electrical installation
manual & setup guide
for neoAir V2 control
© Nu-Heat 2019
v7

2For expert advice call us on 01404 549770
working with you
your project
before,
& after
during
Nu-Heat
Know-How

3
For more information visit www.nu-heat.co.uk
Contents
Introduction 04
Electrical components 05
Planning the installation 06
System control options 07
neoAir and RF Switch connections 08
Systems without direct control of the boiler
Schematic 09
Wiring diagram 09
Systems with direct control of the boiler
Schematic – combi-boiler systems 10
Wiring diagram – combi-boiler systems 10
Schematic – S-Plan systems 11
Wiring diagram – S-Plan systems 11
Schematic – W-Plan systems 12
Wiring diagram – W-Plan systems 12
Schematic – Y-Plan systems 13
Wiring diagram – Y-Plan systems 13
Operation 14
System start up 14
Settings for underfloor heating 15
Installing neoAir 15
Thermostat operation 17
Optional control from a SmartPhone (systems with neoHub) 23
Energy eciency (ErP) 23

4For expert advice call us on 01404 549770
System Ref:
Please read this manual fully before fitting your Nu-Heat OneZone®floor heating
system. It assumes a basic knowledge of electrical wiring, and of common terms
used.
Attention to the advice given in this manual will help to ensure a trouble-free and
eective installation. The requirements of the relevant British Standards and other
Regulations should always be met.
In line with the company policy of product development, Nu-Heat reserves the
right to supply dierent components to those shown.
Please ensure that this manual remains with the homeowner when installation
is complete. It is a companion manual to the OneZone®Installation Manual, which
shows details of the plumbing components and floor construction.
This manual is the copyright of Nu-Heat. All rights reserved. No part of this
publication may be reproduced, stored in a retrieval system, or transmitted
in any form or by any means electronic, mechanical, photocopying, recording
or otherwise without prior written permission of Nu-Heat.
Electrical installation manual –
Nu-Heat OneZone®warm water
underfloor heating with neoAir control

5
For more information visit www.nu-heat.co.uk
Electrical components
neoAir wireless thermostat
NeoAir is a wireless, battery powered
programmable thermostat that is
capable of upgrade to smart control
(see neoHub below). The room/zone is
individually programmed for
temperature and times of use. This can
be independent control or in
conjunction with an existing radiator
system. For screed and floating floor
systems, allowance should be made for
the longer warm-up time of underfloor
heating. With LoPro®Max systems
response time is similar to that of a
traditional radiator system.
In order to comply with wiring
regulations bathroom zones must have
the thermostat fitted outside the room,
i.e. next to the door at light-switch
height.
RF Switch
This is the wireless base receiver, to be
fitted near to the OneZone®wiring
centre.
OneZone®wiring centre
The wiring centre can either be fitted
beside or remotely from the heating
components. It can be wired to suit
individual system requirements.
neoHub
The neoHub connects to a home
broadband router and wirelessly to
the neoAirs in a home. Simply plug into
a router, connect to your Nu-Heat
neoApp on an Android or iOS device
and take control of the underfloor
heating from anywhere.
neoPlug
neoPlug is a simple smart plug that
(with neoHub) enables on/o control
of a household appliance. It also acts as
a signal booster between the neoAir
and the RF Switch.
OPTIONAL COMPONENTS

6For expert advice call us on 01404 549770
Planning the installation
1 Read this Installation Manual
carefully.
2Decide which control method is to
be used for the OneZone®under-
floor heating system (see opposite).
3Agree the position for the wiring
centre and thermostat with the
homeowner.
41st fix all electrical equipment as per
the chosen method of control.
5After the underfloor heating
pipework is installed, 2nd fix the
electrical components.
6Commission the underfloor
heating and test its operation.
7Explain the operation of the
OneZone®underfloor heating
system to the homeowner and
hand over this User Guide
for reference.

