System
Installation
Guide
69-2091EFS-07
Wireless control for up to 3 Heat/2 Cool heat pump systems or up to 2 Heat/2
Cool conventional systems.
Installation guide for:
• Wireless equipment interface module
• FocusPRO®wireless thermostats
• Wireless remote control
• Wireless outdoor air sensor
• Return air sensor
DISCONNECT POWER BEFORE BEGINNING INSTALLATION.Can cause
electrical shock or equipment damage.
MERCURY NOTICE:If this product is replacing a control that contains mercury in
a sealed tube, do not place the old control in the trash. Contact your local waste
management authority for instructions regarding recycling and proper disposal.
Must be installed by a trained, experienced technician. Read these
instructions carefully. Failure to follow these instructions can damage the product or
cause a hazardous condition.
Français : voir la page 21 •Español: vea la página 41

RedLINK
TM Installation Guide (EIM)
69-2091EFS—07 2
System installation at a glance
The THM5320R equipment interface module (EIM) provides control of all heating
and cooling equipment from any FocusPRO wireless thermostat.
Installation procedure
Mount and wire EIM.................................................................. Pages 3-4
Install batteries in wireless devices ...............................................Page 5
Link all devices to wireless network ........................................ Pages 5-7
Exit wireless setup ..........................................................................Page 8
Customize thermostat (installer setup).................................. Pages 8-12
Mount thermostat and outdoor sensor .......................................Page 13
To replace system components if needed, see page 15
For system-specific wiring guides, see pages 16-17
If you have more than one Equipment Interface Module (EIM): Thermostats
are linked to specific EIMs. Optional accessories must be linked to each EIM
separately.
DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical
shock or equipment damage.
Remote
control
Thermostat
Optional outdoor
air sensor
M28484
HVAC equipment
EIM
1
2
3
4
5
6

Français : voir la page 21 • Español: vea la página 41
3 69-2091EFS—07
M28494
1Mount and wire EIM
Mount EIM on wall near HVAC equipment, or on the equipment itself.
Do not install inside HVAC equipment. Use screws & anchors as appropriate
for mounting surface.
EIM wiring
M28467
WIRELESSSETUP
THM5320R
CONNECT
FLASHING:CONNECTINGTOREMOTEDEVICE
RED:REMOTEDEVICE(S)NOTCOMMUNICATING
GREEN:CONNECTEDTOREMOTEDEVICE(S)
CONNECTED
POWER
HEAT
COOL
FAN
M28468
M28469
Install EIM Install return air sensor (optional)**
The return air sensor maintains safe
indoor temperature (62° F in Heat, 82° F
in Cool) if thermostat power is lost.
Drill 1/4” hole
(6.4mm)
Install sensor on return air duct at least
12” (305mm) upstream from ventilator,
humidifier or dehumidifier (do not mount
downstream)
Strip 1/4” insulation, then insert wires
as shown.
Press tabs only to remove wires from
terminal block if necessary.
Wiring must comply with local
electrical codes.
Continued on next page >>
** For hydronic applications, use
C7189U1005 Remote Indoor Sensor and
mount in the living space.

RedLINK
TM Installation Guide (EIM)
69-2091EFS—07 4
EIM wiring guide
See detailed wiring guides for specific system
types on pages 16-17.
FURNACE
Transformer
24Vac 120Vac
Stage 1 heat
Air Conditioning
Compressor
(Stage 1)
Compressor
(Stage 2)
Return air sensor**
M28470
Stage 2 heat
Fan
Jumper
A/B/C/D UNUSED
(reserved for future use)
EQUIPMENT INTERFACE MODULE
** or C7189U1005 Remote indoor sensor for hydronic
AIR HANDLER
Transformer
24Vac
Changeover
relay
Backup heat
(gas/electric)
Compressor
(Stage 1)
Compressor
(Stage 2)
Fan Relay
M28471
Relay **
Return
Air Sensor
120Vac
Jumper
A/B/C/D UNUSED
(reserved for future use)
** L terminal sends continuous output when thermostat is
set to EmHeat. L terminal is for use with zone panels.
EQUIPMENT INTERFACE MODULE
CONVENTIONAL SYSTEMS
HEAT PUMP SYSTEMS

Français : voir la page 21 • Español: vea la página 41
5 69-2091EFS—07
M28474
2Install batteries in wireless devices
When system wiring is complete, install batteries in all devices. Make sure
batteries are inserted properly (see polarity marks on illustrations below).
3Link all devices to wireless network
M28472
M28473
M28475 M28476
M28495
Thermostat
Remote control (optional) Outdoor air sensor (optional)
Restore AC power, then press and release
the CONNECT button at the EIM. Wait for
green flashing light to begin linking devic-
es to the wireless network (see pages 6-7).
If the light stops flashing before you have
linked all devices, press CONNECT again.
If light does not flash, another EIM/
wireless adapter may be in wireless setup
mode. Exit wireless setup at the other
EIM/wireless adapter.
Continued on next page >>
Install 2 fresh AA
batteries
Install quick reference
card
Programmable models only
Install 3 fresh AA
batteries
Install 2 fresh AA
lithium batteries
Press and release CONNECT
Flashing status light times out after 15
minutes of inactivity. Press CONNECT
again if necessary.

