IntelliSense SECURIT 900C Manual de usuario

INSTALLATION
MANUAL
SECURIT 900C CONTROL PANEL

2
CONTENTS
WARNINGS 4
STANDARDS 4
WARRANTY STATEMENT 4
PRODUCT DESCRIPTION 4
AVAILABLE PARTS 4
INTENDED USE 4
FACTORY DEFAULTS 5
INSTALLATION 6
MOUNTING 6
PCB LAYOUT 6
WIRING 6
ELECTRICAL SAFETY NOTICE 6
BATTERY SPECIFIATION 7
TELEPHONE CONNECTIONS 7
DETECTOR CIRCUITS 7
NORMALLY CLOSED 7
DOUBLE BALANCED 7
SINGLE END OF LINE 8
SOUNDERS, SPEAKERS & STROBE WIRING 8
INTERNAL SPEAKER 8
AUXILIARY DC DETECTOR POWER 8
TRIGGER OUTPUT 8
DETECTOR RESET 8
SET LATCH 8
ALARM OUTPUT 8
MOUNTING KEYPADS 9
WIRING KEYPADS 9
INITIAL POWER UP 9
ENGINEER MODE 9
ENGINEER RESET 9
PROGRAMMING CONVENTIONS 10
REVIEW PROGRAMMING 10
ZONE PROGRAMMING 10
FULL SET 10
PART SET 10
NIGHT SET 11
SYSTEM OPTIONS 11
EXIT TIME 11
ENTRY TIME 11
BELL CUT-OFF TIME 12
PART SET EXIT WARNING 12
PART SET BELLS & STROBE 12
NIGHT SET BELLS & STROBE 12
ALARM TRIGGER OUTPUT 12
QUICK SET 12
SET INHIBIT 13
MAINS FAIL WARNING 13
SUPPLIMENTARY ENTRY ALARM DELAY 13
ALARM RESET 13
KEYPAD SOFT KEY ALARMS 13
KEYPAD LOCKOUT 13
BELL OUTPUT POLARITY 14
ALARM OUTPUT POLARITY 14
TAMPER ALARM RESET 14

3
ZONE MODE 14
COMMUNICATIONS 14
PRIMARY TELEPHONE NUMBER 14
SECONDARY TELEPHONE NUMBER 14
ACCOUNT NUMBER 14
USER CODE 8 DURESS ALARM 14
DOWNLOADER TELEPHONE NUMBER 15
DOWNLOADER ID NUMBER 15
AUTO ANSWER RING COUNT 15
ANSWERING MACHINE DEFEAT 15
COMMUNICATIONS FORMAT 15
HANDSHAKE FORMAT 15
DUAL REPORTING 15
DIAL TYPE 15
LINE FAULT INHIBIT SETTING 15
BELL DELAY 16
PUSH TO SET 16
WHEN TO COMMUNICATE 16
LINE FAULT 16
DOWNLOADER OPTIONS 16
ZONE ALARM COUNT LOCKOUT 16
COMMUNICATE REPORT TYPES 17
FIRE ALARMS 17
PA ALARMS 17
ALARMS 17
OPEN / CLOSE 17
DAY TAMPERS 17
ABORT 17
CONFIRMED ALARM 17
LOW BATTERY & MAINS LOSS 18
PERIODIC TEST REPORTS 18
ISOLATE 18
INVERT OPEN / CLOSE 18
DOUBLE KNOCK ZONE 18
ISOLATION ALLOWED 18
COMMUNICATE RESTORE 18
ENTRY DEVIATION 19
PRINT EVENT LOG 19
VIEWING EVENT LOG 19
VIEW EVENT LOG FROM DOWNLOADER 19
RESTORE FACTORY PROGRAMMING DEFAULTS 20
RESTORE DEFAULT CODES 20
SOFTWARE VERSION 20
ADVANCED COMMUNICATIONS 20
TECHNISTORE VERSION 20
CONFIRMED ALARM TIME WINDOW 20
ENGINEER AND USER CODES 20
DOWNLOADER FIRST CONNECTION 21/22
FAULT FINDING 23
FREQUENTLY ASKED QUESTIONS 23
SPECIFICATIONS 24
CTR21 INTERWORK 24
QUICK PROGRAMMING GUIDE 25/27
GENERAL WIRING DIAGRAM 28
SOUNDER CONNECTION CHART 28
NOTES 28/30
ZONE CONFIGURATION CHART 31

