Housewatch 55-307 Manual de usuario

INFRARED SENSOR
INSTRUCTIONS
Model No: 55-307
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 1

CONTENTS
INTRODUCTION .........................................................................................3
IMPORTANT SAFETY INSTRUCTIONS .......................................................3
INSTALLING THE INFRARED SENSOR ..................................................4-5
SET UP AND OPERATION .......................................................................6-9
TROUBLESHOOTING................................................................................10
TECHNICAL SPECIFICATIONS..................................................................11
WARRANTY INFORMATION .....................................................................12
2
INTRODUCTION
The Housewatch indoor sensor is
range of indoor locations includ
hallways, kitchens, pantries etc.
IMPORTANT SAFETY
Please follow these instructions c
operate this sensor.
Ensure power is isolated before
Ensure the voltage marked on t
power supply to be used.
DO NOT mount on a conductiv
Must be installed by a licensed
AS/NZS 3000:2018.
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 2

NTS
..................................................3
..................................................3
...............................................4-5
...............................................6-9
................................................10
................................................11
................................................12
3
INTRODUCTION
The Housewatch indoor sensor is suitable for installation on ceilings in a
range of indoor locations including offices, conference rooms, hotels,
hallways, kitchens, pantries etc.
IMPORTANT SAFETY INSTRUCTIONS
Please follow these instructions carefully before attempting to install and
operate this sensor.
Ensure power is isolated before performing any work on the sensor.
Ensure the voltage marked on the product is the same as the electrical
power supply to be used.
DO NOT mount on a conductive surface.
Must be installed by a licensed electrician in accordance with
AS/NZS 3000:2018.
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 3

4
INSTALLING THE INFRARED SENSOR INSTALLING THE INFR
2) Cut a 75mm hole into the ceiling, taking care not to cut into any concealed
electrical wiring or services.
3) Pull through the electrical cables in preparation for connections to the
sensor.
4) Remove the transparent vinyl cover from the back of the sensor.
1) Isolate power
5) Connect the cable to the termina
as per FIGURE 2.
6) Fit the sensor in the ceiling onc
7) Ensure that associated lighting
the Australia wiring rules.
8) Reconnect power.
FIGURE 1
STEP 1 STEP 2
FI
STEP 3
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 4

5
ED SENSOR INSTALLING THE INFRARED SENSOR
g care not to cut into any concealed
preparation for connections to the
om the back of the sensor.
5) Connect the cable to the terminal block mounted on the back of the sensor
as per FIGURE 2.
6) Fit the sensor in the ceiling once the setup has been completed.
7) Ensure that associated lighting loads are correctly installed according to
the Australia wiring rules.
8) Reconnect power.
1
2
FIGURE 2
STEP 3
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 5

6
SET UP AND OPERATION SET UP AND OPERAT
The indoor sensor is equipped with a highly sensitive PIR (Passive Infrared)
motion detector. It utilises the infrared energy from the human body as the
control signal source to switch the load on once it enters the detection field.
The sensor automatically scans for movement between zones.
The indoor sensor will provide optimal performance and range when installed
in a vertical position approximately 2.2 to 4m above the ground; as is shown in
the diagrams in FIGURE 3 below. The horizontal coverage zone can reach up to
16m with an angle of 360°.
Time Duration:
The length of time the sensor will ac
from 10 seconds to 7 minutes ±2
with the clock) anti-clockwise will re
Lux Level:
The sensor has a built in photoelec
and darkness levels. Rotating the Lu
the day/night image), will ensure tha
the Lux control knob clockwise, the
night depending on the application
testing the sensor after installation.
Sensitivity:
The sensitivity control (marked with
the sensitivity of the sensor. This ad
of the PIR to prevent false triggering
required, the sensitivity adjustment
fully clockwise.
2.2~4m
8m 8m
Max:
8m
Max:
8m
360°
FIGURE 3
FI
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 6

7
SET UP AND OPERATION
hly sensitive PIR (Passive Infrared)
nergy from the human body as the
n once it enters the detection field.
ment between zones.
rformance and range when installed
m above the ground; as is shown in
ontal coverage zone can reach up to
Time Duration:
The length of time the sensor will activate a load after detection can be adjusted
from 10 seconds to 7 minutes ±2 minutes. Rotating the time knob (marked
with the clock) anti-clockwise will reduce the duration time.
Lux Level:
The sensor has a built in photoelectric cell that automatically detects daylight
and darkness levels. Rotating the Lux control knob anti-clockwise (marked with
the day/night image), will ensure that the sensor only works at night. By rotating
the Lux control knob clockwise, the sensor will work in both daylight and at
night depending on the application - the daylight setting is primarily used for
testing the sensor after installation.
Sensitivity:
The sensitivity control (marked with the sensor symbol) allows you to adjust
the sensitivity of the sensor. This adjustment is useful to adjust the sensitivity
of the PIR to prevent false triggering and to adjust the detection range. Unless
required, the sensitivity adjustment should be operated with the knob turned
fully clockwise.
8m
Max:
8m
3
FIGURE 4
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 7