RedLINK
TM Installation Guide (EIM)
69-2091EFS—07 6
M28477
0
0
Wireless Setup
Next
M28478
36
52
Wireless Setup
Next
Back
M28479
Wireless Setup
Connect
Back
M28480
Wireless Setup
Connected
Done
Link thermostat to wireless network
Zone number
Zone name
Press NEXT (always leave zone number set
to zero).
Zone numbers 1-4 are for use with
TrueZONE panels only.
Press NEXT (or see page 11 to change the
zone name if needed).
Change zone name only if you have more
than one thermostat and EIM.
Press CONNECT to establish a link to the wire-
less network.
If E1 appears, see error codes on page 14.
After a brief pause, the confirmation screen
at left should be displayed, to verify that the
wireless connection has been established.
Press DONE to display the home screen.

Français : voir la page 21 • Español: vea la página 41
7 69-2091EFS—07
Link remote control to wireless network (optional)
Link outdoor sensor to wireless network (optional)
CONNECT
WIRELESS SETUP
M28481
M28483
NOYES
CONNECT MORE?
M28482
1Make sure the Connected light on the
EIM is flashing (see page 5).
2 Press CONNECT at the remote. There will
be a short delay as the remote seeks a
signal from the wireless network.
3When the screen displays "Connected,"
press DONE.
4 Press NO at the next screen to save and
exit. (Or press YES and repeat steps 1-4
to link another EIM.)
1Make sure the Connected light on the
EIM is flashing (see page 5).
2 Press and release the CONNECT button
on the back of the sensor.
3Check thermostat to verify that the
outdoor sensor is working. After about
15 seconds, the thermostat should
display outdoor temperature and
humidity.
Press to link
another EIM
Press to save
and exit
If E1 appears, see error codes on page 14.
The linking procedure may time out if there is
no keypress within 30 minutes. To begin again,
press and hold the blank space (or arrow, if
present) in the lower right corner of the screen
until the display changes (about 3 seconds).
Press and release
(If you are installing more than one EIM,
repeat steps 1-3 for each.)

RedLINK
TM Installation Guide (EIM)
69-2091EFS—07 8
4Exit wireless setup
5Customize thermostat (installer setup)
Press CONNECT at the EIM to exit wireless setup (light should stop flashing).
Follow the steps below to begin installer setup. At each function screen, press
sor tto change the setting as desired, then press NEXT to advance to the
next function screen.
See tables on pages 9-11 for a description of options for each function.
Press sor tto change
setting (see tables on pages
9-11).
Press NEXT to display next
function screen.
Note: The EIM will automatically exit wireless setup after 15 minutes of inactivity.
Note: If installing more than one thermostat and EIM, you must exit wireless setup
before installing an additional thermostat and EIM.
FAN
M28485
To begin, press and hold the FAN and sbuttons
until the display changes (about 3 seconds).
Function
Press DONE to save & exit.
Setting
M28486
0
0
Next
Back
Done
M28487
1
0
Next
Back
Done
M28488

