MSA fieldserver ProtoNode FPC-N64 Manual de usuario

Operating Manual
ProtoNode FPC-N64 for Interfacing Hunter Fans Products
Revision: 3.A
Document No.: CN2045
Print Spec: 10000005389 (F)
MSAsafety.com

© MSA 2023. All rights reserved
Technical Support
Thank you for purchasing the ProtoNode for Huntner Fans.
Please call Huntner Fans for technical support of the ProtoNode product.
MSA Safety does not provide direct support. If Huntner Fans needs to escalate the concern, they will contact MSA Safety for
assistance.
Support Contact Information:
Customer Service:
Phone: (888) 830-1326
Website: https://www.hunterfan.com/

Quick Start Guide
1. Record the information about the unit. (Section 2.1 Record Identification Data)
2. Check that the ProtoNode and customer device COM settings match. (Section 2.3 Configuring Device
Communications)
3. If connecting to a serial device:
Connect the ProtoNode 3 pin RS-485 R1 port to the RS-485 network connected to each of the devices. (Section 3.1
Device Connections to ProtoNode)
4. If using a serial field protocol:
Connect the ProtoNode 3 pin RS-485 R2 port to the field protocol cabling (Section 3.2 Wiring Field Port to RS-485
Serial Network).
5. Connect power to ProtoNode 3 pin power port. (Section 4 Power up the Gateway)
6. Connect a PC to the ProtoNode via Ethernet cable. (Section 5 Connect the PC to the Gateway)
7. Setup Web Server Security and login via web browser. (Section 6 Setup Web Server Security)
8. Configure the ProtoNode to connect to the local network. (Section 7 Setup Network)
9. Integrate the ProtoNode with the FieldServer Manager or opt out. (Section 8.1 Choose Whether to Integrate the
FieldServer Manager)
10. Use a web browser to access the ProtoNode Web Configurator page to select the profile of the device attached to the
ProtoNode and enter any necessary device information. Once the device is selected, the ProtoNode automatically
builds and loads the appropriate configuration. (Section 9 Configure the ProtoNode)
3 Hunter Fans ProtoNode FPC-N64

Contents
1 Introduction 6
1.1 ProtoNode Gateway 6
2 Setup for ProtoNode 7
2.1 Record Identification Data 7
2.2 Point Count Capacity and Registers per Device 7
2.3 Configuring Device Communications 7
2.3.1 Set Node-ID for Any Device Attached to the ProtoNode 7
2.3.2 Set IP Address for Any Ethernet Device Connected to the ProtoNode 7
3 Interfacing ProtoNode to Devices 8
3.1 Device Connections to ProtoNode 8
3.2 Wiring Field Port to RS-485 Serial Network 8
3.3 Bias Resistors 9
3.4 Termination Resistor 10
4 Power up the Gateway 11
5 Connect the PC to the Gateway 12
5.1 Connecting to the Gateway via Ethernet 12
5.1.1 Changing the Subnet of the Connected PC 12
6 Setup Web Server Security 13
6.1 Navigate to the Login Page 13
6.2 Login to the FieldServer 13
6.3 Select the Security Mode 15
6.3.1 HTTPS with Own Trusted TLS Certificate 16
6.3.2 HTTPS with Default Untrusted Self-Signed TLS Certificate or HTTP with Built-in Payload Encryption 16
7 Setup Network 17
7.1 Navigate to the Network Settings 17
7.2 Routing Settings 18
7.3 Ethernet 1 and Ethernet 2 Network Settings – LAN Mode 19
7.4 Ethernet 2 Network Settings – WAN Mode 20
8 MSA Grid - FieldSever Manager Setup 21
8.1 Choose Whether to Integrate the FieldServer Manager 21
8.2 User Setup 22
8.3 Registration Process 24
8.4 Login to the FieldServer Manager 28
9 Configure the ProtoNode 30
9.1 Navigate to the ProtoNode Web Configurator 30
9.2 Select Field Protocol and Set Configuration Parameters 31
9.3 Setting Active Profiles 32
9.4 Verify Device Communications 33
9.5 BACnet: Setting Node_Offset to Assign Specific Device Instances 34
9.6 How to Start the Installation Over: Clearing Profiles 35
Hunter Fans ProtoNode FPC-N64 4

10 Troubleshooting 36
10.1 Lost or Incorrect IP Address 36
10.2 Viewing Diagnostic Information 37
10.3 Checking Wiring and Settings 38
10.4 LED Functions 39
10.5 Taking a FieldServer Diagnostic Capture 40
10.6 Factory Reset Instructions 41
10.7 Internet Browser Software Support 41
11 Additional Information 42
11.1 Update Firmware 42
11.2 BACnet: Setting Network_Number for More Than One ProtoNode on the Subnet 42
11.3 Mounting 43
11.4 Certification 43
11.5 Physical Dimensions 44
11.6 Change Web Server Security Settings After Initial Setup 45
11.6.1 Change Security Mode 46
11.6.2 Edit the Certificate Loaded onto the FieldServer 47
11.7 Change User Management Settings 48
11.7.1 Create Users 49
11.7.2 Edit Users 50
11.7.3 Delete Users 51
11.7.4 Change FieldServer Password 52
11.8 FieldServer Manager Connection Warning Message 53
11.9 System Status Button 54
12 Vendor Information – Huntner Fans 55
12.1 Yaskawa Modbus RTU or Modbus TCP/IP Mappings to BACnet, Metasys N2 and Modbus RTU 55
12.2 Mitsubishi Modbus RTU or Modbus TCP/IP Mappings to BACnet, Metasys N2 and Modbus RTU 55
12.3 TRAK Modbus RTU or Modbus TCP/IP Mappings to BACnet, Metasys N2 and Modbus RTU 57
12.4 Specifications 58
12.5 Warnings 58
12.6 Compliance with EN IEC 62368-1 59
13 Limited 2 Year Warranty 60
5 Hunter Fans ProtoNode FPC-N64

