Numens 6002 Manual de usuario

www.numens.com
6002 Addressable Fire Alarm Control and
Indicating Equipment
Revision 1.0.1 Firmware
USER MANUAL

www.numens.com

6002 addressable control and indicating equipment
Installation and Service Manual
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
Contents
1. CONTROLS AND INDICATORS ................................................................................................................ 1
2. ACCESS LEVELS ...................................................................................................................................... 4
2.1. Access Level 1 ................................................................................................................................... 4
2.2. Access Level 2 (User Access) ........................................................................................................... 4
2.3. Access Level 3 (Installer Access) ...................................................................................................... 5
2.4. Access Level 4 (Engineer Access) .................................................................................................... 5
3. CONDITIONS ............................................................................................................................................. 6
3.1. Quiescent Condition .......................................................................................................................... 6
3.2. Alarm Condition ................................................................................................................................. 6
3.3. Actions During the Alarm Condition ................................................................................................... 6
3.4. Fault Condition ................................................................................................................................... 7
3.5. Actions During the Fault Condition .................................................................................................... 8
3.6. Disabled Condition ............................................................................................................................. 8
3.7. Test Condition ................................................................................................................................... 11
3.8. System Reset .................................................................................................................................. 12
4. TROUBLE SHOOTING GUIDE ................................................................................................................ 13
4.1. General Fault Indicator .................................................................................................................... 13
5. GLOSSARY AND REFERENCES ............................................................................................................ 14
6002 addressable control and indicating equipment forms the central part of a fire
detection and alarm system. 6002 is available with 2 addressable loops. The
control and indicating equipment is easy to install and commission. A central
microprocessor delivers reliable operation and requires minimum maintenance.
6002 control and indicating equipment is compatible with Numens addressable
detectors, and other devices, such as manual call points and audio/visual alarm
devices. They are suitable for small and medium-sized buildings.
This Manual provides users with instructions to operate the 6002 control and
indicating equipment using revision 1.0.1 operating firmware.

6002 addressable control and indicating equipment
Installation and Service Manual
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
Building Name
Building Address
Installation Company
Installation Company Contact
Date Installed
Service Company
Service Company Contact
Website
For more information, including product datasheets and other support material, please view our website at
www.numens.com.

6002 addressable control and indicating equipment
User Manual
1
33-0019-r04_2018-08
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
1. CONTROLS AND INDICATORS
Figure 1 – Controls and main indicators
LCD
Displays the status of the control and indicating equipment and connected
devices.
GENERAL
ALARMS
ACTIVE/SILENCE
Silences and activates audio/visual alarm devices. The LED illuminates when the
alarm devices are active.
If the SILENCE ACTIVATE ALARMS button is pressed when alarm delays are
active, the delay timer will be cancelled and the alarm devices queued for
activation will be silenced. Any subsequent fire events will no longer initiate the
alarm delay timer until the control and indicating equipment has been reset.
DELAYS ACTIVE Disables and enables delays of configured initiating devices and input/output
devices. When the indicator is on, the delay is active. Pressing the DELAYS
ACTIVE button over-rides the delays and causes immediate actions.
LAMP TEST Illuminates all LEDs, LCD segments and activates the internal sounder.
SYSTEM RESET Resets the fire detection and alarm system.
BUZZER SILENCE
Acknowledges a new Alarm or Fault event and silences the internal sounder.
ALPHA-
NUMERIC
KEYPAD
Numeric input controls, used in conjunction with other functions and LCD.
0 ~ 9 Access Level passcode. Used to input device descriptions.
+ Increments the loop number.
- Decrements the loop number.
Alphabetic
characters
Used to input device descriptions.

