IGD TOCSIN 650 SERIES Guía de instalación

TOCSIN 650 SERIES
A d d r e s s a b l e D e t e c t o r C o n t r o l P a n e l
O p e r a t i o n a n d M a i n t e n a n c e
V 3 . 1
Triton House
Crosby Street
Stockport
Sk2 6SH
England
Tel: +44 (0)161 483 1415
Fax: +44 (0) 161 484 2345
Email: [email protected]
Website: www.internationalgasdetectors.co.uk
Addressable
2-Wire
FS646773
REF: T650 V3.1
EMS696504

2
Table of Contents
Help Section
Overall Dimensions
Interface Wiring
Specification
CE Declaration
Operating System
15
22
19
28
9
26
17
25
13
10
4
14
5
7
12
23
27
27
Addressable Detector Node
Highway Hub Controller Overview
Relay Card Overview
Relay Card Setup
User Actions
Overview
Menu overview
Putting Into Service
New Setup Sequence
The Sensor ZERO Function
Checking Reaction Time
The Sensor CALIBRATE Function
Troubleshooting
Standard Accessories Supplied
Accessories Available

2 Core Cable Connection (No Polarity)
RGB Backlit Display
It is recommended that control panels and all connected detectors are commissioned upon
installation and serviced every 6 months by an IGD trained technician. IGD can offer full training to
enable your staff to do the servicing or offer a competitive service from our fleet of service
engineers.
This product must be earthed in accordance with local safety regulations.
Standard options are indicated in the basic specifications on page 4
Up to 128 Detector Nodes
Main Features
Colour Touch Screen
° °
The control panel may be stored at temperatures between 0 C and 55 C. If stored at low temperatures
and then brought into a warmer environment, condensation may form on some components. In such a
situation , this condensation should be allowed to evaporate prior to use of the equipment. If stored at
high temperature, care should be taken to ensure that humidity condensation does not enter critical
electrical components, for example the power supply.
Up to 350 Detecor Nodes
750 Series
650 Series
Warnings and Performance Statements
The Tocsin 750 and 650 series control panels use the latest technology 2-wire addressable
highways to control gas detectors and associated accessories. Providing an extremely flexible and
low cost solution.
Internal or External Battery Backup
Cascade Panels as Master - Salve
Brief Introduction
Jog Wheel Interface
Service & Maintenance
The Control Panel leaves the factory configured for the supply voltage stated on the customers order.
Should the control panel be used in conjunction with portable generating equipment, care should be
taken to ensure that the electrical supply is within the tolerance band described above.
o
The Control Panel is designed to operate within specification for ambient temperature between 0 C
o
and 55 C, relative humidity up to 95% ( non-condensing ). Sensor specifications may differ.
Do not use a Control Panel for protection applications that has not been calibrated. If calibration seals
are missing from the control panel or have been tampered with or broken, then the control panel must
be re-calibrated and sealed by a trained engineer.
Substances and interfering gases can cause adverse effects on the performance or electrical safety of
the gas detection systems. Care should be taken to limit exposure to these poisoning substances, for
further advice and information contact head office
The response time of the entire system is determined by the time of response of all the parts of the
equipment within the gas detection system.
The relationship between the output signal and the gas concentration is linear, the control panel
interprets the signal and the gas level is displayed on the HMI or RGB backlit display. IGD hold
evidence of this linear performance which is available upon request.
We recommend users read the procedures described in BS EN 60079-29-2 for reference.

4
Basic Specification
Ambient Operating Humidity
150W PSU @ 230VAC Nominal
150W PSU @ 110V AC Nominal
300W PSU
Ambient Operating Temperature
Protection
(Range Dependant)
Displayed Detector Resolution
Connected Hubs
CE Declaration
Pressure Limits
Connected devices
Display
Warm up time
Max Power Consumption
EMC Compatibility
Air Velocity
88 to 127 V AC 50/60Hz by selection
190 to 260V AC 50/60Hz by selection
88 to 260V AC 50/60Hz by selection
1% LEL
2 x 8 LCD Display and Jog Wheel
0.1ppm
Full EC Declaration appears on Page 4
0 to 55 Degrees Centigrade
IP ratings do not imply that the equipment will detect gas during and after exposure to these conditions.
Calibration and maintenance may be required more frequently and should be assessed based upon exposure.
1%Vol
Cascade hub optional
Ip54
5-95% RH Non-Condensing (see sensor data)
0.1% Vol
2 Watts
15 minutes
800 to 1200mBar (80 to 120kPa)
see installer guide
Up to 128 Devices on single hub max 350 input channels
0-6M/S refer to installers guide for allowable orientation
1 ppm

