Condition
Buzzer
Sound
Power
Indication
Fault
Detector
Operated
Fire
Alarm
Fault Detector
operated Fire Alarm
9-11
10-11
1-3
2-3
4-6
5-6
Supervision
○ - - - open
close
close
open
close
open
-
Power Cut - - - - close
open
close
open
close
open
-
Cable break/
Short circuit/
Detector
○ ○ - - close
open
close
open
close
open
Intermittent B
1 detector
in alarm ○ - ○ - open
close
open
close
close
open
Intermittent C
Fire
(more than 2
detectors in
○ - ○ ○ open
close
open
close
open
close
Continuous
Note:
*Fault means detector line is at fault, short circuit and detector drop-off.
*Intermittent sound B: cycle 0.5Hz (bi- -tu, bi- -tu, bi- -tu), Intermittent sound C: cycle 5Hz (bi-tu, bi-tu, bi-tu)
(Terminal)
⑥
⑤
④
③
②
①
⑦
⑨
⑬
⑫
⑪
⑧
⑩
Unused
Unused
Unused
Please make sure wiring to smoke detector as two
wire connecting arrangement.
● Please connect End-of-Line Resistor (7.5Kohm, 1/4W) to end line of smoke detectors to be
connected.
●
Maximum number of smoke detectors to be connected is 20. (0KB3 and old model 0KB/ 0IB can
be mixed.)
● Smoke detector connection terminals (L+ and C-) have polarity.
● Please use shield cables for wiring in electromagnetic disturbing environment.
● This equipment cannot be connected to detectors in automatic fire alarm system.
● Make sure to check the equipment by activating smoke detectors.
(Indication/Operation)
Fault (Trouble light: Yellow)
This turns on when detector line (L+, C-) is at
fault/short circuit and detector drop-off.
Fault is not latched at automatic reset.
② Fire Alarm (Fire light: Red)
This turns on when 2 or more detectors operate.
It remains ON until pressing Reset.
③ Detector Operated (1 detector op. light: Red)
This turns on when 1 or more detector operates.
It remains ON until pressing Reset.
④ Reset (Reset Switch) Switch to reset fire.
⑤ Power Indication (Power supply light: Green)
This turns on when power supply switch is set to ON.
⑥ Power SW (Power supply switch)
⑦ Earth Terminal(Noise reduction )
⑧ Detector Operated (1 or more detectors operate,
C contact terminal)
⑨ Fire Alarm (Fire, C contact terminal)
⑩ L+, C-(Detector connection terminal)
⑪ DC24V or AC24V Power Line (Power input terminal)
⑫ Fault (Trouble, C contact terminal)
⑬ R+, R-(Reset input terminal)
Terminal to input reset signal from outside.
* Please use round crimp terminal with insulation coating
(RAV11.25-3) when connecting wire to terminal block.
5. Overall Wiring Diagram
6. Product Specifications
Rated Power Supervisory condition: 0.9VA (DC24V) / 1.6 VA (AC 24V)
Below 20ohm (between Control P
anel and distal Smoke Detector)
5K ohm, 1/4W (attached to body)
(Reset Switch): Momentary Type
Indicator Light Power Indication (Power Supply Light): Green
Fault (Trouble Light): Yellow, Fire Alarm (Fire Light): Red
Detector Operating Light): Red
Relay Contact Point
Fault, Fire Alarm, Detector Operated
Contact Point Ratings: DC30V,
/
AC 125V, 0.3A (resistance load)
(Electronic Buzzer)
(Cycle:0.5Hz)
One detector operated: intermittent sound (Cycle: 5Hz)
Cover: Steel plate (Trivalent chrome chemical processing)
Screws: Iron and steel (Trivalent chrome chemical processing)
Mounting Bracket: Steel plate (Triva
Storage Temperature Range
Insulation characteristics: Pollution degree 2, overvoltage category I
(to be purchased separately)
*3 0KB3 is KC (MSIP-REM-nkt-0KB3) certified.
Control Panel
CPC-4-24
Fault
Operated Fire Alarm
Grounding (Noise absorption)
Power supply
(DC24V or AC24V)
End-of-Line Resistor
(7.5Kohm, 1/4W)
Smoke Detector
Smoke Detector
External Reset Switch
(momentary type)
(Pulse signal over 500msec)
* 1 It is recommended to use either AE cable or CPEV cable with conductor diameter over 0.65mm.
It is recommended to use shielded CPEV-S cable where electromagnetic noise causes disturbance.
Connect the shielded part of cable to the earth terminal.
* 2 After connection, please operate the detectors and confirm that the Smoke Detector Control Panel
will be restored from operating condition to normal monitoring condition by External Reset Switch input.
Non-Voltage C Contact: The labels indicate a condition when power is supplied.
External Reset Switch Input Line*2