MultiTrode MTIC Manual de usuario

MultiTrode
MTIC
Indicator Controller

MTIC Installation & Operation Manual
Page 2 of 18 MTIC Manual R6

MTIC Installation & Operation Manual
MTIC Manual R6 Page 3 of 18
MTIC –Indicator Controller
Four Actuation Delays:
Used to average out wave action and for other control functions.
Method of Operation:
The MultiTrode MTIC liquid level monitoring and control system was
developed to provide a solution for interfacing to building
management systems and town water/sewerage systems.
The system can directly control operation of pumps and provide level indication at the site, as well as at
up to four remote locations, using 0-10V DC or 4-20mA current loop.
Until the advent of this MultiTrode system, these facilities had not been economically practical for
hydraulic services in high-rise buildings.
MTIC Installation & Operation Manual
Revision 6.0
7 August 2013
MULTITRODE® and MULTISMART® are registered trademarks of MultiTrode Pty Ltd in Australia, USA, and Europe. PUMPVIEW® is a
registered trademark of MultiTrode Pty Ltd in the USA and Australia. Designs registered for the MultiSmart Pump Controller Remote and
Base Modules in Australia, USA, Europe and China. Patents pending in Australia, USA, and Europe.
©2013 MULTITRODE PTY LTD.THIS PUBLICATION IS PROTECTED BY COPYRIGHT.NO PART OF THIS PUBLICATION MAY BE REPRODUCED BY ANY
PROCESS,ELECTRONIC OR OTHERWISE,WITHOUT THE EXPRESS WRITTEN PERMISSION OF MULTITRODE PTY LTD.

MTIC Installation & Operation Manual
Page 4 of 18 MTIC Manual R6
WARNINGS AND CAUTIONS
Information to User
Please read through the manual so you will know how to operate and obtain maximum performance
from your product. After you have finished reading the manual, put it away in a safe place for future
reference.
WARNING:
Do not use this unit in environments that may contain flammable/explosive or
chemically aggressive gases or powders.

MTIC Installation & Operation Manual
MTIC Manual R6 Page 5 of 18
Contents
1Introduction.......................................................................................................................... 6
1.1 Front Panel..........................................................................................................................7
2Function DIP Switches........................................................................................................ 8
2.1 Timer & Sensitivity DIP Switches.........................................................................................8
2.2 Output Relay DIP Switches .................................................................................................9
2.3 Probe Inputs........................................................................................................................9
2.4 Output Relays......................................................................................................................9
2.5 Analog Output....................................................................................................................10
2.6 Power Supply Terminals & Ratings Label..........................................................................10
3Installation & Power-Up..................................................................................................... 10
4Mounting............................................................................................................................ 11
5Electrical Connections....................................................................................................... 12
5.1 Probe Inputs......................................................................................................................12
5.2 Output Relays....................................................................................................................13
5.3 Analog Output....................................................................................................................13
5.4 Power Connection .............................................................................................................13
6MTIC –Pump Station Schematic & Overview .................................................................. 14
7MTIC –Installation Sheet No. 1 ........................................................................................ 16
7.1 Time Delay & Sensitivity Settings......................................................................................16
8MTIC –Installation Sheet No. 2........................................................................................ 17

MTIC Installation & Operation Manual
Page 6 of 18 MTIC Manual R6
1 Introduction
WARNING:
Do not use this unit in environments that may contain flammable/explosive or
chemically aggressive gases or powders.
The MTIC is a conductive liquid level indicator and controller which continuously monitor liquid level in
order to control the operation of up to 10 appliances. It will work in the following modes:
Fill (Charge) mode: Filling a tank
Empty (Discharge) mode: Emptying a tank
In a standard installation, the liquid level is sensed via a MultiTrode multi-sensored probe. Individual
sensors can be used in installations, if desired. Ten output relays control pumps, valves and, in addition,
there are 4-20mA and 0-10V stepped analogue outputs for use with variable speed drives, chart
recorders etc.
A 4-way DIP switch on the rear panel provides for the setting of four sensitivities and four time delays. In
addition, a 10-way DIP switch allows for the setting of the relays as Normally Open or Normally Closed.

MTIC Installation & Operation Manual
MTIC Manual R6 Page 7 of 18
1.1 Front Panel
POWER ON
1
2
3
4
5
6
7
8
9
10
LAG
STANDBY
LEAD
PUMPOFF
LOALARM
HI ALARM
MULT ITR ODE IN DICATO R CONTROL LER
IC
MT
MTIC
Figure 1 - MTIC Indicator Controller Front Panel
The MTIC has 11 LED’s. The bar graph on the left-
hand side indicates level, whilst the green LED in the
upper right-hand corner indicates power availability.
There is a slot located next to the bar-graph, that is
used for the placement of labels to indicate at what
levels pumps and alarms operate. Up to 10 labels can
be placed here.
PROBE
INPUTS
MAINS POWER
OUTPUTS
A
N
E
240VAC
50/60Hz
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
+ 12V
-12
0-10V
4-20mA
0V
see fig #3
see fig #1
NO NC
SELECT
FUNCTION
A
B
C
D
1
2
3
4
5
6
7
8
9
10
see fig #2
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4
ON
see fig #1
MTIC
S/N: ___________
Figure 2 - MTIC Indicator Controller Back Panel
The MTIC rear panel (see Figure 2), contains the
terminals, as well as function DIP switches, used to
preset the unit's basic operations.
This section describes the function of each terminal
and DIP switch.

