Medem SEC-Le V4 Manual de usuario

1
00243
SEC-Le V4
Installation Instructions
The SEC-Le is a gas pressure proving system with electrical isolation, gas detection and ventilation interlock.
The system will perform a down stream integrity check ensuring gas tightness before use, close the gas
solenoid valve in the event of a high-level gas alarm, ventilation failure, low incoming gas pressure or if the
emergency stop fire alarm is activated.
It is designed for use primarily in laboratories.
Before commencing installation please familiarise yourself to the equipment by reading the comprehensive
installation instructions. If in doubt then please call 0161 233 0600. Out of hours please call 07894 684080 or
07843 355163.
It is a statutory requirement that this safety system is installed and commissioned
to the satisfaction of the manufacturer.
A commissioning certificate must be issued to the end user along with instructions for the operation of the
equipment.
As the Manufacturer Medem UK should commission this safety system whereupon a commissioning report
will be forwarded to the installing agent who should provide a copy to the end user.
At the point of our commissioning an individual serial number will be attached to the system along with a 24
help line number. Photos and all relevant information for the installation will then be stored on the Medem
site database to be accessed in the event of a call on the 24 hour help line. The warranty period for the
panel and sender unit will then be extended to Ten years.
• Gas Pressure proving.
• Electric Isolation
• Gas Detection .(up to 16 detectors with a power pack)
• Fan interlock. (optional)
• 5 year warranty - 10 years when commissioned

2
00243
System description
SEC-Le
System On Off enables gas detection and use of
each soft touch service button
A Blind button for displaying gas pressures on the LCD screen
B Blind button for displaying first 8 detectors (Gas & temperature) on the LCD screen.
A B
Multi gas detection, air quality monitor and gas pressure proving system
The SEC-Le system comprises of a mains powered main control panel, and low voltage pressure sender unit and fitting kit. The
pressure sender unit it mounted onto the gas valve (with the fitting kit) and transmits the gas pressure information back to the
main panel in order to perform its integrity test.
Control Panel
The front of the panel has the following controls and indications:
Emergency stop button.
System On Off switch.
Yellow soft touch On off buttons for gas and electric.
White Blind buttons A and B for engineer functions.
LED indications:
Power On - green………..A: blind button for displaying gas pressures on the LCD screen
Gas Electric - red when active to warn of live service
Fans running light – yellow…B: blind button for displaying connected devices (detectors & temperature) on the LCD screen
LCD display:
For displaying system status during both installation and normal use, also for displaying diagnostics
Pressure sender unit
Pressure sender unit transmits pressure information back to the main panel in order for it to preform its integrity test. Its is not
optional and must be connected, the system will not work without it.
It is mounted to the gas solenoid valve inlet and outlet test ports using 8mm OD copper pipe. Use the appropriate Medem fitting
kit to fit the control valve size (see page 10,11).
The pressure sender is connected to the control panel with low voltage two core screened cable using the terminal marked A & B.
N TE: This is low voltage and should be segregated from mains wiring.
Pressure Sender Unit

3
00243
Main features
SEC-Le
Connections to panel: marked on board
1. Live & Neutral 230 volts supply from 3amp switched fuse spur
2. 230 volts out to gas solenoid valve (required)
3. To contactor for isolating bench socket electricity supply (optional) see page 9
4. volts out to water supply isolation valve
5. Earth connection terminals
6. Remote emergency stop and thermal links, SELV, connect in series multiple buttons (requires a N C circuit)
7. Extract fan interlock for current monitor (CM2M-K) or PD switches.
8. Supply fan interlock for current monitor (CM2M-K) or PD switches.
9. 12 volt power for current monitor (CM2M-K)
10. Pressure sender unit SELV and comm’s both through “A” & “B” terminals (2 wire) (Required)
11. Power connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature
12. Comms connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature
13. Fire alarm input signal (N C contact required).
14. 0-10 volt output to fan speed controllers based on CO2 and temperature levels
15. Three relays, outputs for connection to a BMS see page 4 for full details.
16. OPTA=Over pressure check, will isolate gas supply if pressure exceeds 70 mbar
17. Fill & prove time for gas pressure proving, see page 5.
18. Timer adjustment for fan commissioning, allows timed period for gas installation commissioning.
19. Auto stop timer to isolate gas after set length of time. Factory set for model & use
20. CO2 alarm level adjustment depending on application. Factory set for model & use
21. High pressure low cut out adjustment (
when high pressure sender unit is used 1 bar>
)
22. Fan comm button, enables commissioning of the gas supply without fans running.
23. Learn field device button, press once only when all detectors are connected and powered (verify with Blind button B).
24. Selector switch to disable audible alarm sounder.
25. Lift valve button, opens the gas valve only whilst the button is continuously pressed, for commissioning purposes.
26. Fill Prove Multiplier SW=X2 multiplies the prove time by 2, CPI=ACTV Can monitor position of a CPI switch on a gas valve when
used with a CPI pressure sender unit.
27. OPTL Enable Disable the front panel “FANS” LED (switch on to disable)
Power at 230
volts from a
3amp fused spur
17
26
24
27
1 2 3 5 7 6 8 9 10 11 12 13 14
15
16
18 19
21
20
22 23
25
4