Français : voir la page 21 • Español: vea la página 41
9 69-2091EFS—07
Installer setup tables
Setup function Settings & options (factory default in bold)
0Zone number 0 No zoning (single thermostat used with THM5320R EIM)
[Options: select zone 1, 2, 3 or 4]
1System type 0 1 heat/1 cool conventional
1 1 heat/1 cool heat pump (no aux. heat)
2 Heat only (includes Series 20)
3 Heat only with fan
4 Cool only
5 2 heat/1 cool heat pump
6 2 heat/2 cool conventional
7 2 heat/1 cool conventional
8 1 heat/2 cool conventional
9 2 heat/2 cool heat pump
10 3 heat/2 cool heat pump
2Changeover valve
(O/B terminal) 0 O/B terminal controls valve in cooling
1 O/B terminal controls valve in heating
3Fan control
(conventional heat) 0 Gas/Oil heat (equipment controls fan)
1 Electric furnace (thermostat controls fan)
4Backup heat (Aux &
EmHeat) 1 Electric backup heat
0 Fossil fuel backup heat
5Stage 1 heat cycle
rate (CPH: cycles/
hour)
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
6Stage 2 heat cycle
rate (CPH) 5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
7Stage 3 heat cycle
rate (CPH) 5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
8Emergency heat cycle
rate (CPH) 9 Electric furnace
[Cycle rate options: 1 to 12 CPH]
9Stage 1 compressor
cycle rate 3 Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
10 Stage 2 compressor
cycle rate 3 Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
11 Heat pump type 0 Air to Air Heat Pump
1 Geothermal heat pump
12 Manual/Auto
changeover 0 Manual (User options: Heat/Cool/Off)
1 Automatic (User options: Heat/Cool/Auto/Off)
13 Adaptive Intelligent
Recovery™
Applies only to Model TH6320
1 On
0 Off
14 Temperature
display 0 Fahrenheit
1 Celsius

RedLINK
TM Installation Guide (EIM)
69-2091EFS—07 10
15 Compressor off time
(minimum) 5 5 minutes (Heat On/Cool On flashes during off time)
[Options: 0 to 4 minutes]
16 Schedule format Applies only to Model TH6320
0 Weekday/weekend program schedule
1 Weekday/Saturday/Sunday program schedule
17 External fossil fuel kit 1 External fossil fuel kit controls backup heat
0 Thermostat controls backup heat (outdoor sensor required)
18 Dual fuel heat pump
control 1 Droop control**
0 No droop control**
2 Droop control with Aux Heat Lockout**
20 Droop temperature
(dual fuel) 2 Auto temperature droop 2° F (1° C)
[Options: 2 to 5 (2 to 5° F / 1 to 2.5° C)]
21 Dual fuel upstage to
furnace timer 1 1 hour**
[Options: 0 (off) to 16 hours]
22 Outdoor air sensor? 0 No
1 Yes
24 Heat pump
compressor lockout
(balance point)
0 No heat pump compressor lockout**
15° F (-15° C) 735° F (1.5° C)
210° F (-12° C) 840° F (4.5° C)
315° F (-9.5° C) 945° F (7° C)
420° F (-6.5° C) 10 50° F (10° C)
525° F (-4° C) 11 55° F (13° C)
630° F (-1° C) 12 60° F (15.5° C)
25 Heat pump
auxiliary lockout 0 No heat pump auxiliary lockout**
15° F (-15° C) 840° F (4.5° C)
210° F (-12° C) 945° F (7° C)
315° F (-9.5° C) 10 50° F (10° C)
420° F (-6.5° C) 11 55° F (13° C)
525° F (-4° C) 12 60° F (15.5° C)
630° F (-1° C) 13 65° F (18.5° C)
735° F (1.5° C)
26 Auxiliary heat control Applies only to Model TH5320
0 Comfort**
1 Economy
27 Maximum heat
setpoint 90 Max. heat temperature setting is 90° F (32° C)
[Options: 40 °F to 90 °F (4.5 °C to 32 °C)]
28 Minimum cool
setpoint 50 Min. cool temperature setting is 50° F (10° C)
[Options: 50 °F to 99 °F (10 °C to 37 °C)]
32 Temp. display offset
(indoor) 0 Thermostat displays actual temperature
[Options: -3 to +3 °F offset (-1.5 to +1.5 °C)]
33 Temp. display offset
(outdoor) 0 Thermostat displays actual temperature
[Options: -5 to +5 °F offset (-2.5 to +2.5 °C)]
35 Humidity display
offset (outdoor) 3 Thermostat displays actual humidity
[Other options: 0 = -15%, 1 = -10%, 2 = -5%, 4 = +5%, 5 = +10%,
6 = +15% offset]
Setup function Settings & options (factory default in bold)
** See page 11
Installer setup tables
Otros manuales para RedLINK
4
Tabla de contenidos
Idiomas:
Otros manuales de Sistema de micrófono de Honeywell
Manuales populares de Sistema de micrófono de otras marcas

Sennheiser
Sennheiser Evolution Wireless Digital EW-DX EM 2 Manual de usuario

Alpha Technologies
Alpha Technologies RBMS Manual de usuario

SWIT Electronics Co.,LTD.
SWIT Electronics Co.,LTD. CW-S150 Manual de usuario

Shure
Shure UA844 Manual de usuario

Panasonic
Panasonic SHFX70 - DVD HOME THEATER WIRELESS SYSTEM Manual de usuario

Pyle
Pyle PDWM5000 Manual de usuario