlUnitsforFireAlarmSystems
Other:
NECArticle300WiringMethods
NEC Article 760 Fire Alarm Systems
ApplicableLocalandStateBuildingCodes
Requirementsof the Local AuthorityHavingJurisdiction
NotifierDeviceCompatibilityDocument,15378.
ADA Americans with Disabilities Act

PDRP-1001/PDRP-1001A Document 50734 RevB 12/21/97
5
1.0 ThePDRP-1001/PDRP-1001A
1.1 Features
• Microprocessor-controlled
• Alarmandtroubleresound
• Four Style B/D Initiating Device Circuits
• Two Style Y/Z Notification Appliance Circuits
• Two Style Y Release Circuits
• Generalalarmandtroublerelays
• Optionalmodulefor4zone/functionrelays(4XZM)
• Optional transmitter module (4XTM). Complies with
NFPA 72 Auxiliary and Remote Station Fire Alarm
Systems.
• Optionalvolt/ampmetermodule(4XMM)
• Optionalsupervisedremoteannunciator
(RZA-4X). RequiresLEDInterfaceModule(4XLM)
• Optionaldigitalcommunicator(NOTI•FIRE911AC).*
• ComplieswithNFPA72CentralStationandNFPA72
Remote Station Fire Alarm Systems.
• DesignedforsprinklerstandardsNFPA13,15,and16.
• Disable/enablecontrolsperinitiatingzone.
• Last Event Recall
• Battery/Earthfault supervision
• Fuseprotection on all Notification/Release Circuits
• RMSregulatedoutputpower,2.25amps
• 7amp/hourto15amp/hourbatteryoptions,
up to 90 hours standby
• Resettable and non-resettable regulated
poweroutputs
• Extensivetransient protection
• Watchdog timer to supervise microproces-
sor(includes MICRO FAIL LED)
• Output circuits protected against false
activations.
• Slide-inzoneidentification labels
• Steel cabinet 14.5" wide by 16" high by 5"
deep
• Dead-frontdresspaneloption(DP-4X)
• Trimringforflushmountbetween16"center
studs(TR-4XR)
• Cross-zone(double-interlock)option
• Municipal Box output.
• InterfaceModule(4XLM)
• Dualhazardoperation
• Adjustabledischargetimer
* Applications which require the NOTI-FIRE 911AC is not FM approved.
1.2 Circuits
Input Circuits
Manual Release/Detector Circuit 1 (Style B/D)
Detector Circuit 2 (Style B/D)
Waterflow (Style B/D)
Supervisory (Style B/D)
Output circuits (optional auxiliary relay module (4XZM) tracks these four circuits)
Alarm/Waterflow Bell (Style Y/Z)
Waterflow/Supervisory Bell (Style Y/Z)
Releasing Circuit 1 (Style Y)
Supervisory Bell/Release Circuit 2 (Style Y)
Front Panel Control Switches
Switch 1 Tone Silence
Switch 2 Alarm Silence
Switch 3 Alarm Activate
Switch 4 System Reset

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97
6
Figure 1.0-1: PDRP-1001/PDRP-1001A Installation Diagram

PDRP-1001/PDRP-1001A Document 50734 RevB 12/21/97
7
1.3 Optional Boards
The PDRP-1001/PDRP-1001A has mounting slots for two option boards. Any two of the three option
modules may be installed.
TransmitterModule(4XTMNOTIFIER)
The Transmitter Module provides a supervised output for local energy
municipalbox transmitter (for NFPA72-1993Auxiliary Fire Alarm System)
and alarm and trouble reverse polarity circuits (for NFPA 72-1993 Remote
StationFireAlarmSystem). AlsoincludedisaDISABLEswitchanddisable
troubleLED.
Asajumperoption,the alarm reversepolaritycircuitwillopen on troubleifnoalarm
exists.
LEDInterfaceModule(4XLMNOTIFIER)
The LED Interface Module supports the RZA-4X Remote Annunciator
module.Annunciatorwiringissupervisedforopenconditionsbythismodule.
TheAnnunciatorDriverModulemountstothemainboard,occupyingoneof
the two option connectors.
ZoneRelay Module (4XZMNOTIFIER)
TheZone Relay module provides Form-Ccontactsfor the following:
• Alarm/WaterflowBell
• Waterflow/SupervisoryBell
• ReleasingCircuit1
• SupervisoryBell/Release Circuit2
• System Alarm
• SystemTrouble
As a jumper option, the first four relays described above can be made silenceable.