4
00243
System Settings
SEC-Le
ALT EST G N HAL
1 2 3 4
Low Pressure (Any State) - LP OFF OFF OFF OFF
High Pressure (Any State) - HP ON OFF OFF OFF
Test Fail OFF ON OFF OFF
Fan Fault - FF ON ON OFF OFF
EM Stop - ES OFF OFF ON OFF
Fire Panel Active -FA ON OFF ON OFF
High Alarm (Any State) - HA OFF ON ON OFF
Low Alarm (Any State) - LA ON ON ON OFF
Gas On State OFF OFF OFF ON
Detector Fault ON OFF OFF ON
Generic Fault (LP,HP,FF,ES,FA,HA OFF ON OFF ON
Key Switch State ON ON OFF ON
Two relays, for connection to a BMS or sounder Beacon (One status selectable from each relay)
Max switching 48 volts 1 amp
15. BMS Relay PCB
Press button A - To display the gas pressures and view the set pressure proving set times.
Press button B - To display the gas installed gas detectors 1-8 press A & B together to view 9-16.
Fire Test Mode (Press button B three times)
When connected to a fire alarm panel using the fire alarm terminal (no.13) the system will isolate the gas during an fire alarm.
If for the purposes of a fire test you wish to temporarily disable this interlock the SEC system can be put into a “fire test mode” by
pressing blind button B three times in quick succession.
This is a timed feature and will auto clear after 45mins. Press again three times to manually clear and return to normal running.
A B
Blind buttons - engineer features

5
00243
17. Fill and Prove
Gas Fill Time.
The Fill Time should be set such that there is sufficient time to fill an empty pipe work
system to full normal pressure while ensuring a minimum escape of gas where a leak
exists.
(Factory default setting is 5 seconds).
Gas Prove Time. This should be set such that the smallest leak can be detected. This time
can be set up to a maximum of 9 minutes. Increasing this time effectively makes the
system more sensitive to gas leaks.
(Factory default setting is 1 minute).
FILL switch @ 1,2,3,4,5,6,7,8,9,0 = 1s, 2s, 3s, 4s, 5s, 6s, 7s, 8s, 9s, 10s,
PROVE switch @ 1,2,3,4,5,6,7,8,9,0 = 1m, 2m, 3m, 4m, 5m, 6m, 7m, 8m, 9m, 30s,
The prove time can be extended using FILL PROVE MULTIPLIER, see No 26.
18. Timer adjustment for fan commissioning, allows timed period for gas installation
commissioning.
19. Auto stop timer to isolate gas after set length of time. Factory set for model & use
20. CO2 alarm level adjustment depending on application. Factory set for model & use
21. High pressure sender unit: Low pressure cut out adjustment (for systems over 1 bar)
18, 19, 20, 21 ption Headers
18 19
21
20
Fan comm.
To enable the commissioning of the gas portion of the system before the ventilation interlock is
completed you may temporarily disable the interlocking by pressing button 22.
This will bypass the ventilation interlock allowing the gas to be tested, the system must not be
left in this state and as such is only for a maximum 24hour period before auto exiting. While in
commissioning mode the display will show the message “Not to current standards”. Pressing
the button again at anytime will cancel commissioning mode.
Learn Field devices.
Any gas detectors connected to the system will require “learning”. First ensure all detectors are set to a unique ID address using
the selector switch on the detectors themselves. Having addressed each detector press the learn field devices button (23), the
system will scan and store any connected detectors. To verify that all detectors have been successfully learnt press the “blind
button B” on the front panel to view address details.
22, 23 Fan Comm & Learn Detectors
22 23
System Settings
SEC-Le
SW = X2 This doubles the fill & prove time.
SW = X0.5 This halves the fill and prove time test, please note the minimum prove time is 30
seconds which cant be reduced any lower.
26. Fill/Prove multiplier

6
00243
Gas Detection
Gas Detectors
IMPORTANT - Gas Detectors should not be installed until all building, construction or painting work etc.. Is completed, as these
works can effect the sensitivity and longevity of the detectors.
Ensure that the protective cover labels (RED) are removed only
after the completion of all building work and the system has
been commissioned by the Medem engineer.
The labels are required to be removed for the detectors to
operate, but removal before the completion of works risks
contaminating the sensor element.
The system is capable of operating a mix of up to 16 detectors (additional power pack may be required) of different types.
The detector types are:
• Carbon Dioxide.
• Carbon Monoxide.
• Combustible gases (Methane, Propane).
• Oxygen depletion and temperature.
Detector location will vary dependant on the individual characteristics of the target gas that is being monitored for. See the gas
detectors own instructions for more guidance.
SEC-Le Detector Information
+VE supply & Comm’s
From either the main panel or an
extender.
Detectors are wired in parallel and can be
connected to one another daisy chain
Address Selector
Each detector must be set to its own
address and then “learnt” using button
(23, see page 5)
Connection and addressing
Status LED
All current wiring regulations must be followed with reference to running low and mains voltage cables together.
The maximum cable length between a detector and the control panel should not exceed 100 meters, if the distance between
the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the +VE, 0v terminals
Gas detectors, require a four core screened Belden type security cable or 600v rated BMS cable (max cable length of
100meters.)
Remote emergency stops and thermal links require a two core screened cable.
Warranty will be void if Fire Protection Cable or cable over 1mm dia. is used on the SELV side.
When addressing gas detectors CO &
CO2 detectors must be numbered
before natural gas detectors.