8
SET UP AND OPERATION SET UP AND OPERAT
Walk Test
1) Rotate the Lux knob fully clockwise for daylight operation, set the time
control to minimum (anti-clockwise).
2) Turn on the power at the isolating switch. The load should turn on for a
short period of time (warm up 30 seconds).
3) Wait another 10 seconds for the circuit to stabilise.
4) Walk across the centre of the detection area until the load switches on. Your
sensor is now ready for final adjusting.
5) Adjust the time control to the desired level.
6) Adjust the sensitivity (if required) to limit detection range. This can be tested
via walk testing.
7) Adjust the Lux control to revert to night time operation. If the load is
required to switch on earlier, e.g. dusk; wait for the desired light level, and
slowly turn the Lux knob clockwise while someone walks across the centre
of the detection area.
Manual Override Feature
When the power is initially turned ON, the sensor operates in AUTO mode. In
this mode, the sensor turns the load ON and OFF automatically.
The manual override function means that the sensor can be put permanently
“ON”. In this mode the PIR sensor is disabled.
Resetting the Sensor into “Manual
9) To bypass the “AUTO mode” and
the wall switch “OFF” and “ON”
Wall switch action: OFF > ON > OFF
10) Wait for 3 seconds and the light
will be in the “MANUAL mode”.
Note: The maximum manual ov
sensor will automatically enter A
Setting the Sensor into “Auto Mod
1) To change back to “AUTO mode
10 seconds, then turn it back “O
2) Wall switch action: OFF, wait 10
3) The PIR sensor will enter into th
“ON” for 10 seconds, then will t
4) Now wait for about 10 seconds
will operate now in “AUTO mod
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 8

9
SET UP AND OPERATION
for daylight operation, set the time
witch. The load should turn on for a
onds).
t to stabilise.
area until the load switches on. Your
.
evel.
it detection range. This can be tested
night time operation. If the load is
; wait for the desired light level, and
ile someone walks across the centre
sensor operates in AUTO mode. In
nd OFF automatically.
the sensor can be put permanently
bled.
Resetting the Sensor into “Manual Mode”
9) To bypass the “AUTO mode” and set the sensor into “MANUAL mode”, turn
the wall switch “OFF” and “ON” twice within 2 seconds.
Wall switch action: OFF > ON > OFF > ON.
10) Wait for 3 seconds and the light will turn “ON” permanently and the sensor
will be in the “MANUAL mode”.
Note: The maximum manual override time is 8 hours, after this time the
sensor will automatically enter AUTO mode.
Setting the Sensor into “Auto Mode”
1) To change back to “AUTO mode”, turn the power “OFF” and wait for about
10 seconds, then turn it back “ON” again turning the switch “ON” once only.
2) Wall switch action: OFF, wait 10 seconds > ON.
3) The PIR sensor will enter into the “WARM-UP” mode and the load will stay
“ON” for 10 seconds, then will turn “OFF”.
4) Now wait for about 10 seconds for the circuit to stabilise and the sensor
will operate now in “AUTO mode”.
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 9

10
TROUBLESHOOTING TECHNICAL SPECIFIC
Installation of elect
out by a qualified el
Contact a qualified
break down.
Problem
Load does not
turn off
Load does not
turn on
Nuisance
triggered
Possible Cause
1) Auto off time is set
too long
2) Sensor is nuisance
triggered
3) Incorrect wiring
1) Exceeding the
detection range
2) No power is supplied
3) Incorrect wiring
There are heat sources,
highly reflective objects
or any objects which
may be swayed in the
wind within the
detection coverage
Suggested Solution
1) Set auto off time to a
shorter time and check if
the load switches
2) Keep away from detection
coverage to avoid
activating sensor while
doing the test
3) Refer to wiring diagrams
for correct connection
1) Walk in the effective
detection range
2) Switch on the power
3) Refer to wiring diagrams
for correct connection
Avoid aiming the sensor
towards heat sources, such
as air conditionings, electric
fans, heaters or any highly
reflective surfaces. Make
sure there are no swaying
objects within the detection
coverage.
Rated Voltage
Rated Load
Detection Angle
Detection Range
Auto Time Off
Adjustment
Lux Adjustment
Meter Adjustment
Operating Temperature
Environmental
Protection
220-2
For Li
LED L
Tungs
Incand
360°
Up to
From
Adjust
Adjust
at heig
-20°C
IP20
55-307 instructions_Jul21.qxp_Layout 1 6/8/21 10:55 am Page 10