NX-8E-CF CONTROL
10
UL has only verified compatibility with the following listed DACRs and formats: Sure-Gard SG-MLR2-DG: 2,9,10,12,13,14; Silent Knight
9000 - 2,12; FBI - CP220FBI, 13; and Ademco 685: 2,11,12, and 13.
For burglary installations, cross-zoned detectors shall overlap 100 percent in the area of coverage and similar coverage areas must be
used. For example, interior protection is cross-zoned with interior protection, and so on.
Expander trouble must activate the siren (Loc. 37, Seg 2)
For UL 1637, expander trouble must activate keypad sounder (Loc. 39, Seg 1)
If the Late to Close/Early to Open feature is enabled, the Opening and Closing reports shall be enabled (Loc. 23, Seg. 4, Option 1 and
Loc. 23, Seg. 3, Option 1).
Use type FPL, FPLR, or FPLR cables as required by Article 760 of the National Electrical Code.
Compatible listed devices (Special Applications – Commercial Fire):
• Bell Output (Sirens): Wheelock models NS-1215W, NS-121575W, NS4-1215W, NS4-121575W, AS-1215W, AS-121575W
• Horn / Strobe: System Sensor: S1224MC Strobe series; 1224MC Horn/Strobe series; H12/24 Horn series
• Smoke Output (4 wire detectors):
o ESL: 500N series; 449CTE series; 521 series; 541 series
o System Sensor models: 2112/24R; 2112/24TR; 2112/24AT; 2112/ATR; 2112/24AITR; 4WTA-B; 4WTR-B; 4WTAR-B;
4WITAR-B.
o Detection Systems: F220-B6C; D273 series
o Hochiki: SBC-4/12, 4/12W
o The 4-wire smoke detector employed shall be rated to operate over the voltage range of 11.5 to 12.4V
• Smoke Output (2-wire detectors): ESL 429 series, 521 series, 711U/UT, 721U/UT
For Canadian installations, the class II transformer secure tab shall not be employed.
VIII. GLOSSARY
TERM DESCRIPTION LOC PG
ABORT If enabled, the NX-8E-CF will wait the programmed number of seconds in location 40 prior
to sending an alarm. To abort the report, type in a code and press CANCEL. “Dialer Delay”
must be enabled in the “Characteristic Select” of locations 110-169.
40
110-169
22
28-31
AC FAIL
LOW BATTERY
REPORT/WARNING
The NX-8E-CF can be programmed to report AC failure and/or Low Battery conditions to
the central station. It can also be programmed to sound the keypad immediately upon
detection of the condition. The AC failure report/warning can be delayed.
37 & 39 21-22
AC POWER
LOW BATTERY
SOUNDER ALERT
If enabled, the NX-8E-CF will beep the keypad sounder upon arming or disarming if the
AC power is missing or a low battery has been detected.
For UL Commercial Fire installations, this feature must be ENABLED.
23 18
ARM / DISARM
CODES
The NX-8E-CF can have 240 four-digit codes or 160 six-digit codes to arm/disarm the
control. All codes must have the same number of digits. The factory default for User #1
is 1234 when using a 4-digit code, or 123456 for a 6-digit code. This code can
then be used to enter the new arm/disarm codes.
41 23
AUTO CANCEL / ABORT
If enabled, the Cancel and/or Abort features will be automatic (pressing the CANCEL
button is not required). The Cancel and Abort features, in locations 23 and 40
respectively, must be enabled to permit this Auto feature to work. For proper operation of
these features, “Dialer Delay” must be enabled in the “Characteristic Select” of locations
110-169 Zone Types. Default is OFF.
For UL Commercial Fire installations, this feature must be DISABLED.
41 23
AUTO TEST This feature will cause the panel to call the central station to report a communicator test
at a specified interval. Default is ON.
51 24
AUTOMATIC ARMING If programmed, the NX-8E-CF will Auto Arm at a specified time. At this time, the keypad
will beep for 50 seconds before the panel arms. The arming process will be stopped if a
code is entered on the keypad. The NX-8E-CF will attempt to arm after every 45 minutes
of inactivity until the next “opening” time (loc. 52), or until the system is armed. The 45-
minute timer will be extended when there is activity in the building. The Auto Arming of a
partition can be programmed to be silent. If closing reports are sent, the user code will be
97.
For UL Commercial Burglary installations, this feature must be DISABLED.
23,
52-55
18
24
AUTOMATIC BYPASS
INSTANT ARMING
When enabled, the control panel can automatically bypass interior follower zones if an
exit is not detected during the exit delay time. Entry delay zones can also be made
instant.
23
Seg 1 & 3
18
AUXILIARY OUTPUTS There are four programmable outputs that can be used to activate relays, LEDs, etc. 45-50
Diagram
23-24
7
AUXILIARY POWER
OVERCURRENT
The control panel will display a "Service Required" message on the keypad when too
much current is drawn from any device powered by the system. This condition can be
reported to the central station.
37 21