6002 addressable control and indicating equipment
User Manual
2
31-0019-r04_2018-08
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
STATUS
FIRE Indicates the Alarm Condition. The LED will flash with un-acknowledged alarms
and be on steady when acknowledged.
Alarm zone information will be displayed on the ZONE indicators. Alarm device
information will be displayed on the LCD.
FAULT Indicates the Fault Condition. The LED will flash with un-acknowledged faults and
be on steady when acknowledged.
Fault information will be displayed on the LCD, and depending on the source of
the fault, in the FAULTS area of the control and indicating equipment.
PRE-ALARM Indicates a device is reaching the alarm threshold level. The LED will flash with
un-acknowledged alarms and be on steady when acknowledged.
Pre-alarm information will be displayed on the LCD.
TEST Indicates the Test Condition. The LED illuminates during the Test Condition.
DISABLE Indicates at least one device is disabled.
SUPPLY Indicates power is connected to the control and indicating equipment.
FAULTS
SUPPLY Indicates the mains supply is unavailable. The LED will flash with un-
acknowledged mains supply faults and be on steady when acknowledged.
BATTERY Indicates the standby battery supply or battery charger is faulty. The LED will flash
with un-acknowledged battery faults and be on steady when acknowledged.
SYSTEM Indicates a fault in the central processing unit. The LED will illuminate when a
processing fault or memory fault is detected.
ALARM Indicates when either an alarm zone circuit fault or an addressable audio/visual
alarm device fault is detected. The LED will flash with un-acknowledged alarm
faults and be on steady when acknowledged.
EARTH Indicates an earth fault is detected in the alarm zone transmission path wiring.
The LED will flash with un-acknowledged earth faults and be on steady when
acknowledged.
ZONES
Indicates the Alarm, Fault, Disable and Test Conditions for a specific detection
zone.
NAVIGATION
KEYPAD
Navigation controls, used in conjunction with other functions and LCD.
Increases the selection or number. Used for menu scrolling.
Decreases the selection or number. Used for menu scrolling.
Moves the cursor on the LCD.
Moves the cursor on the LCD.
Confirms the current entry.
Reverses/aborts the current entry or display.

6002 addressable control and indicating equipment
User Manual
3
33-0019-r04_2018-08
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
QUEUE REVIEW
FIRE LED will flash if more than one input device is reporting a fire. Pressing the button
will step through the queue of fire events. Once the queue has been reviewed, the
LED will be on steady. If a new event occurs, the LED will begin to flash. An event
in the queue will be displayed for 20 s, after which time the LCD will display the
first alarm event.
FAULT LED will flash if more than one input device is reporting a fault, or if a fire signal is
also present when a fault occurs. Pressing the button will step through the queue
of fault events. Once the queue has been reviewed, the LED will be on steady. If a
new event occurs, the LED will begin to flash. An event in the queue will be
displayed for 15 s. After this time, the LCD will display the first fault event, or the
fire event if a Fire Condition exists.
TEST LED is on during the Test Condition. Pressing the TEST button will display which
detection zones and which alarm zones are in Test. If the LCD cannot display all
zones, pressing the TEST button again will display the next page of results. A test
event will be displayed for 15 s, after which time the LCD will revert to the default
display.
DISABLE LED will be on if one or more devices are disabled. Pressing the DISABLED
button will step through the queue of disablements. An event in the queue will be
displayed for 15 s, after which time the LCD will revert to the default display.
DISABLEMENTS
SELECTED
DEVICES
Selects specific input devices (detectors, manual call points, input/output
modules) for disablement/enablement. Used in conjunction with KEYPAD and
LCD. The indicator is active when disablements are active.
ALARMS Disables and enables alarm output devices. When the indicator is active, the
alarm devices are disabled.
ALARM RELAY Disables and enables on-board Alarm Condition relay outputs. When the
indicator is active, the output relays are disabled.
FAULT RELAY Disables and enables on-board Fault Condition relay output. When the indicator is
active, the output devices are disabled.

6002 addressable control and indicating equipment
User Manual
4
31-0019-r04_2018-08
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
2. ACCESS LEVELS
Four access levels are used to operate or configure the control and indicating equipment.
2.1. Access Level 1
Access Level 1 is enabled when the CONTROLS ENABLE key switch is on. Access Level 1 provides open
access to perform the following functions:
Acknowledge a new event and silence the internal sounder.
Override any configured active delays in the Alarm Condition.
Alarm, Fault, Test and Disable queue review.
Place the panel into Access Level 2 or Access Level 3.
Perform the indicator test.
2.2. Access Level 2 (User Access)
Access Level 2 provides access to the functions enabled during configuration at Access Level 3 using Menu
Item 7-3-3. The default setting is to deny access to functions.
Typical functions configured for Access Level 2 may include:
Acknowledge a new event (and silence the internal sounder).
Activate and de-activate pre-configured alarm delays.
Perform the indicator test.
Silence and re-active alarms (including for a building evacuation).
Reset the fire detection and alarm system.
Disable or enable the following:
o Zones
o Alarms
o Alarm outputs
o Fault outputs
2.2.1. Enter Access Level 2
To enter Access Level 2, undertake the following actions.
1) Press the
button. The LCD will prompt to enter the Access Level 2 passcode.
2) Enter 1 2 3 4 5.
3) Press the
button to confirm the passcode.
The LCD will display User Access Level and prompts to navigate through the Menu Items.
Access Level 2 allows unlimited input attempts, however the entry sequence must start within 10 s and there
must be no more than 5 s between key presses. If these times are exceed, the control and indicating equipment
will revert to Access Level 1.
2.2.2. Change Access Level 2 Passcode
The Access Level 2 passcode can be changed from the default settings. The Access Level 2 passcode is
configured using the alpha-numeric keypad. To change the Access Level 2 passcode, undertake the following
actions.
1) Enter Access Level 3.
2) Select Menu Item 7-3-2.
3) Use the alpha-numeric keypad to enter a new 5-digit Access Level 2 code.
4) Press
to confirm and return to the menu.