EC Declaration of Conformity
Declares that the product listed as:
Addressable Gas Detection Control Panel
TOCSIN 650
Issued by: Oliver IGD Limited, Stockport, SK2 6SH , United Kingdom
Name: Andrew J Collier M.I.O.D
Position: Managing Director Date: 1 January 2019 Declaration Ref: T650-DEC-3
Signature: Declaration of Conformity in accordance with EN ISO/IEC 17050-1:2004
Are in conformity with the provisions of the following European Directive(s) when installed, operated, serviced and maintained
in accordance with the installation and operating instructions contained in the product documentation.
And that the standards and/or technical specifications referenced below have been applied or considered.
2004/108/EC EMC Directive
2006/95/EC Low Voltage Equipment Directive (note not applicable to 24V DC Powered Versions)
EN 50271:2001
EN 61779-1:2000
EN 61000-6-2: 2005
EN 61000-6-4/A1: 2011
EN 61000-3-2: 2014
EN 61000-3-3: 2013
Technical File Reference
EMC Limits. Limits for harmonic current emissions (equipment input current ≤ 16 A per phase)
Electrical apparatus for the detection and measurement of combustible gases, toxic gases or
Oxygen: requirements and tests for apparatus using software and or digital technologies.
Excluding requirements for SIL
EMC Generic standards. Immunity for industrial environments
Electrical apparatus for the detection and measurement of flammable gases, general
requirements and test methods.
EMC Generic standards. Emission standard for industrial environments
EMC Limits. Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems, for equipment with rated current ≤ 16 A per phase
T650-TF9
Issuers name and address:
Triton House
United Kingdom
Oliver IGD Limited of
Crosby St,
Stockport, SK2 6SH
EMC Tested by:
Concorde Way
Octagon House
TUV - SUD
PO 15 5RL Fareham
TUV Certificates and reports can be checked on-line at
https://www.tuev-sued.de/industry_and_consumer_products/certificates
Oliver IGD Limited Operate an
Independently assessed ATEX/IECEX
QAN.
United Kingdom
Quality Assurance Notification Number:
16PQAN0014
2585
Wrexham, LL13 9UZ
Units 16-18 Abenbury Way,
Quality Assurance Certificate Number
Wrexham Industrial Estate,
Select Oliver IGD when prompted on the website to view certificates
Certificate Number
E8N 15 05 91327 004
FS0646773 & EMS696504
Oliver IGD Limited operate an independently
assessed ISO9001:2015 Quality Management and
ISO14001:2015 Environmental Management System
Certificate Numbers
BSI Assurance UK LTD,
London, W4 4AL
United Kingdom

6
Gas detection systems must be correctly specified, installed and maintained in order to be effective.
Anyone undertaking elements of this work should have access to the necessary equipment and be able
to demonstrate competence. This will usually mean having passed a training competency course.
International Gas Detectors run training courses for safety survey, specification , installation and
service aspects of hazardous gas detection systems. In addition IGD can supply test equipment and
calibration gases necessary to undertake this work.
1. A zero grade gas usually instrument air or Nitrogen and a suitable calibration gas mixture is required.
Please the following points
2. The correct gas adaptors must be used to apply gases to detectors when zeroing and calibrating.
Incorrect application of gases can affect calibration results
3. Use equipment and gases traceable to a national standard. Any calibration will only be as good as
the equipment and materials used.
4. IGD supply fixed flow regulators for use with IGD calibration gas bottles which supplies gas at
0.5L/Min
Important Notes
Panel Options
TOCSIN 750 Series Controller
TOCSIN 750 Series Annunciator
Options With:
Display, Relay Output, Digital or
Analogue Input, Flammable Gas Detector
TOCSIN 750 Series Detectors
Flammable Gases, Toxic Gases
Oxygen
TOCSIN 102 Series Detectors 2-WIRE
Flammable Gases, Toxic Gases
Oxygen For ATEX Applications
Part Number
TOC-650-24
TOC-650-150
TOC-650-150BB
TOC-650-150B1
TOC-650-300
TOC-650-300B1
Description
24V DC Control Panel No Internal PSU
Standard Features inluding
2 x 8 RGB Display and Jog Wheel
4 Relays, 4 Highways
110/230V AC Control Panel 150W PSU
Standard Features inluding
2 x 8 RGB Display and Jog Wheel
4 Relays, 4 Highways
110/230V AC Control Panel 150W PSU
Standard Features inluding
2 x 8 RGB Display and Jog Wheel
4 Relays, 4 Highways
Built in 1.2AH Battery Backup
110/230V AC Control Panel 150W PSU
Standard Features inluding
2 x 8 RGB Display and Jog Wheel
4 Relays, 4 Highways
Built in 5AH Battery Backup
110/230V AC Control Panel 300W PSU
Standard Features inluding
2 x 8 RGB Display and Jog Wheel
4 Relays, 4 Highways
110/230V AC Control Panel 300W PSU
Standard Features inluding
2 x 8 RGB Display and Jog Wheel
4 Relays, 4 Highways
Built in 5AH Battery Backup

