Pavone Systems MCT 1302 Manual de usuario

PAVONESYSTEMS
TECHNICAL MANUAL
MCT 1302 Touch screen batching version with RS232 serial, analog and Fieldbus
output Software version PW1507

Page II

Rel ID 19230101 SW 1.1
Page 1
TABLE OF CONTENTS
PRECAUTIONS.............................................................................................. Page 2
INTRODUCTION ........................................................................................... Page 3
TECHNICAL FEATURES................................................................................... Page 5
INSTALLATION .............................................................................................. Page 5
FRONT PANEL OF THE INSTRUMENT .............................................................. Page 16
MAIN SCREEN.............................................................................................. Page 17
INFO DISPLAY ............................................................................................... Page 19
OPERATING FUNCTIONS .............................................................................. Page 20
BATCHING RECIPES SELECTION ..................................................................... Page 22
MENU STRUCTURE ........................................................................................ Page 26
USER MENU ................................................................................................. Page 27
BATCHING PARAMETERS MENU..................................................................... Page 35
HARDWARE TEST MENU................................................................................ Page 39
INPUT/OUTPUT MENU .................................................................................. Page 40
ACCESSING THE SETUP................................................................................. Page 41
CALIBRATION................................................................................................ Page 42
ANALOG OUTPUT PARAMETERS..................................................................... Page 47
SERIAL OUTPUT PARAMETERS......................................................................... Page 48
WEIGHING PARAMETERS .............................................................................. Page 56
FILTER PARAMETERS ....................................................................................... Page 57
WORKING MODE PARAMETERS..................................................................... Page 59
TIME AND DATE MENU, DISPLAY CONTRAST MENU........................................ Page 62
UPLOAD/DOWNLOAD FUNCTION ................................................................ Page 63
SERIAL COMMUNICATION PROTOCOLS ........................................................ Page 64
FIELDBUS PROTOCOLS .................................................................................. Page 75
TROUBLESHOOTING ..................................................................................... Page 80

Page 2
PRECAUTIONS
READ THIS MANUAL BEFORE using or servicing the instrument.
FOLLOW these instructions carefully.
KEEP this manual for future use.
CAUTION
The purpose of this manual is to make the operator aware of the
texts and explanatory figures, the basic requirements and criteria
for the installation and correct use of the instrument.
Installation, maintenance and repair must carried be out only by
specialized personnel who must have read and understood this ma-
nual. “Specialized personnel” means personnel who, due to training
and professional experience, have been expressly authorized by the
System Safety Manager to perform the installation.
Supply the instrument with voltage whose value is within the limits
specified in the specifications.
It is the user’s responsibility to ensure that the installation complies
with the applicable regulations.
Any attempt to disassemble or modify the instrument not expressly
authorized will invalidate the warranty and relieve Pavone Sistemi
of any responsibility.
The installation and maintenance of this instrument should only be
permitted by qualified personnel.
Pay attention when checking, testing, and adjusting with the instru-
ment turned on.
Make the electrical connections in the absence of the power supply
voltage.
Failure to observe these precautions may result in danger.
DO NOT ALLOW untrained personnel to work, clean, inspect, repair
or tamper with this instrument.

Page 3
INTRODUCTION
The MCT 1302 is a touch screen weight indicator and batcher to be combined with load cells to meet
the industrial applications.
The instrument is installed in a frame in a slot having a drilling template of 138 x 53 mm and is secured
by means of the 2 tensioning screws supplied.
The MCT 1302 uses the RS232 serial port with ASCII protocols, to be connected to the PC, PLC and re-
mote units with a maximum distance of 15m beyond which it is necessary to use the RS422/RS485 serial
output that allows the connection also with MODBUS RTU protocol up to 32 addressable instruments.
The availability of the most popular field buses, as an alternative to the RS485 port, also allows inter-
facing the instrument with any supervision device currently offered by the market.
A USB 2.0 port is also available and facilitates interfacing with PCs using AN Utility Software available
in the kit.
6 digital inputs and 6 digital outputs configurable by Set-up are always available.
It is also possible to have the analog output in voltage or current even in the presence of the FIELDBUS.
Available versions:
• MCT 1302: weight indicator with RS232 serial output, USB, RS485. The supported protocols are
continuous Modbus RTU.
• MCT 1302/A: version with analog output.
• MCT 1302/PROFINET: weight indicator with RS232, USB and PROFINET serial output.
• MCT 1302/ETHERNET IP: weight indicator with RS232, USB and ETHERNET IP serial output.
• MCT 1302/ETHERCAT: weight indicator with RS232, USB and ETHERCAT serial output.
• MCT 1302/PROFIBUS: weight indicator with RS232, USB and PROFIBUS serial output.
The analog output can also be present with the FIELDBUS option

PAVONE SISTEMI
Page 4
IDENTIFICATION PLATE OF THE INSTRUMENT
It is important to communicate this data, in case of request for information or indications concerning
the instrument, together with the program and version number, shown on the cover of the manual and
displayed when the instrument is switched on.
WARNINGS
The procedures listed below must be performed by specialized personnel.
All connections must be made when the instrument is switched off.

