Infrapower IPM-02 Manual de usuario

www.austin-hughes.comUM-IPM-02-Q414V3
IPM-02 PDU management software
WkWh Monitored PDU
WS kWh Switched PDU
PDU Inspired by Your Data Center
User Manual
Designed and manufactured by Austin Hughes

www.austin-hughes.comUM-IPM-02-Q414V3
Legal Information
First English printing, October 2002
Information in this document has been carefully checked for accuracy; however, no guarantee is given to the correctness
of the contents. The information in this document is subject to change without notice. We are not liable for any injury or
loss that results from the use of this equipment.
Safety Instructions
Please read all of these instructions carefully before you use the device. Save this manual for
future reference.
■Unplug equipment before cleaning. Don’t use liquid or spray detergent; use a moist cloth.
■Keep equipment away from excessive humidity and heat. Preferably, keep it in an air-conditioned environment with
temperatures not exceeding 40º Celsius (104º Fahrenheit).
■When installing, place the equipment on a sturdy, level surface to prevent it from accidentally falling and causing dam
age to other equipment or injury to persons nearby.
■When the equipment is in an open position, do not cover, block or in any way obstruct the gap between it and the
power supply. Proper air convection is necessary to keep it from overheating.
■Arrange the equipment’s power cord in such a way that others won’t trip or fall over it.
■If you are using a power cord that didn’t ship with the equipment, ensure that it is rated for the voltage and current
labelled on the equipment’s electrical ratings label. The voltage rating on the cord should be higher than the one listed
on the equipment’s ratings label.
■Observe all precautions and warnings attached to the equipment.
■If you don’t intend on using the equipment for a long time, disconnect it from the power outlet to prevent being dam
aged by transient over-voltage.
■Keep all liquids away from the equipment to minimize the risk of accidental spillage. Liquid spilled on to the power
supply or on other hardware may cause damage, fire or electrical shock.
■Only qualified service personnel should open the chassis. Opening it yourself could damage the equipment and invali
date its warranty.
■If any part of the equipment becomes damaged or stops functioning, have it checked by qualified service personnel.
What the warranty does not cover
■Any product, on which the serial number has been defaced, modified or removed.
■Damage, deterioration or malfunction resulting from:
□Accident, misuse, neglect, fire, water, lightning, or other acts of nature, unauthorized product modification, or
failure to follow instructions supplied with the product.
□Repair or attempted repair by anyone not authorized by us.
□Any damage of the product due to shipment.
□Removal or installation of the product.
□Causes external to the product, such as electric power fluctuation or failure.
□Use of supplies or parts not meeting our specifications.
□Normal wear and tear.
□Any other causes which does not relate to a product defect.
■Removal, installation, and set-up service charges.
Regulatory Notices Federal Communications Commission (FCC)
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the
FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential instal-
lation.
Any changes or modifications made to this equipment may void the user’s authority to operate this equipment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following measures:
■Re-position or relocate the receiving antenna.
■Increase the separation between the equipment and receiver.
■Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

www.austin-hughes.comUM-IPM-02-Q414V3
The equipment comes with the standard parts shown on the package contents. Check and make sure they are included and in good
condition. If anything is missing, or damage, contact the supplier immediately.
Unpacking
Package contents
( 1 ) Vertical W / WS PDU x 1
- VMS mounting screw, set of 2 or 3 - VMB mounting bracket set
2 - 3 sets
+
M4 M4 x 2 M6 x 2 M6 nut x 2
PEG
M4
M4
M6
M6
M6 nut
M6 nut
Bracket x 2
( 2 ) Rackmount W / WS PDU x 1
OR
Power ON
■Connect the PDU into an appropriately rated receptacle
■When the PDU is power on, the LED display will light up. That means all outlets are activated
■Keep the equipments in the power off position until it is plugged into the PDU
Don’t exceed the outlet, branch or phase limitations
All electrical power and power control wiring must be installed by a qualified electrician and comply with local
and national regulations.
LINK OUT
TH1 TH2
65
37.545
22.3
15.9
3.48
3.49
15.8
31.7
6.97
LINK OUT
TH1 TH2
6537.545
22.3
15.9
3.48
3.49
15.8
31.7
6.97

www.austin-hughes.comUM-IPM-02-Q414V3
Content
Part I. Hardware
< 1.1 > W /WS PDU Key Features
< 1.2 > W Meter Display & Setting
< 1.3 > PDU Meter Setting & Cascade
< 1.4 > Temp. / Humidity Sensor Connection & Specification
< 1.5 > IP Dongle Installation & Connection
< 1.6 > Easy Change on PDU Power Feed Position
Part II. Software
< 2.1 > Key Features
< 2.2 > IP Dongle Configuration
< 2.3 > Hardware Requirements of the Management PC
< 2.4 > Supported OS Platform & Language
< 2.5 > Software Download
< 2.6 > First Time Start-up Setting
< 2.7 > Change Port no. of Web Server
Part III. System Setup & Remote Access
< 3.1 > System Setup
< 3.2 > Remote Access
Part IV. Software Usage & Operation
P. 1
P. 11
P. 18
P. 25