7
00243
Detector Information
Detector location will vary dependant on the individual characteristics of the target gas that is being monitored for.
The descriptions below describe the position for each detector after considering these characteristics.
For proper function care must be taken not to site a detector in a “dead space” or in the flow of any ventilation.
Natural Gas/Methane
Natural gas detectors should be mounted at high level on a wall approximately 150mm from the ceiling height and avoiding
corners and potential dead air areas.
Natural gas detectors should not be mounted below the height of the top of a doorway for example. This is because as the gas
is slightly lighter than air it will rise filling the room from the ceiling down and will spill through the top of a door opening into the
next room. If the detectors are mounted below this height then it will take longer the gas to reach the detector.
LPG /Propane
LPG gas is heavier than air so detectors need to be mounted at low level 100mm from the floor, consideration should be given
to any potential mopping or wet floor height.
Carbon Monoxide
Carbon Monoxide is similarly weighted to air so detectors should be mounted between 1 to 2 meters from the floor.
Carbon Dioxide
Carbon Dioxide detectors should be installed so they monitor the general level of CO2 within the area. They should be mounted
above standing head height and between 1m and 3m from the potential source. Care should be taken so they are not located
close to the edge of a canopy or in direct flow of the supply or extract ventilation.
For additional information or guidance on site specific requirements please don’t hesitate to contact us.
SEC-Le
Detector Location
Detector Indications
Each detector has its own Bi-Colour LED which is used to indicate the status of that detector.
Not Lit: No power comm’s. These a four wire units and all connections are required (0v, +VE, MA, MB), check the
polarity of both the power and the comm’s (MA MB) terminals are correct.
Flashing Green: Detector is warming up, the detectors will flash green on power up for 90 seconds while the sensor
elements stabilize. The system will ignore any detectors while flashing.
Solid Green: Detector is powered and active. Note: The detectors will still require correctly addressing (using the address
selector pot) and learning by the system using button 23, (see page 5).
Flashing Red: Low level alarm. All detectors have both a low and high level alarm, low level alarms serve as a warning
that an unsafe condition maybe building and gives chance to intervene before loss of gas service.
Solid Red High level alarm. An unsafe level of the target gas have been reached and the system will isolate the
gas supply. The cause of the alarm will require identifying and resolving before the gas supply can be re-
established.
After installation a simple bump test can be performed by using an appropriate level test gas in order to check operation. Full
testing and calibration checking takes place during a Medem commissioning.

8
00243
Basic Connections
SEC-Le
230v Supply
3Amp Fused Spur
EM Stop Buttons,
Thermal links
(Normally closed)
For multiple, connect in
series.
Pressure Sender unit
mounts on to the body of the gas
valve
(Required)
Gas Solenoid
Live feed through the
Medem CM2M-K2 channel
current Monitor
fans Fan speed
controls Fan live
Supply
Fire Alarm
Requires a volt
free NC contact
Where using 3 phase fans
interlock on a single phase
See page nine
Earth Connections not shown
0-10v output for
connecting to a fan
speed controller
Two core low voltage connection
6 core low voltage
+ - 12v Power
S1 = Supply Fan N C contact
E1 = Extract Fan N C contact
Fan Interlock Connections
4 Core
connection
Medem
Gas detectors
Multiple,
connect in
parallel

9
00243
Electrical contactor
SEC-Le
Method 1 (
Preferred
)
Using this wiring method, when isolating the supply there are no other voltages present within the panel.
IMPORTANT! If wired this way, a warning notice must be attached to the panel to indicate that there
are two separate mains feeds.
Contactor coil
Live feed through switched relay
To bench
sockets
L N
Supply in
230v Supply
3Amp Fused Spur
Electrical Contactor
230v Supply
3Amp Fused Spur
Method ne (Preferred)
Method Two

10
00243
SEC-Le Pressure Sender & Valve connection
Incorrect
Ensure that the valve is correctly installed with regard to the direction of the flow of gas and that the Sender Unit is fitted the
correct way round. (Note: there is no flow “through” the pressure sender unit, it is purely reading the pressures either side of the
valve.
Correct
Pressur
e
Solenoid
Never mount the valve such that the Solenoid or Sender Unit are below the horizontal.
Inlet Side Upstream Outlet Side Downstream
Direction of flow
Gas Solenoid and Sender Unit Mounting
Pressure sender unit