1 Introduction
1.1 ProtoNode Gateway
The ProtoNode wireless gateway is an external, high performance building automation multi-protocol gateway that is
preconfigured to automatically communicate between Huntner Fans devices (hereafter simply called “device”) connected to
the ProtoNode and automatically configures them for BACnet/IP, BACnet MS/TP, Metasys N2 and Modbus RTU.
It is not necessary to download any configuration files to support the required applications. The ProtoNode is pre-loaded
with tested profiles/configurations for the supported devices.
FPC-N64Connectivity Diagram:
The ProtoNode can connect with the MSA Grid – FieldServer Manager. The FieldServer Manager allows technicians, the
OEM's support team and MSA Safety's support team to remotely connect to the ProtoNode. The FieldServer Manager
provides the following capabilities for any registered devices in the field:
• Remotely monitor and control devices.
• Collect device data and view it on the Dashboard and the MSA Smart Phone App.
• Create user defined device notifications (alarm, trouble and warning) via SMS and/or Email.
• Generate diagnostic captures (as needed for troubleshooting) without going to the site.
For more information on the FieldServer Manager, see the MSA Grid - FieldServer Manager Start-up Guide.
Hunter Fans ProtoNode FPC-N64 6

2 Setup for ProtoNode
2.1 Record Identification Data
Each ProtoNode has a unique part number located on the side or the back of the unit. This number should be recorded, as it
may be required for technical support. The numbers are as follows:
Model Part Number
ProtoNode FPC-N64-2045
• FPC-N64 units have the following 4 ports: 2 Ethernet + RS-485 + RS-485/RS-232
2.2 Point Count Capacity and Registers per Device
The total number of registers presented the device(s) attached to the ProtoNode cannot exceed:
Part number Total Registers
FPC-N64-2045 1,500
Devices Point Count Per Device
Yaskawa 20
Mitsubishi 60
TRAK 24
2.3 Configuring Device Communications
2.3.1 Set Node-ID for Any Device Attached to the ProtoNode
• Set Node-ID for any device attached to ProtoNode. The Node-ID needs to be uniquely assigned between 1 and 255.
• Document the Node-ID that is assigned. The Node-ID assigned is used for deriving the Device Instance for BACnet/IP
and BACnet MS/TP. (Section 9.5 BACnet: Setting Node_Offset to Assign Specific Device Instances)
NOTE:The Metasys N2 field protocol Node-ID is automatically set to be the same value as the Node-ID of the
device.
2.3.2 Set IP Address for Any Ethernet Device Connected to the ProtoNode
• Ensure any device is set to Modbus TCP/IP to communicate with the ProtoNode.
• The device needs to be on the same IP subnet as the ProtoNode and the configuration PC.
• Record the following device information to start the setup:
◦ IP Address
◦ IP port
◦ TCP_ID
NOTE:This information is required for Section 9.3 Setting Active Profiles.
7 Hunter Fans ProtoNode FPC-N64

3 Interfacing ProtoNode to Devices
3.1 Device Connections to ProtoNode
The ProtoNode has a 3-pin Phoenix connector for connecting RS-485 devices on the R1 port.
NOTE:Use standard grounding principles for RS-485 GND.
3.2 Wiring Field Port to RS-485 Serial Network
• Connect the RS-485 network wires to the 3-pin RS-485 connector on the R2 port.
◦ RS-485 is part of the RS-485 interface and must be connected to the corresponding terminal on the BMS. If the
cable is shielded, the shield must connected only at one end and to earth ground – it will help suppress the
electromagnetic field interference. (Connecting the shield at both ends will likely produce current loops, which
could produce noise or interference that the shield was intended to block).
• See Section 5.1 Connecting to the Gateway via Ethernet for information on connecting to an Ethernet network.
Hunter Fans ProtoNode FPC-N64 8

3.3 Bias Resistors
To enable Bias Resistors, move both the BIAS- and BIAS+ dip switches to the right in the orientation shown
above.
The bias resistors are used to keep the RS-485 bus to a known state, when there is no transmission on the line (bus is
idling), to help prevent false bits of data from being detected. The bias resistors typically pull one line high and the other low -
far away from the decision point of the logic.
The bias resistor is 510 ohms which is in line with the BACnet spec. It should only be enabled at one point on the bus (for
example, on the field port were there are very weak bias resistors of 100k). Since there are no jumpers, many ProtoNodes
can be put on the network without running into the bias resistor limit which is < 500 ohms.
NOTE:Seethe Termination and Bias Resistance Enote for additional information.
NOTE:If the gateway is already powered on, DIP switch settings will not take effect unless the unit is power
cycled.
9 Hunter Fans ProtoNode FPC-N64

3.4 Termination Resistor
If the gateway is the last device on the serial trunk, then the End-Of-Line Termination Switch needs to be enabled. To
enable the Termination Resistor, move the TERM dip switch to the right in the orientation shown in above.
Termination resistor is also used to reduce noise. It pulls the two lines of an idle bus together. However, the resistor would
override the effect of any bias resistors if connected.
NOTE:The R1 and R2 DIP Switches apply settings to the respective serial port.
NOTE:If the gateway is already powered on, DIP switch settings will not take effect unless the unit is power
cycled.
Hunter Fans ProtoNode FPC-N64 10
Otros manuales para fieldserver ProtoNode FPC-N64
1
Tabla de contenidos

