MTIC Installation & Operation Manual
Page 8 of 18 MTIC Manual R6
2 Function DIP Switches
An important step in the commissioning of the controller is to preset the positions of the rear panel DIP
switches. This will set up the basic operation of the unit to match the installation. The following tables
show the switch functions.
2.1 Timer & Sensitivity DIP Switches
This section of the back panel is black.
SELECT
FUNCTION
A
B
C
D
see fig #2
Figure 3 –The MTIC should be switched off prior to altering the DIP switch settings.
SW
Function
Position
Description
A
Timer
►
►
Instantaneous actuation when level reaches sensor.
B
A
Timer
►
◄
Time delay on actuation approx. 5 seconds.
B
A
Timer
◄►
Time delay on actuation approx. 10 seconds.
B
A
Timer
◄
◄
Time delay on actuation approx. 15 seconds.
B
C
Extra low sensitivity 1KΩ
◄
◄
For concentrates such as acids, minerals, alkalis leaving
residue.
D
C
Normal low sensitivity
4KΩ
◄
►
Acids, alkalis, diluted brine, sea water.
D
C
Normal sensitivity 20KΩ
►
◄
Sullage, sewage effluent, town water.
D
C
►
►
Effluent and processes with oil contaminants, purified
water.
D
NOTE:
Conductance may vary from liquid type as described above. Adjust sensitivity as
required.

MTIC Installation & Operation Manual
MTIC Manual R6 Page 9 of 18
2.2 Output Relay DIP Switches
This section is black in colour on the rear panel.
SELECT
FUNCTION
see fig #1
Figure 4 –Output Relay DIP Switches
Setting a DIP switch to the left or right makes the corresponding output
relay act as a normally closed or normally open contact under the
following condition:
Power is supplied to the unit and no liquid covers the corresponding
sensor.
2.3 Probe Inputs
This section is blue in colour on the rear panel.
PROBE
INPUTS
see fig #3
Figure 5 –Probe Inputs
A MultiTrode probe would be the normal method of level detection.
Connection of ball floats is also accomplished via these terminals,
although this is not recommended for reliable level detection.
2.4 Output Relays
This section is white in colour on the rear panel.
OUTPUTS
see fig #1
Figure 6 –Output Relays
10 programmable contacts allow for the switching of contactors or other
equipment. Each relay is rated at 240VAC 5 Amp resistive or 2 Amp
inductive.
The operation of the devices is controlled by level switch points hardwired
to the appropriate output relay. This sets the levels at which the devices
activate and de-activate.

MTIC Installation & Operation Manual
Page 10 of 18 MTIC Manual R6
2.5 Analog Output
This section is white in colour on the rear panel.
see fig #1
Figure 7 –Analog Output
The analogue outputs supply 4-20mA and 0-10V.
It must be noted that these outputs are non-isolated. Various
wiring configurations allow for 4-20mA loads up to 940 W.
CAUTION:
Under no circumstances connect 0 volts to mains earth.
2.6 Power Supply Terminals & Ratings Label
This section is red in colour on the rear panel.
MAINS POWER
240VAC
50/60Hz
Figure 8 –Power Supply Terminals
A ratings label is located above the supply terminals and power
is supplied through these terminals.
Active, Neutral and Earth are connected to their respective
terminals as marked.
3 Installation & Power-Up
PROBE
INPUTS
MAINS POWER
OUTPUTS
A
N
E
240VAC
50/60Hz
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
+ 12V
-12
0-10V
4-20mA
0V
see fig #3
see fig #1
NO NC
SELECT
FUNCTION
A
B
C
D
1
2
3
4
5
6
7
8
9
10
see fig #2
1 2 3 4 5 6 7 8 9 10
ON
1 2 3 4
ON
see fig #1
MTIC
S/N: ___________
Figure 9 - MTIC Indicator Controller Back Panel
Before attempting to install the MTIC read this
section thoroughly.
Check the power rating label above the power input
terminals (see drawing below). Make sure that the
power supply configuration is compatible with the
installation being carried out.
Tabla de contenidos
Manuales populares de Panel táctil de otras marcas

IBASE Technology
IBASE Technology ASTUT-152-RE1S Manual de usuario

YASKAWA
YASKAWA TP 610C Manual de usuario

B&R
B&R Power Panel C Series Manual de usuario

Beijer Electronics
Beijer Electronics X2 control Manual de usuario

AXIOMTEK
AXIOMTEK GOT321W-521 Manual de usuario

TRIDONIC.ATCO
TRIDONIC.ATCO x-touchBOX Manual de usuario