Meggitt F251 Series Manual de usuario

Maintenance Manual
HYDRANT COUPLER
F251 Series
MMF251
Revision 4.0
28 February 2014
Meggitt (North Hollywood), Inc. Proprietary Information
The information contained in this document is disclosed in confidence. It is the property of Meggitt (North Hollywood), Inc. and shall not be used,
disclosed to others, or reproduced in whole or in part without the express written consent of Meggitt (North Hollywood), Inc. If consent is given, this
notice shall appear in any such reproduction. These commodities, technology, or software were exported from the United States in accordance with
the export administration regulations. Diversion contrary to U.S. law is prohibited.
SENSITIVE BUT UNCLASSIFIED-EXPORT CONTROLLED-EAR RESTRICTED.
These commodities, technology or software are exported from the United States of America in accordance with the Export Administration
Regulations. ECCN EAR99. Diversion contrary to U.S. law is prohibited.
Copyright © 2014 Meggitt (North Hollywood), Inc.
Shown with additional
coupler modifications

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 i
REVISION RECORD
Keep this record in the front of the manual. When you get the revisions, put the revised pages in the
manual. Write the revision number, date issued and your initials on this page.
REV NO. PAGES
AFFECTED DESCRIPTION OF
CHANGE DATE APPROVED
BY
1.0 ALL Initial Release 05/31/2011 A.B
1.1 ALL - 06/06/2011 A.B
2.0 ALL - 09/30/2011 A.B
2.1 ALL - 04/20/2012 A.B
3.0 ALL See DCN 07/30/2013 A.B
4.0 1, 9-12, 14, 18 & 19 See DCN 3/19/14 A.B

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 ii
TABLE OF CONTENTS
SUBJECT PAGE
IMPORTANT SAFETY INSTRUCTIONS ........................................................................................................A
INTRODUCTION............................................................................................................................................. 1
DESCRIPTION AND OPERATION................................................................................................................. 2
FAULT ISOLATION......................................................................................................................................... 5
DISASSEMBLY............................................................................................................................................... 6
CLEANING.................................................................................................................................................... 10
INSPECTION ................................................................................................................................................ 12
ASSEMBLY................................................................................................................................................... 13
ILLUSTRATED PARTS LIST ........................................................................................................................ 17
LIST OF ILLUSTRATIONS
FIGURE PAGE
Figure 1.Hydrant Coupler............................................................................................................................ 3
Figure 2.Coupler Section Assembly.......................................................................................................... 14
LIST OF TABLES
TABLE PAGE
Table 1Leading Particulars........................................................................................................................ 4
Table 2Fault Isolation................................................................................................................................ 5
Table 3Recommended Cleaning Materials ............................................................................................. 10
Table 4Component Checks..................................................................................................................... 12
Table 5Recommended Assembly Materials............................................................................................ 13

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 A
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS!
This manual contains important instructions that shall be followed during installation and maintenance of the
Hydrant Coupler. The following are general safety precautions that are not related to specific procedures
and therefore do not appear elsewhere in this publication. These are recommended precautions that
personnel must understand and apply during maintenance.
The coupler is a mechanical device and can be dangerous if not correctly operated or maintained.
Safety Alert Symbols
Safety alert symbols are used in this manual to identify potential or immediate personal injury hazards. The
safety alert symbol words are explained below:
- indicates an imminently hazardous situation which, if not
avoided, will result in injury or serious injury.
- indicates a potentially hazardous situation which, if not avoided,
could result in injury or serious injury.
- indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.
- used without the safety alert symbol indicates a potentially
hazardous situation which, if not avoided, may result in
property damage.
WEAR PROTECTIVE CLOTHING
Wear protective clothing (gloves, apron, etc.) approved for the materials and tools being used.

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 B
Equipment Safety Information
The following safety information briefly discusses hazards peculiar to the equipment, which are likely to be
encountered during maintenance activity.
COUPLER INSTALLATION AND OPERATION PRECAUTIONS
The design of the piping system must provide adequate pressure to prevent exceeding the limits of the
coupler.
Make sure the coupler orientation is correct and install the coupler in-line with the flanges. Make sure
the piping flanges are correctly positioned and spaced. Do not force the piping in order to fit the
coupler.
Make sure the coupler operates correctly after installation.
Do not exceed the pressure limits of the coupler.
COUPLER MAINTENANCE PRECAUTIONS
Do not loosen any fasteners or attempt to remove the coupler from the line until all pressure is isolated
and released from the system.
Use only authorized replacement parts or hardware.

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 1
INTRODUCTION
NOTE: The F251 Hydrant Coupler is a direct upgrade replacement for the F250 coupler. The F251
Coupler complies with the API Standard 1584 3rd edition breakaway requirements. The shaft and
seals are designed to improve safety, reliability and maintainability.
1. General
The information and procedures contained in this manual have been prepared to assist qualified repair
personnel in off-aircraft maintenance of the Hydrant Coupler (coupler). The instructions provide
information necessary to perform maintenance functions. The Coupler is manufactured by Meggitt
(North Hollywood), Inc., 12838 Saticoy Street, North Hollywood, California 91605.
2. Scope
The instructions contained in this manual do not claim to cover all details or variations in equipment.
They do not provide for every problem that could occur during installation, operation, or maintenance. If
further information is required, contact Meggitt (North Hollywood), Inc., Product Support Department.
3. Standard Shop Practices
Use approved procedures and safety precautions to prevent damage to the equipment and injury to
personnel.
4. Weights and Measurements
Weights and measurements in this manual are expressed in both English (U.S. customary) and Metric
(SI) units.
5. Revision Service
This manual will be revised, as necessary, to reflect current information.