Page 5
TECHNICAL FEATURES
Power supply 18÷30 Vdc
Max. absorption 5 W
Isolation Class II
Installation category Cat. II
Working temperature -10°C ÷ +50°C (Max. humidity 85% without
condensation)
Storage temperature -20°C ÷ +70°C
Display Graphic 240x128 pixel LCD
Keyboard 4 wire resistive touch screen
Overall dimensions 150 x 95 x 26 mm (l x h x w) including terminal
blocks
150 x 95 x 56 mm (l x h x w) with FIELDBUS option
Drilling template: 138 x 82 mm
Assembly Panel Mount
Case material Aluminum
Connections Removable screw terminal blocks, 3.81 pitch.
Load cell power supply 5 Vdc/120 mA (max. 8 cells of 350 in parallel)
protected against short circuit
Input sensitivity 0.02 µV min.
Linearity < 0.01% of the full scale
Temperature drift < 0.001% of the full scale / C°
Internal resolution 24 bits
Displayed weight resolution Up to 999,999 divisions on the payload
Measuring range From -3.9 mV/V to +3.9 mV/V
Weight acquisition frequency 12 Hz - 1000 Hz
Digital filter Selectable 0,1 ÷ 250 Hz
Weight decimal number from 0 to 4 decimal places
Zero and Full Scale Calibration Automatic (theoretical) or executable from the
keyboard.
Logic outputs 6 opto-insulated (dry contact) max 24 Vdc / 100 mA
each
Logic inputs 6 opto-insulated at 24 Vdc PNP (external power
supply)
Serial port (#2) RS232C and RS422/485
Maximum cable length 15 m (RS232C) and 1000 m (RS422 and RS485)
Serial protocols ASCII, Modbus RTU
Baud rate 1200, 2400, 4800, 9600, 19200, 38400, 57600,
115200 selectable
USB port: compliant with USB 2.0; speed up to 12 Mbps
Analog output (optional) 16-bit opto-insulated
Voltage: 0 ÷ 5/10 V (R min 10 KOhm),
Current: 0/4 ÷ 20 mA (R max 300 Ohm)
Analog output calibration From the keyboard
Linearity <0.02% FS
Thermal drift 0.001% FS/°C
Microcontroller: ARM Cortex M0 + 32 bit, 256 KB Flash
reprogrammable on-board from USB.
Data memory 64 Kbytes expandable up to 1024 Kbytes
Fieldbus (as an alternative to RS485) PROFINET, ETHERNET IP, ETHERCAT, PROFIBUS
Compliance with Standards EN61000-6-2, EN61000-6-3, EN61010-1,
EN45501

Rmax 2
82±1
138±1
94
149
80
136
52
5.0
20
30
149
94
MCT 1302
Page 6
INSTALLATION
GENERAL INFORMATION
The MCT 1302 is a compact panel mounting instrument made of aluminum.
The instrument is installed in a panel in a slot with a drilling template of 138 x 82 mm and is secured
by means of the 2 tensioning screws supplied.
The MCT 1302 must not be immersed in water, subjected to jets of water and cleaned or washed with
solvents.
Do not expose to heat or direct sunlight.
Do not install the instrument near power equipment (motors, inverters, contactors, etc.) or near devices
that do not comply with CE regulations for electromagnetic compatibility.
The connection cable for the load cells must have a maximum length of 140 m/mm².
The RS232 serial line must have a maximum length of 15 meters (EIA RS-232-C standards).
The warnings given on the connection of the individual peripheral devices must be observed.
OVERALL DIMENSIONS

237
146
202
32
169
20
68
37
M4
113
62
Page 7
MCT S 1302 DIMENSIONS

+
-
10÷30 Vdc
GND
123456789
1 2 3 4 5 6 7 8 9 15 16 17 18 19 20 21 22 2310 11 12 13 14 24 25 26
1 2 3 4 5 6 7 8 9 10 11 12 13 14
In 1
In 2
In 3
In 4
In 5
In 6
I Com
Out 1
Out 2
Out 3
Out 4
Out 5
Out 6
O Com
-Sig2
+Sig2
+Sig1
-Sig1
-Sense
+Sense
+Exc
-Exc
Shield
123456789
N.6 INPUTS N.6 OUTPUTS
LOAD CELL 1LC2
&
2008/ 9 5/ EC
USB
Device
17 18 19 20 21 22 23 24 25 26
TXD
RXD
SGND
S I/O +
S I/O -
AGND
Vout+
Iout+
+Vdc
GND
SERIAL Power
Supply
AN.
+
-
EXC-
EXC+
SENSE+
SENSE-
SIG-
SIG+
SHIELD
OUTPUTS
30 Vdc
100 mA Max
OUTPUT 2
OUTPUT 1
COM. OUTPUT
V+ (10 kΩ min)
Ana-
mA+ (300 Ω max)
RS485
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
COM. INPUT
INPUT 1
OUTPUT 3
OUTPUT 4
OUTPUT 5
OUTPUT 6
TX-/RX-
TX+/RX+
ANALOG
OUTPUT
24 Vdc
100 mA Max
RS232
RXD
TXD
SGND
OPTIONAL
OUTPUT
OPTIONAL ETHERNET
FIELDBUS
+
-
25 +Vdc
Power Supply
24 Vdc
26 GND
Screw
Page 8
ELECTRICAL INSTALLATION
The MCT 1302 instrument uses for the electrical connection of the 3.81 mm removable screw terminal
blocks. The load cell cable must be shielded and channeled away from power cables to avoid elec-
tromagnetic interference.
The field wiring of the instrument must be suitable for the environment in which it will be used
and must comply with all national regulations.
A switch or disconnector must be included in the electrical system.
The switch must be close to the instrument and easily reachable by the operator.
The switch must be marked as a device to stop the machine.
The switch or circuit breaker used as a disconnecting device must comply with the applicable require-
ments of IEC 60947-1 and IEC 60947-3.
WARNING
Disconnect the power supply to the instrument before making electrical connections.
POWER SUPPLY OF THE INSTRUMENT
The instrument is powered through terminals 25 and 26. The power cable must be routed separately
from other cables.
The electric zero (terminal 26) is connected to the metal case. Connect
the terminal 26, in addition to the GND of the power supply, also
on the ground using the screw near the power terminals.
Supply voltage: 18÷30 Vdc, max 5W