SUGGESTED ENGINEERING SPECIFICATION
OVERVIEW
The boilers must be fully automatically controlled, wall mounted,
fanned, super-ecient condensing appliances utilising a
stainless steel heat exchanger and be suitable for connection to
a sealed water system.
CONTROLS
The condensing boilers must have connectivity for common
types of BMS. Additional modules may be used for volt free
connectivity. Where no BMS is present a modulating sequencer
must be available.
The boiler must be fully modulating with a 5:1 turndown ratio
and have control features enabling set point adjustment, heating
circuit control of one constant temperature and one DHW
circuit or 2 constant temperature circuits, and safety lock out
parameters including fault diagnosis for both boiler and external
components such as sensors or pumps.
Boiler capabilities must include, with the use of external
components, frost protection, weather or room compensation
and system pump control.
FLUE
The condensing boilers must be suitable for use with a room
sealed flue or open flue applications including
C13, C33 and B23 classifications. The combined flue outlet and
air inlet must be situated on the top
of the boiler.
HYDRAULIC
The condensing boiler must be suitable for connection to a
sealed water system. All hydraulic connections including flow
return and condensate drain must be located on the bottom of
the boiler. Hydraulic connections must be uniform across the
outputs available in the range to ensure ease of installation and
maintenance in mixed output cascades. The boiler must have
a maximum operating pressure of 4 bar and be suitable for
heating and indirect hot water systems.
DIMENSIONS
The condensing boiler range must have a universal compact
width and height across the range to ensure mixed output
cascades maintain the same universal configuration. Maximum
permitted wall area of 0.49m2.
MOUNTING
The condensing boilers can be installed either on the wall or
into a prefabricated floor mounted frame. Wall brackets must be
located at the top of the boiler and visible from the front to aid
installation.
EFFICIENCY
The condensing boilers are capable of high seasonal eciencies
with a minimum requirement of 96.02% and low NOx emissions
no greater than 36mg/kWH.
Models <70kW must have a Seasonal Space Heating Energy
Eciency of A.
APPROVALS
The boiler must be tested and certified to; EN 483,
EN 677, PREN 15420, BSEN 15417, BSEN 656, BSEN 60335-2-
102, BSEN 55014-1 and BSEN 55014-2 for use with Natural Gas.
Boilers are certified to meet the requirements of the EC Gas
Appliance Directive, Boiler Eciency Directive, EMC and Low
Voltage Directive.
The manufacturer must be ISO 9001 accredited.
SPECIFICATION
The boiler will be capable of flow rates for common systems
using 11°C to 20°C temperature dierentials.
CASCADE
The boiler must be configurable up to 4 boilers (max 540kW)
in cascade using a prefabricated frame and header kit.
WARRANTY
The boiler must be available with a 5 year warranty.
The Suggested Engineering Specification
is wording designed for specifiers to copy
and paste into their specifications to ensure
inclusion of Ideal Commercial boilers.