Intellihot i200 Manual de usuario

Troubleshooting
Guide
This guide contains information for
identifying and correcting issues
that may arise.
Product Support / Warranty
If the water heater requires additional service, please use one of the following options
for contacting Intellihot Technical Support:
- Call: 309-473-8040 (toll-free 1-877-835-1705), and press 3
- Email: [email protected]
When you contact Technical Support, please have the following information ready:
- Model Number
- Serial Number
- Date purchase / Date installed
- Installation location & application
- Error code (if any) or other problem with the unit
Applicable Models:
i200
i200P
i250
i250P
i200X
i201X
i250X
i251X
iQ251
iQ251D
iQ751
iQ1001
iQ1501


Table of Contents
Error Code List & Suggested Tool List......................................................................2
E1-Blower Speed Fault...................................................................................................3
E3-Blocked Flue................................................................................................................4
E7-Ignition Failure...........................................................................................................5
E9-Temperature Sensor Shorted................................................................................6
EA-Temperature Sensor Open Circuit......................................................................7
EC-Flue Temperature Exceeded.................................................................................8
Ed-Heat Exchanger Outlet Temperature Exceeded............................................9
Flashing Icon..............................................................................................................10
Icon Flashing......................................................................................................11
Recirculation Icon Flashing................................................................................12
Blank (Blue)/Illegible Display....................................................................................13
Breaker Tripped (Over-Load)....................................................................................14
Dead Unit-No Powerup..............................................................................................15
No Hot Water.................................................................................................................16
Rough Ignition...............................................................................................................17
Rumbling.........................................................................................................................18
Water Leaks.....................................................................................................................19
Appendix
Blower Replacement..............................................................................................20
Gas Valve Replacement.........................................................................................21
Controller Pin Layout.............................................................................................24
Wiring Diagram (Wall-Hung)...............................................................................24
Wiring Diagram (Floor-Mount)...........................................................................25
Electrode Replacement.........................................................................................23
1

Error Code List
Suggested Tool List
- Digital Manometer
- Electrical Multimeter
- Flue Gas Analyzer (for NOx & CO2)
- 7mm Socket & Ratchet
- #1 Phillips Screwdriver
- #2 Phillips Screwdriver
- Instrument Flat Blade Screwdriver
- Pliers
- Adjustable Wrench
Code Description Page
E1 Blower Speed Fault 3
E3 Blocked Flue 4
E7 Ignition Failure 5
E9 Temperature Sensor Shorted 6
EA Temperature Sensor Open Circuit 7
EC Flue Temperature Exceeded 8
Ed Heat Exchanger Outlet Temperature Exceeded 9
2

E1 Blower Speed Fault
E1-Blower
Speed Fault
Is
Blower
Noisy?
Yes
Check blower.
Is there a broken
vane?
No
Does
Blower Run
on Start-up
No
Yes
Unplug
blower and
measure 120V at the
3-pin Connector
(J15)?
Replace Blower
No
Check
fuse. Is it
blown?
No
Replace controller
Yes
Replace Fuse
Yes
No Remove blower
and inspect inside
for damage.
Power cycle unit and at
start up, use a
multimeter to check
PWM at J18.
Does PWM
read between
10-90%? Yes
No
Replace blower
Check
J18 & J15.
Are the contacts
loose?
No
Repair/tighten
connectors
Yes
RED LED
(BURNER ON)
GREEN LED
(POWER)
FUSE
FUSE
ON
DIP SWITCH SW1
FUEL SELECT
NG
LP
DIP SWITCH SW3
ON
OFF
OFF
CASCADING
CONNECTIONS
J12
J14
J15
J23
J7 J18 J11 J3 J1
J9
J10
J5
J19A J20
J19B
J8
E12
Red
Black
3

E3-Blocked Flue
E3-Blocked flue
Check
exhaust
termination. Is it
blocked?
Yes
Remove blockage
and Install screens
if not installed
No
Are
the drain
hoses sloped
away from
unit?
Yes
Check for double
loops, air locks or
debris in loop
No
Slope drain per
Manual
Check Air
switch wiring
(green/black). Is it
loose
Yes
Repair faulty
wiring at air switch
No
Is
vent
piping sized
(diameter & total
length and installed
per manual?
No
Yes
Contact
Authorized
Service Personnel
Correct piping per
manual specs
Turn off
gas and
remove condensate
line. Remove the
condensate tube/input
trap. Is it
blocked?
No
Yes
4