4
WARNINGS
Prolonged short circuit of any supply can cause damage to the unit. Take the necessary
precautions in not allowing liquids to spill on or into the unit.
STANDARDS
This unit conforms to EMC directive 89/336/EEC, LVD 73/23/EEC & R&TTE (CTR21).
This unit has been tested and has proven to meet all current emission and immunity
regulations as set out by the EU. This unit conforms to the requirements of BS4737 part 1
1986 which relates to security control equipment.
WARRANTY STATEMENT
This product is covered by the IntelliSense warranty in force as of the purchase date. A
copy may be obtained from the address at the end of this document.
PRODUCT DESCRIPTION
The Securit 900C is an 8-zone programmable microprocessor control panel with onboard
communicator allowing remote upload and download. There are many options in the
programming functions to allow the control panel to be versatile and user friendly. This
panel is the ideal choice for residential or light commercial installations where remote
communications are needed.
AVAILABLE PARTS
A selection of spares and extras are available. These are:
•Remote Keypad giving full control over the control panel.
•Spare PCB for replacement in the event of damage.
These can be obtained from your original place of purchase.
INTENDED USE
This panel must be installed by a competent person. It is designed to be used in
residential and smaller commercial applications such as homes, shops, offices etc.

5
FACTORY DEFAULTS
User Code 1 (master) 1234
User Code 2 - 8 Disabled
Engineer Code 9090
Full Set Exit Time 30 Seconds
Night Set Exit Time 30 Seconds
Entry time 30 Seconds
Sounder Ring Time 20 Minutes
Bell Trigger Polarity Negative
Zone Mode Normally Closed loops
Zone Programming
Zone Full Set Part Set Night Set
1Final Exit Final Exit Final Exit
2Walkthrough Walkthrough Final Exit
3Alarm Alarm Alarm
4Alarm Alarm Alarm
5Alarm Alarm Alarm
6Alarm Alarm Alarm
7Alarm Alarm Alarm
8Alarm Alarm Alarm
Zone Lockout After 2 alarms
Double Knock Zone None
Part Set Exit Warning Silent
Part Set External Bell On
Night Set External Bell On
Alarm Trigger Output Alarm
Set Inhibit Mains fail only
Alarm Reset Customer
Tamper Reset Customer
Easy Set Disabled
User 8 as Duress Disabled
Zone Isolation Allowed
Communications Alarms in all set modes
Alarm Verification time 45 minutes
Auto Answer Ring Count 14 rings
Bell Delay None
Dial Type DTMF
Supplementary Entry Alarm Delay None
Entry Deviation Not allowed
Line Fault Enabled
Line Fault Set Inhibit Disabled
Restore Sent at unset
Technistore Version 000
Verified Alarms Not enabled

6
INSTALLATION
Locate the control panel out of sight, such as in a hall, under stairs or in a
cupboard where connection is easy and the detector zone and mains
cables can be concealed. Avoid areas subject to high temperatures or
humidity such as next to a boiler, airing cupboard or conservatory.
MOUNTING
1. Remove the lid screws and remove lid.
2. Remove the PCB or keypad packaging.
3. Place the panel in the selected position and mark the fixing holes.
4. Mount the panel securely using all three mounting hole positions.
5. Attach the tamper spring and mount the PCB onto the support pillars.
6. Connect the transformer secondary leads to the AC terminals.
7. Connect the battery leads to BATTERY + and -. Observer polarity.
WIRING THE CONTROL PANEL
ELECTRICAL SAFETY NOTICE
THIS PRODUCT MUST BE EARTHED
This Power Supply must be permanently connected to the mains
supply in accordance with current IEE wiring regulations. A 3 amp
fused spur, installed by a qualified electrician, is strongly
recommended.
Any fault which could be mains related must be diagnosed and
corrected by a qualified electrician to ensure continued safe
operation.
CAUTION: Under certain circumstances the transformer
metalwork can reach 70°C. This is normal and within prescribed
limits.
INSTALLATION
MOUNTING
PCB LAYOUT
WIRING
ELECTRICAL
SAFETY
NOTICE