TOCSIN 650 PHYSICAL
Installation Cables
FRONT VIEW
382mm
292mm
72mm
120.5mm
134mm
20mm
48.5mm
Front Face
Top Face
Side Face
56.5mm
30mm
10 off 20mm
Cable Entries
360mm
Addressable
2-Wire
Supported Installation Cables 2 Core 1.5mmSQ or 2.5mmSQ See IGD Cable System Calculator
Typically SWA, MICC, FP200, SY, CY, System cables must be screened, refer to installers guide
General
Power can be taken from system modules for small current devices such as LED beacon sounders and is
limited to 100mA per module
Highways are fused at 2A, observe load calculations when planning, use boosters where necessary
Observe interface requirements for relays, fitting freewheel diodes and snubbers as indicated
Note cables run with modules sequentially wired.
End of line terminators, supplied with panels must be fitted for correct operation

8
Installation Guide
Failure to follow correct installation may result in poor performance and/or damage to system
components.
Copies of the installation guide are available in the downloads section of our website. Always check
you are using the latest versions of the supplied manuals by checking on the IGD website.
Your 750 Series control panel has been supplied with a separate installation guide. Please read this
before installing your system. The Installation guide provides information for correct cable selection,
how to correctly install cables and devices and ensure correct cable segregation. It is important to
read and understand this document prior to installation.
2-WIRE SYSTEMS
2 - W i r e G a s D e t e c t i o n S y s t e m I n s t a l l e r s G u i d e V x x
OL I VER I G D
Triton House
Crosby Street
Stockport
SK2 6SH
England
Tel: +44 (0)161 483 1415
Fax: +44 (0) 161 484 2345
Email: [email protected]
Website: www.internationalgasdetectors.co.uk
Addressable
2-Wire
Version 2.0
T750-INST
International Gas Detectors
IGD-Academy
IGD’s On-Line training academy is available to support your companies activities. The Academy
features a range of CPD approved training courses and ‘how to’ videos.
The academy can be found at: https://igdacademy.internationalgasdetectors.com
Please note that some courses are only available on a request basis. If you require a request only
course please email to request your account and course.[email protected]

T650 Control Panel & 2 Wire Hub Controller PCB Features
Power in
24V DC
Battery Connection
For Battery Backup
Ethernet
Rs485 Remote
(Modbus etc)
Display
Colour HMI
Display TOC-650 (2x8 LCD)
Fault Relay
Alarm Relay 1
Alarm Relay 2
Alarm Relay 3
Direct Beacon-Sounder O/P
Inputs for E-stops/Fire
4 off 2 Wire Ports Each supporting 32 Devices
128 Devices in Total
Two display options, either 650 style with jog wheel
or
HMI Style touch screen display
Note both displays can be fitted at the same time which can allow
the HMI display to be remote from the panel and used as a
system repeater or mimic
L1
L1 L1
L1
L1
L2
L2 L2
L2
L2
Hub cards can be cascaded to add more ports if
required. Note This is Polarity Sensitive And
Must be Connected L1 to L1 and L2 to L2.
Failure to observe polarity when cascading can
result in damage to the card

10
Tocsin 750 Addressable Relay Card Setting Relay Addresses
Press and hold the DOWN button until all LED's are OFF. Release the button
and the address currently set will be illuminated on the bottom five LED’s.
Use the UP and DOWN buttons to alter the address set as indicated in the
table below
To exit press and hold UP or DOWN button until all LED’s are off then release.
DOWN
BUTTON
UP
BUTTON
Each Addressable relay card must have its own unique base address. This can
be set on the card and is indicated below. The relays are then
addresses/numbered from that base address. The example below shows a card
with a default base address of 101
101
102
103
104
105
106
107
108
A0A4
100
108
116
124
101
109
117
125
102
110
118
126
103
111
119
127
104
112
120
128
105
113
121
129
106
114
122
130
107
115
123
131
1 2 3 4 5 1 2 3 4 5
NOTE: WHEN SETTING ADDRESSES YOU CANNOT HAVE TWO DEVICE ADDRESSES SET THE
SAME ON THE SAME ADDRESSABLE HIGHWAY or DEVICE.