E7-Ignition Failure
E7-Ignition
Failure
Nat.
Gas or
Propane?
Propane
Gas
Is LP
conversions
completed per
manual?
Yes
No
Complete the
conversion per the
manual
Are the
regulators & gas
lines sized for
loads? Yes
Check
the static gas
pressure. Is it
within specs?
No
Size gas lines and
regulators for max
BTU/h
requirements
Yes Put unit at maximum
firing value. Did pressure
drop less than 0.5" W.C.?
No
Gas lines and/or
regulators
inadequate.
Please correct.
Yes
No
Is
dynamic
pressure within
spec?
Yes
Overheat
Hi-limit tripped?
Regulator or gas
lines inadaquate.
Please correct.
Replace switch for
wall-hung, for IQ
check flow change
requirement. Check
recirc pump
Check wiring
to gas valve and to
DSI (brown/blue). Is it
damaged?
Is the
flame visible
through the
viewport? Yes
No
Remove
igniter and
inspect. (Gap and
cleanliness)
Is red
LED lit up on
controller? Yes
No
Check white wire
from electrode to
controller (E12)
Contact an
authorized service
technician
Bad
Replace the igniter
Good
Shut off
gas and test fire
to see if sparks at
the gap
Yes
No
Replace igniter
Repair or
replace wiring.
Yes
No Check for 120 V at J23
pins during ignition
Replace gas valveReplace controller
Yes
No
Is flame
visible during
ignition?
No
No
Yes
No
Yes
Go to **
**
RED LED
(BURNER ON)
GREEN LED
(POWER)
FUSE
FUSE
ON
DIP SWITCH SW1
FUEL SELECT
NG
LP
DIP SWITCH SW3
ON
OFF
OFF
CASCADING
CONNECTIONS
J12
J14
J15
J23
J7 J18 J11 J3 J1
J9
J10
J5
J19A J20
J19B
J8
E12
5

E9 Temperature Sensor Shorted
E9-Temp.
Sensor Shorted
Is
Sensor
wiring or pigtails
damaged or
corroded?
Yes
Repair nicked or
broken sensor
wiring/connectors.
No
Verify Secondary Sensor code:
HE-heat exchanger water outlet temperature sensor (orange wire)
FL-flue temperature sensor (gray wire)
IN-inlet water temperature sensor (blue wire)
rE-Recirculation temperature sensor (white wire)
Ou-Domestic hot water outlet temperature sensor (green wire)
Contact
Authorized
Service Personnel
Check
harness
connector J3. Is it
damaged?
Repair or replace
connector wire.
Yes
No
Measure
resistance of sensor
using multimeter. Is it
within spec?
No
Replace
corresponding
sensor
Yes
RED LED
(BURNER ON)
GREEN LED
(POWER)
FUSE
FUSE
ON
DIP SWITCH SW1
FUEL SELECT
NG
LP
DIP SWITCH SW3
ON
OFF
OFF
CASCADING
CONNECTIONS
J12
J14
J15
J23
J7 J18 J11 J3 J1
J9
J10
J5
J19A J20
J19B
J8
E12
Temp of Water
(°F)
Sensor Resistance
(kW)
50 18
77 10
140 3
6

EA Error Code-Temp Sensor Open Circuit
EA - Temp
Sensor-open circuit
Verify Secondary Sensor code:
HE-heat exchanger water outlet temperature sensor (orange wire)
FL-flue temperature sensor (gray wire)
IN-inlet water temperature sensor (blue wire)
rE-Recirculation temperature sensor (white wire)
Ou-Domestic hot water outlet temperature sensor (green wire)
Is
Sensor
wiring or pigtails
damaged or
corroded?
Yes
Repair nicked or
broken sensor
wiring/connectors.
No Contact
Authorized
Service Personnel
Check
harness
connector J3. Is it
damaged?
Repair or replace
connector wire.
Yes
No
Measure
resistance of sensor
using multimeter. Is it
within spec?
No
Replace
corresponding
sensor
Yes
RED LED
(BURNER ON)
GREEN LED
(POWER)
FUSE
FUSE
ON
DIP SWITCH SW1
FUEL SELECT
NG
LP
DIP SWITCH SW3
ON
OFF
OFF
CASCADING
CONNECTIONS
J12
J14
J15
J23
J7 J18 J11 J3 J1
J9
J10
J5
J19A J20
J19B
J8
E12
Temp of Water
(°F)
Sensor Resistance
(kW)
50 18
77 10
140 3
7

8