Page7
1. ActivatewirelessFUSEprotectionDYNAMICchargingonwallmountedstation(s)asdescribedonPage3
(smartportablestationshaveenabledwirelessdynamicchargingRFreceiverbydefault).Youalsoneedtoset
housephasesandsolarphasesbutdon’tchangethemainfuseratingonthewallmountedstation(leave
default35Aorsetinbackto35Aifithasbeenchanged).
2. Installthe3FD‐3DYNAMICEVCHARGINGUNITandsuppliedcurrentmeasuringtransformers(CT)onthe
house/buildingmainpowersupplyinput(inthehousemaindistributionpanel)asshownonthe3FD‐3‐1
or/and3FD‐3‐2drawingsintheattachment.
3. SettheneededparametersviaMetronDynamicPowerControlapplication.YouentertheDynamicPower
ControlapplicationthesamewayasChargeControlapplicationonstations(seeinstructionsonpage2)except
thatdefaultWiFiname(ssid)isinthiscase“METRONDynamic1”.Onthefirstpageclick/presson“Settings”
buttonandscrolldownto“Essentialparameters”windowwhereyouseethesettings.Press“Change
parameters”buttonandenterthepassword“param2011”inordertobeabletochangesettings.Thenchange
settingsasneeded/requiredandpress“Confirmnewparameters”buttonbelowtosavenewsettings.
4. DESCRIPTIONOFEACHESSENTIALPARAMETERtheinstallercanset:
INSTALLINGthe3FD‐3DYNAMICEVCHARGINGUNITfor1or3‐
phaseMAINFUSEprotectionWIRELESSDYNAMICchargingofup
to150wallmountedandportablechargingstationspermainfuse
Select1,2or3phasepowerplantgridconnection.
Defaultsetting:3phases
Select1,2or3phasehousegridconnection.
Defaultsettin
:3
hases
Selecthousemainfuserating‐
from1Ato1000A.
Defaultsetting:35A
Selectcurrentmeasuringrange:
‐Range1:upto80A(nofurtheractions,use
suppliedCTs)
‐Range2:upto160A(connect1additional84.5
Ohmresistorbetweeneachcurrentmeasuring
inputandGND)
‐Range3:upto250A(connect2additional84.5
Ohmresistorsbetweeneachcurrentmeasuring
inputandGND)
‐Range4:upto500A(connect6additional84.5
Ohmresistorsbetweeneachcurrentmeasuring
inputandGND)
‐Range5:upto1000A(connect12additional84.5
Ohmresistorsbetweeneachcurrentmeasuring
inputandGND)
Defaultsetting:Range1
Note:ForRange2,3,4,5youcanuseappropriate
currentratingcurrentmeasuringtransformers
(CTs).CTcurrentratioshallbe2000:1inallcases.
Thereare25channelsavailablein
ordertopreventinterferenceof
wirelesssignalincase2ormore
DynamicEVchargingunitsare
installednearby(e.g.twoneighbour
houses).DynamicEVchargingunit
andallwirelesslycontrolledcharging
stationsshallbesettothesameRF
channelinordertowork.
Defaultsetting:channel1
Selectnumberofstationsthe3FD‐3willcontrol.Upto
150wallmountedandportablechargingstationscanbe
controlledbyoneDynamicEVChargingUnit.
Defaultsetting:1chargingstation
SelectMASTERchargingcurrentlimitintherangeof
6Ato32A.Thissettingrepresentsabsolutemaximum
allowedchargingcurrentoneachbythis3FD‐3unit
controlledstation.Thereisalsoadditionalsetting0A
whichstopschargingonallwirelesslycontrolled
stationsbythis3FD‐3unit.
Defaultsettin
:32A
GeneralNOTE:Onceconfirmed
thesetvaluesstaysavedinthe
internalmemorypermanently
(powerlossdoesn’tdelete
settings).