7
BATTERY SPECIFICATION
Maximum battery size is12 V 7.0 Ah. The panel requires a standby
battery to be fitted to provide power in the event of mains failure. A valve
regulated lead acid battery must be used. Observe the battery polarity.
Take great care to connect correctly.
TELEPHONE CONNECTIONS
The telephone connections, A & B on TB5, must be hard-wired to the
incoming telephone line. If the master socket is the NTE5/CTE5, the
connection can be carried out by the installation engineer otherwise the
network operator must make the connection. It must NOT be installed as
an extension to a payphone.
The panel is approved to EEC 98/482/EEC (R&TTE Directive, CTR21-see
Page 23 for a list of countries) for single terminal connection to the Public
Switched Telephone Network (PSTN) for
•Auto dialling •Auto Answer
•Modem Communications •Auto Clearing
•Multiple Repeat attempts •Series Connections
•Operation with Call Process Monitoring (CPM) tone recognition
DETECTOR CIRCUITS
Normally Closed Double Balanced EOL Single End-of-Line
Connections for up to eight alarm circuits. Normally closed detection
devices must be used. The Zones may be programmed for normally
closed loop, double balanced or single End-of-Line resistor modes.
Programmed as Normally Closed (Factory default)
Wire a shorting link across any unused zones. One or more
devices may be connected to each alarm circuit. These should be
connected in a series configuration. All zone tampers should be
wired in series and connected to the Zone Tamp terminals.
Programmed as Double Balanced End-of-Line
Wire a 1kΩresistor across any unused zones. Only one device
should be connected to each alarm circuit. Wire the zone and
tamper connections in series with a 1kΩresistor, fit a second 1kΩ
resistor across the alarm contact. All other normally closed
tampers should wired in series and be connected to the Zone
Tamp terminals.
BATTERY
SPECIFICATION
TELEPHONE
CONNECTIONS
DETECTOR
CIRCUITS
DOUBLE
BALANCED
NORMALLY
CLOSED

8
Programmed as Single End-of-Line
Wire a 1kΩresistor across any unused zones. Only one device
should be connected to each alarm circuit. Wire the zone in
series with a 1kΩresistor fitted within the detector. All zone
tampers should be wired in series and connected to the Zone
Tamp terminals.
INTERNAL SOUNDERS, SPEAKERS & STROBE WIRING
This shows the connection for external sounder and strobe. Please note
default sounder trigger is applied negative, (negative ring.).
BELL + Sounder hold off/strobe
positive supply
BELL – Sounder switched
negative trigger
STRB Strobe switched negative
trigger
BTMP – R Sounder tamper return
(negative)
BTMP – Sounder hold off supply &
sounder tamper feed
(negative)
A 16 Ω(ohm) speaker may be fitted between the AUX + & LS terminals.
If two speakers are required, these should be wired in series.
AUX DC - DETECTOR POWER
The auxiliary power is provided from connections marked AUX. This is
to provide the 12 V supply for detectors e.g. movement or glassbreak
detectors. The auxiliary power output is rated at 500 mA max. (12 VDC
nominal).
TRIGGER OUTPUT (TRIG)
This is a multifunction output and can be programmed using Menu 47.
OPTION 1 DETECTOR RESET (Menu 47-1)
Some detectors require the removal of power to reset (e.g. Viper Plus®
or smoke detectors). The TRIG terminal can be programmed to be used
as an 'ID' output using option 4-7-1. The TRIG terminal should then be
used as the negative supply for these devices. The positive supply
should be taken from the AUX +.
OPTION 2 SET LATCH (Menu 47-2)
If latching detectors are used the 'TRIG' should be connected to the
appropriate SET or LATCH terminal in your detector connection. It is
normally high (12 V) going low (0 V) when set, going high in alarm or
when the entry sequence starts. See glossary for explanation.
OPTION 3 ALARM OUTPUT (menu 47-3)
This option sets the output normally high (12 V), going low in Alarm,
Panic or Fire Alarm.
SINGLE
END OF LINE
SOUNDERS,
SPEAKERS
& STROBES
INTERNAL
SPEAKER
AUXILIARY DC
DETECTOR
POWER
TRIGGER
OUTPUT
DETECTOR
RESET
SET LATCH
ALARM
OUTPUT