www.austin-hughes.comUM-IPM-02-Q414V3
Content
Part V. Events / Log / Report
Part VI. SNMP Setup / Firmware Upgrade
Part VII. FAQ
Part VIII. Troubleshooting
P.30
P.33
P. 37
P. 40

www.austin-hughes.comUM-IPM-02-Q414V3 P. 1
kWh PDU
Monitored Switched
WWS
Outlet Measurement
Circuit kWh Measurment
Temp-Humid Sensor port x 2
16 Levels in Single Daisy Chain
One IP Access 16 PDU Levels
SNMP Capability via IP Dongle
Hot-pluggable Meter w/ 1.8” Color LCD
Outlet Switch ON / OFF
Local kWh & Amp Meter
Vertical & Horizontal PDUs
Tool-less Mounting for Vertical PDU
Management Software Editions
( Free ) IPM-03
IPM-02
PPS-02-S
(via IPD-02S)
IPM-03
IPM-02
PPS-02-S
(via IPD-02S)
Part I. Hardware
< 1.1 > W /WS PDU Key Features

www.austin-hughes.comUM-IPM-02-Q414V3 P. 2
Temp. + Humidity sensor port x 2
or
Temp. sensor port x 2
2
1.8” color LCD display
3
Menu button
Buzzer
4
6Reset button
5
For 1U / 2U rackmount PDU, on the front, on the rear
The buzzer only sounds when the circuit amp. over the alarm amp. setting.
Reset button is to re-power the meter. It will not affect any settings and memories.
53 4 1
PDU cascade port
1
2
All W series PDUs are equipped with a highly advanced and sophisticated component - W Meter. It
provides the cascade ports for daisy chain up to 16 x PDU. Furthermore, for IP PDU access, simply
connect 1 x IP Dongle for all daisy chain PDUs to save IP network address. Two sensor ports are
integrated for temperature & humidity monitoring. Creatively, 1.8” color LCD display offers a real time
local monitoring and detailed PDU status.
< 1.2 > W Meter Display & Setting

www.austin-hughes.comUM-IPM-02-Q414V3 P. 3
Display 6 only for Wi / WSi
outlet measurement PDU
Press to change °C / °F
Display 1.1
W meter 1.8” color LCD provides a sharp and highly visible reading for the local reading of Current
( Amp ), Voltage ( Volt ), Power ( kW ), Energy Consumption ( kWh ), Power Factor, Temperature &
Humidity.
< 1.2 > W Meter Display & Setting

www.austin-hughes.comUM-IPM-02-Q414V3 P. 4
Step 1 - Press the & button to display no.9 and press to confirm
Step 2 - Press the & button to PDU ID and press to confirm
Step 3 - In display 9.1, Press the & button to select PDU level no. & press to confirm
Step 4 - Press to exit
W meter allows the user to do some settings below :
Buzzer :
W meter allows the user to set the meter buzzer ON / OFF by meter’s 4 buttons.
All PDUs are shipped with the buzzer in ON status.
When the PDU’s circuit Amp is over alarm level, the buzzer will sound.
The user can press any button to stop the buzzer sound.
Screen OFF :
All PDUs are shipped with the metter LCD in always ON status.
W meter allows the user to turn off the meter LCD by time setting ( 1 - 60 mins, 0 = always ON )
When the meter is in OFF status, the user can press any button to make it ON.
PDU level setting :
< 1.2 > W Meter Display & Setting

www.austin-hughes.comUM-IPM-02-Q414V3 P. 5
■The PDU can be cascaded up to 16 levels
■For IP PDU access simply connect 1 x IP dongle - IPD-02-S
■1 x IP dongle allows access to 16 levels
PDU Daisy Chain up to 16 Levels
The W meter built-in not only provides the local power monitoring, but also the connection ports for
the PDU daisy chain. For daisy chain connection, each PDU just simply to be connected in series to
the next by Cat5/6 cables. Maximum 16 PDUs are supported in one daisy chain group.
1st level
PDU meter
Final level
PDU meter
3rd level
PDU meter
2nd level
PDU meter
Cat 5 / 6 cable
Up to 20M
Cat 5 / 6 cable
Up to 20M
For PDU level setting, please refer to previous page.
< 1.3 > PDU Meter Setting & Cascade