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97
8
LEDInterfaceModule(4XLMNOTIFIER)
Maximumvoltage/current,eachoutput:27.6V/8mA.
Note: Outputs are power limited.
ZoneRelay Module (4XZMNOTIFIER)
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
1.4 Remote Annunciator
RemoteAnnunciator(RZA-4XNOTIFIER)
TheRemoteAnnunciatormountsonastandardsingle-gangbox,andprovidesLED
indication of the following:
•Alarm/WaterflowBell(red)
•Waterflow/SupervisoryBell(red)
•ReleasingCircuit1(red)
•SupervisoryBell/ReleaseCircuit2(red)
•SystemTroubleLED(yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is
supervised for open conditions. Any open condition will cause the System Trouble
LED to illuminate.
Note: The Remote Annunciator requires the use of an LED Interface module (4XLM).
1.5 Optional Meters
Voltage,CurrentMeters (4XMM NOTIFIER)
The Meter Module provides a voltmeter to measure the voltage across the
batteriesandanammetertomeasurethechargingcurrenttothe batteries.The
meters are provided as a assembly that mounts to the lower left corner of the
cabinet.
TransmitterModule(4XTMNOTIFIER)
For Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System)
Supervisory current: 5.0 mA.
Tripcurrent: 0.35 amps(subtractedfromNotification Appliancepower).
CoilVoltage: 3.65 VDC.
Coil resistance: 14.6 ohms.
Maximum allowable wire resistance between panel and trip coil: 3 ohms.
Municipal Box wiring can leave the building.
ForRemote Stationservice (NFPA72 RemoteStation FireAlarmSystem):
Maximum load for each circuit: 10 mA.
Reverse polarity output voltage: 24 VDC.
RemoteAlarm andRemoteTrouble wiringcanleave thebuilding.

PDRP-1001/PDRP-1001A Document 50734 RevB 12/21/97
9
AC Circuit
Breaker
1.6 Specifications
ACPower
ForPDRP-1001/PDRP-1001A:120VAC,50/60Hz,1.2amps
Wire size: minimum #14 AWG with 600V insulation
Battery(leadacidonly)
Maximum Charging Circuit: 27.6V, 1.5 amps
Maximum Battery Capacity: 15 AH. (Batteries larger than 12 AH require Notifier
#BB-17 or other UL listed battery cabinet.)
InitiatingDeviceCircuits
Power-limitedcircuitry
Operation: Style B (Class B)/ Style D (Class A)
NormalOperatingVoltage: 24VDC (ripple=1.0Vpeak-to-peak)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 200 ohms
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252 UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisorycurrent:5mA(includingend-of-lineresistor)
NotificationApplianceandReleasingCircuits
Power-limitedcircuitry
Maximumallowablevoltagedropduetowiring:2VDC
NormalOperatingVoltage: 24VDC
Total current available to all external devices: 2.25 amps.
Maximum signaling current per circuit: 1.5 amps
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252 UL listed)
Alarmand TroubleRelays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
All relays must be connected to a power-limited power supply.
Four-wireSmokeDetectorPower
Up to 200 mA is available for powering 4-wire smoke detectors.
Maximum ripple voltage: 1.0 V p/p
Non-resettablePower
TotalDC currentavailablefromthis outputisupto 200mA(subtractedfrom four-wiresmokepower).
Maximum ripple voltage: 1.0 V p/p
RMSRegulatedPower
Total DC current available for powering external devices is 0.5 amp (subtracted from 2.25
amps available to notification appliance circuits).
Maximum ripple voltage: 100 mV p/p
Note: For device compatibility data, refer to the Device Compatibility Chart, Appendix B.
P1 P2 P3 P4
Output Circuit PTCs

PDRP-1001/PDRP-1001A Document 50734 Rev B 12/21/97
10
Cabinet = 5.375"
Backbox = 4.750"
Door = 16.125"
Backbox = 16"
Door = 14.625"
Backbox = 14.5"
Figure 1.6-1: Cabinet Dimensions
OptionalTrimRing
TR-4XR