6002 addressable control and indicating equipment
User Manual
5
33-0019-r04_2018-08
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
2.3. Access Level 3 (Installer Access)
Access Level 3 is used to configure the control and indicating equipment and connected devices (see
section 9).
2.3.1. Enter Access Level 3
To enter Access Level 3, undertake the following actions.
1) Press the
button. The LCD will prompt to enter the Access Level 2 passcode.
2) Enter 4 5 6 7 8.
3) Press the
button to confirm the passcode.
The LCD will display Installation Access Level and prompts to navigate through the Menu Items.
Access Level 3 allows unlimited input attempts, however the entry sequence must start within 10 s and there
must be no more than 5 s between key presses. If these times are exceed, the control and indicating equipment
will revert to Access Level 1.
2.3.2. Change Access Level 3 Passcode
The Access Level 3 passcode can be changed from the default settings. The Access Level 3 passcode is
configured using the alpha-numeric keypad. To change the Access Level 3 passcode, undertake the following
actions.
1) Enter Access Level 3.
2) Select Menu Item 7-3-4.
3) Use the alpha-numeric keypad to enter the existing 5-digit Access Level 3 code.
4) Press
to confirm.
5) Enter the new 5-digit Access Level 3 code.
6) Press
to confirm.
7) Confirm the new 5-digit Access Level 3 code.
8) Press
to confirm and return to the menu.
2.4. Access Level 4 (Engineer Access)
Access Level 4 is used to restore the factory default settings, and is rarely required. Where restoration is
required, contact Numens Customer Service.
Changes made at Access Level 3 affect the factory default settings and the
operation of the system. Changes should only be made by qualified personnel who
are fully aware of their effects.
If an Alarm Condition or Fault Condition has occurred, the conditions must be
acknowledged before entering Access Level 3. Access Level 3 can only be accessed
when the control and indicating equipment has no unacknowledged events.

6002 addressable control and indicating equipment
User Manual
6
31-0019-r04_2018-08
© 2017, 2018 Ambest Electronics (Ningbo) Co Ltd. All rights reserved.
All specifications and other information were current at the date of publication and subject to change without notice.
3. CONDITIONS
3.1. Quiescent Condition
The Quiescent Condition is the normal condition for the control and indicating equipment. In the Quiescent
Condition, only the SYSTEM LED is on.
3.2. Alarm Condition
When the control and indicating equipment enters the Alarm Condition, the audio/visual alarm devices and
output modules will operate according to their configuration programming.
Figure 2 – Alarm condition indications
3.3. Actions During the Alarm Condition
3.3.1. Fire Investigation
After the control and indicating equipment enters the Alarm Condition, take the following actions.
1) Insert the key and enable the controls. The CONTROLS ACTIVE LED will be on steady.
2) Enter Access Level 2.
3) Press the
button to acknowledge the Alarm. The FIRE LED will be on steady.
4) Press the BUZZER SILENCE button to mute the internal sounder.
5) Read the details of the alarm event on the LCD and investigate the source of the Alarm Condition.
6) If the building or area needs to be evacuated, once the area(s) is cleared, silence the alarm devices by
pressing the SOUNDER ACTIVATE/SILENCE button. The SOUNDER ACTIVATE/SILENCE LED will turn
off. Alarm devices can be re-started by pressing the button a second time.
7) If the cause of the Alarm Condition was not a fire, enter Access Level 2 and press the SYSTEM RESET
button to reset the fire detection and alarm system.
8) If the cause of the fire alarm has not cleared, the control and indicating equipment will re-enter the Alarm
Condition. If this occurrence repeats, disable the zone and contact the service company.
The relevant alarm zone
FIRE LED will flash.
The ALARMS
ACTIVATE/SILENCE
LED will illuminate.
The FIRE LED will flash.
The internal sounder will o
p
erate.
The device in alarm
will display in the LCD.
DO NOT RESET THE CONTROL AND INDICATING EQUIPMENT UNTIL THE
SOURCE OF THE ALARM HAS BEEN DETERMINED.