9
MOUNTING A REMOTE KEYPADS
1. Choose the keypad location and then mark the holes for mounting.
2. Make sure the cable is run through the backbox.
3. Screw the backbox in the selected position making sure it is not
twisted.
WIRING REMOTE KEYPADS
Use 4-core cable for connection of all remote keypads. Connect the
cable, making sure each wire goes to a like named terminal in the panel.
KPD goes to KPAD, +to AUX + and -to AUX -. Tamper is signalled
through the data bus so no separate connection is required.
Individual keypads do not need to be identified to the system. If more
than one remote keypad is used it can be either wired back the control
panel or daisy chained from another keypad. All connections are in
parallel.
INITIAL POWER UP
Prior to the full wiring of the panel we recommend the following installation
stages. The lid should remain off the main control panel. Do NOT
connect the battery yet.
1. Connect the keypad, wire and switch on the mains supply. The
keypad buzzer will start. This denotes a tamper alarm.
2. Enter 1 2 3 4. This will silence the keypad buzzer. This has now
acknowledged and cancelled the alarm. However, because the panel
lid is removed, the main tamper loop is open and the keypad will
indicate the tamper. This is normal.
3. Close the panel lid, enter 1 2 3 4, check the tamper LED clears.
4. Power down and complete the wiring of the control panel. NEVER
wire the control panel live.
5. Power back up, enter 1 2 3 4 to cancel the alarm and enter engineer
mode by entering 9090#*. The panel is now ready for
programming.
ENGINEER MODE
To enter engineer mode, enter the engineer code and then press the #
and * keys. The mains light will flash and the keypad will bleep twice to
signify the panel has entered engineer mode. Entering engineer mode
will abort any communications that may be in progress.
To exit engineer mode, close ALL tamper circuits and enter the #and *
keys.
ENGINEER RESET
To perform an engineer reset, enter the engineer code. There is no need
to enter engineer programme mode.
MOUNTING
REMOTE
KEYPADS
WIRING
REMOTE
KEYPADS
INITIAL POWER
UP
ENTER & EXIT
ENGINEER
MODE
ENGINEER
RESET

10
PROGRAMMING CONVENTIONS
The following conventions are used in the Menu tables:
(z)Zone Number – enter key for required zone number.
(o)Option Number – enter key for required option number.
Two bleeps will follow a successful data entry.
The currently programmed setting in menu options can easily be
reviewed. With the exception of menu 6, enter the first menu number
followed by 00. The display will sequence through the current setting
for each option selected in the group eg. to view night set zones enter 3
0 0. The display will step through the setting starting at zone 1 and
ending with zone 8. A bleep will be heard each time the display steps.
To review menu 6 (the communications options) enter 6 0 followed by
the sub option number. eg. to review the primary telephone number
enter 6 0 1. The display will step through each digit of the programmed
number. A bleep will be heard each time the display steps. The
display will show numbers 1 through 8, with ‘day’ corresponding to 0
and ‘Tamper’ corresponding to 9.
ZONE PROGRAMMING
Any zone may have independent options programmed for Full, Part &
Night set.
FULL SET ZONE PROGRAMMING MENU 1
Enter 1-(z)-(o). Enter 1followed by the key corresponding to the Option
Number required from the table below:
Enter 0Not Used
Enter 1Final Exit
Enter 2Keyswitch
Enter 3Full Alarm
Enter 4Walkthrough
Enter 5Tamper (24 hr)
Enter 6Silent PA
Enter 7Audible PA
Enter 8Exit Terminator
Enter 9Fire
PART SET ZONE PROGRAMMING MENU 2
Enter 2-(z)-(o). Enter 2followed by the key corresponding to the Option
Number required from the table below:
Enter 0Not Used
Enter 1Final Exit
Enter 2Keyswitch
Enter 3Full Alarm
Enter 4Walkthrough
Enter 5Tamper (24 hr)
Enter 6Silent PA
Enter 7Audible PA
Enter 8Exit Terminator
Enter 9Fire
PROGRAMMING
CONVENTIONS
REVIEWING
PROGRAMMING
ZONE
PROGRAMMING
FULL SET
PART SET
Otros manuales para SECURIT 900C
1
Tabla de contenidos
Otros manuales de Panel de control de IntelliSense