7
For more information visit www.nu-heat.co.uk
System control options
There are two ways to connect the system:
B – Connection is at the boiler
This arrangement gives optimum performance. It allows time and
temperature settings for the OneZone®underfloor heating system to be
independent of other areas of the home. It also enables use of a set-back
temperature facility to reduce warm-up times. Pipework is connected back
to the boiler side of any control valves.
What type of heating system do you have?
Combination boiler
Refer to page 10 for wiring details.
S Plan
The system has two 2-port zone
valves, one controlling the radiator
circuit and the other controlling
the cylinder. Refer to page 11 for
wiring details.
Boiler & cylinder
What type of system
control do you have?
W or Y Plan
The system has a 3-port zone valve
controlling both the cylinder and
radiator circuits. This system type
requires an additional 2-port zone
valve to be fitted. Refer to pages
12–13 for wiring details.
Don’t know
Please consult your heating
engineer or electrician.
Please consult your heating
engineer or electrician.
Don’t know
OR
A – Connection is to the radiator circuit
Pipework is connected directly to the radiator circuit meaning that time
settings will correspond to the radiator circuit and set-back operation is
not possible. With screed and floating floor constructions, heating operation
times for the whole system may have to be altered to allow for the
longer warm-up time of underfloor heating compared to radiators. With
LoPro®Max systems response time is similar to that of a traditional radiator
system.
Refer to pages 9 for wiring details.

8For expert advice call us on 01404 549770
NEOAIR TERMINAL CONNECTIONS RF SWITCH TERMINAL CONNECTIONS
Remote
sensor
neoAir & RF Switch connections
REMOTE TEMPERATURE SENSORS
All OneZone®systems are supplied with a remote floor temperature sensor for
use with sensitive floor coverings such as engineered hardwood, vinyls (including
Amtico) and linoleums.
Note applying to all wiring diagrams:
All new electrical works must comply with IEE Regulations and health and safety
requirements, and be tested by a competent person before connection to mains
voltage.

9
For more information visit www.nu-heat.co.uk
SCHEMATIC
OneZone®
wiring centre
RF Switch5A fused spur
Radiator circuit Distributor assemblies and
Underfloor heating circuit
Pump & blending
valve assembly
Dierential bypass valve
WIRING DIAGRAM
1
2
3
4
RF Switch (see diagram on p.8 for terminal connections)
5A switched fused spur
Zone actuator
Underfloor heating pump
1
2
3
4
KEY
SL Switched Live
LLive NNeutral
EEarth
LS Live (source) LR Live (return)
Live voltage marker sleeve
Notes: Colour of wires may vary from
those shown.
Earth where required.
KEY
Pre-wired 2-core flex
2-core + Earth
3-core + Earth
4-core + Earth
Systems without direct control
of the boiler
neoAir
Notes:
a The Nu-Heat underfloor heating programmable thermostat must be set so that
heating periods coincide with the availability of hot water in the radiator circuit.
b Components shown in outline are not supplied.
c A 2-port zone valve is not needed on the UFH circuit.

10 For expert advice call us on 01404 549770
Systems with direct control
of the boiler
COMBINATION BOILERS WITH MAINS OR LOWVOLTAGE SWITCHING
OneZone®
wiring centre
Existing radiator room
thermostat and/or timeclock
RF switch5A fused spur neoAir
Radiator circuit
Combi-boiler
and pump Distributor assemblies and
Underfloor heating circuit
Pump & blending
valve assembly
Dierential bypass valve
Additional
2-port zone valve
SCHEMATIC
WIRING DIAGRAM
1
2
5
3
6
4
RF Switch (see diagram on p.8 for terminal
connections)
Radiator room thermostat and/or
timeclock – note: number of cable cores
depends on the thermostat used – see
manufacturer’s instructions.
5A switched fused spur
Boiler and boiler pump
Zone actuator
Underfloor heating pump
Additional 2-port zone valve
1
2 5
3
6
4
7
7
KEY
SL Switched Live
LLive NNeutral
EEarth
LS Live (source) LR Live (return)
COM Common NO Normally open
Live voltage marker sleeve
Notes: Colour of wires may vary from
those shown. Earth where required.
KEY
Pre-wired 2-core flex
2-core + Earth
3-core + Earth
4-core + Earth
Boiler
Refer to
note d
Notes:
a Refer to boiler manufacturer’s instructions for connection details and system
recommendations.
b Ensure radiator room thermostat (if used) is suitable for 230v AC switching.
c Components shown in outline are not supplied.
d A 2-port zone valve is not needed on the UFH circuit.
e Low-voltage switched boilers: Ls and LR must NEVER be connected to mains voltage.