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 2
DESCRIPTION AND OPERATION
1. Description
The Hydrant Coupler (coupler) (see Figure 1) provides the means of connecting 4-inch hydrants and
adapters conforming to API Standard 1584. The various optional configurations permit the use of
several thread and hose sizes. The major functional components of the hydrant coupler are the
swiveling outlet adapter, the elbow and the coupler body section.
2. Installation/Operation
A. Install Coupler on Hydrant
The coupler may be connected to the hydrant adapter by pressing it downward onto the adapter.
This actuates the six locking lugs, and releases the shroud. The shroud slides downward and holds
the locking lugs in their locked position. If product selection is installed, the shroud will need to be
rotated to align the product selection screws with the slots in the shroud.
B. Operate the Coupler
DO NOT OPEN THE COUPLER WITHOUT BEING CONNECTED TO AN
ADAPTER. SLEEVE SEAL DAMAGE MAY OCCUR.
After installation, to open the coupler, rotate the handle to the OPEN position. To close the coupler,
rotate the handle to the CLOSED position.
C. Remove Coupler from Hydrant
With the hydrant closed, the coupling may be disengaged from the hydrant adapter by rotating its
operating handle to the CLOSED position and pulling back the shroud to disengage the locking
lugs.
D. Remove Coupler and Elbow from Hose
Pull the safety ring from its groove and slide it back to the retaining ring. Do not remove the safety
ring. Unscrew the four retaining screws approximately 3 full turns. Slide the retainer back to the
safety ring. The elbow can now be separated from the hose.

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 3
Figure 1. Hydrant Coupler

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 4
3. Leading Particulars (Refer to Table 1)
Table 1 Leading Particulars
Service ........................................................................................................................Automotive and Aviation Fuels
Operating Pressure
Maximum Working...............................................................................................................200 psi (1380 kPa)
Peak Surge..........................................................................................................................305 psi (2100 kPa)
Pressure Drop (connected to F368 Hydrant)
(approximate) ...................................................................................13 psi at 1200 gpm (90 kPa at 4500 lpm)
Fluid Temperature..............................................................................................................–40 to 160°F (-40 to 71°C)
Ambient .............................................................................................................................–40 to 160°F (-40 to 71°C)
Weights (approximate)
Basic.................................................................................................................................16.6 pounds (6.2 kg)
Mod A – Hydrant 4 inch Coupler for CCMZ7300M2/ CCMZ7309M2
Pressure Control Elbow.....................................................................................16.6 pounds (9.7 kg)
Mod B – with 90° Elbow + F597A 4 inch NPT Swivel......................................................24.4 pounds (9.7 kg)
Mod C – with 90° Elbow + F597B 4 inch BSPPL Swivel................................................25.2 pounds (10.1 kg)
Mod D – with 90° Elbow + F597C 3 inch NPT Swivel....................................................25.2 pounds (10.1 kg)
Mod E – with 90° Elbow + F597D 3 inch BSPPL Swivel................................................ 25.2 pounds (10.1 kg)
Mod F – with 90° Elbow + F597E 2.5 inch NPT Swivel .................................................25.2 pounds (10.1 kg)
Mod G – with 90° Elbow + F597F 2.5 inch BSPPL Swivel...............................................24.4 pounds (9.7 kg)
Mod H – with 90° Elbow + F597G 4 inch NPSM Swivel ..................................................21.9 pounds (8.6 kg)
Mod J – with 90° Elbow for F597 Swivel........................................................................+0.1 pound (+0,05 kg)
Mod K – (Use only with MOD B thru J) + 0.75 inch NPT THD in Elbow, with plug......... 21.9 pounds (8.6 kg)
Mod L – Add Product Selection Position 4........................................................................... No weight change
Mod M – With 90° Elbow + F597M 4 inch NPSH.............................................................24.4 pounds (9.7 kg)
Mod R – Viton Seals............................................................................................................. No weight change

Meggitt Fuelling Products
Maintenance Manual (MMF251)
Hydrant Coupler – F251 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
28 Feb 2014 Revision 4.0 5
FAULT ISOLATION
1. General
Refer to Table 2 for fault isolation information. Locate suspected faulty component and take appropriate
remedial action.
Table 2 Fault Isolation
FAULT POSSIBLE CAUSE CORRECTIVE ACTION
Leakage from outlet adapter Damaged or worn bearing ring,
(IPL Figure 2, 6), seal (IPL Figure 1,
15) or O-ring (21)
Check condition and if necessary
replace the bearing ring, seal,
and/or O-ring.
Leakage from elbow flange Damaged or worn O-ring (13) Check condition and if necessary
replace the O-ring.
Leakage past handle shaft Damaged or worn O-ring (33) Check condition and if necessary
replace the O-ring.
Leakage past poppet when closed Damaged or worn O-ring ( 21) Check condition and if necessary
replace the O-ring.
Damaged or worn sleeve assembly (12) Check condition and if necessary
replace the seat.
Damaged or wear on seat face of
poppet (9) Check condition and if necessary
replace poppet.
Leakage at hydrant adapter when
open Damaged or worn O-ring (21) Check condition and if necessary
replace the O-ring.
Damaged or worn seal (15) Check condition and if necessary
replace the seal.
Tabla de contenidos
Otros manuales de Equipos de extinción de incendios de Meggitt
Manuales populares de Equipos de extinción de incendios de otras marcas

Tyco Fire Protection Products
Tyco Fire Protection Products AM31 AQUAMIST Nozzle Manual de usuario

Task Force Tips
Task Force Tips Extend-A-Gun RC3 Manual del propietario

Autronica
Autronica AutroSafe BSD-321/EX Manual de usuario

POK
POK Froggy Manual de usuario

Waterous
Waterous AQUIS Series Manual

CTP
CTP NPO ETERNIS GUARANT-7 Manual de lista de piezas