Functional Description
• Adjustable constant current output: 700 mA to 1400 mA (default)
• Current setting via with dip-switches
• Amplitude dimming technology for the highest quality light in every application
• Suitable for flicker-free camera recording applications
• Optimal fit for EPBD/BREEAM/LEED/WELL due to flicker-free light, energy efficiency and controllability
• Push to Fade functionality for easy-to-use intensity control with smooth fade in transitions
• Potted casing providing additional cover against vibration
• Overload, open & short circuit protection
Mains Characteristics
Nominal rated voltage range 220 V – 240 V, 50 – 60 Hz
Rated emergency voltage range* 196 V – 254 V, 0 Hz
AC voltage range 198 VAC – 264 VAC
Withstands max. 320 VAC (max. 1 hour)
Withstands min. 176 VAC (max. 1 hour)
DC voltage range* 176 VDC – 280 VDC
Mains current at full load 0.28 – 0.32 A
Frequency 50 Hz –60 Hz
Stand-by power consumption < 0.5 W
THD at full power < 10 %
Tested surge protection 1 kV L-N (IEC 61000-4-5)
2 kV L/N-GND (IEC 61000-4-5)
Tested fast transient protection 2 kV (IEC 61000-4-4)
*For emergency use, see details in page 4
Insulation between circuits & driver case
Mains circuit - SELV circuit Double/reinforced insulation
DALI circuit - SELV circuit Double/reinforced insulation
Mains circuit - DALI circuit Basic insulation
Mains, DALI and output - Driver case Double/reinforced insulation
Load Output (SELV <60 V)
Output current (Iout) 700 mA –1400 mA (default)
Accuracy ± 5 %
Ripple < ±3 %* at ≤ 120 Hz
*) Low frequency
PstLM < 0.06*
SVM < 0.02*
*) At full power, measured with Cree XP-G LED modules.
Uout (max) (abnormal) 60 V
ILED 700 mA 1400 mA
PRated 36.4 W 60.2 W
ULED*9 – 52 V 9 – 43 V
PF (λ) at full load 0.95 0.95
Efficiency (η) at full load 88 % 88 %
*see voltage ranges per selectable current on page 3.
60.2 W SELV Dimmable DALI-2 LED driver
• DALI-2 certified LED driver, 1-100 % dimming range
• SELV output protection for safety and flexibility in luminaires
• Low current ripple, complying with IEEE 1789 recommendation
• Amplitude dimming for the highest quality light output
• Suitable for use in emergency lighting applications
• Current setting via dip-switches
• Ideal solution for Class I and Class II luminaires
• For driving Class III (SELV) luminaires, optional strain relief available
for independent use outside of luminaire (LC-SRC)
60.2 W 220 – 240 V 50 – 60 Hz
Product code: 5934
03.11.2021 1/5T22 199 1A
LC60DS-DA-700-1400
T22 199 1A

Helvar |Helvar Oy Ab, Keilaranta 5 FI-02150 Espoo, Finland. Data is subject to change without notice. www.helvar.com
Operating window
Driver performance
Operating Conditions and Characteristics
Absolute highest allowed tcpoint temperature 90 °C
Tc life (50 000 h) temperature 85 °C
Ambient temperature range –20 °C ... +50 °C*
Storage temperature range –40 °C ... +80 °C
Maximum relative humidity No condensation
Life time (90 % survival rate) 50 000 h, at tc = 85 °C
30 000 h, at tc = 90 °C
*) For other than independent use, higher taof the controlgear possible as long as highest allowed tcpoint temperature is not exceeded
Note: 1) Dimming between 1 - 100 % possible across the operating window,
restricted by the absolute minimum dimming current of 10 mA
2) Current value is adjustable in steps via dip-switch. See dip-switch
settings in page 3 for details.
0
5
10
15
20
25
30
35
40
45
50
55
60
0,60 0,70 0,80 0,90 1,00 1,10 1,20 1,30 1,40 1,50
Output voltage [V]
Output current [A]
U
LED
(max), V
U
LED
(min), V
60,0
64,0
68,0
72,0
76,0
80,0
84,0
88,0
92,0
0 5 10 15 20 25 30 35 40 45 50 55 60 65
Efficiency (%)
Total output power (W)
Typical efficiency
1400 mA
1050 mA
700 mA
0,60
0,65
0,70
0,75
0,80
0,85
0,90
0,95
1,00
0 5 10 15 20 25 30 35 40 45 50 55 60 65
λ
Total output power (W)
Typical power factor
1400 mA
1050 mA
700 mA
03.11.2021 2/5
LC60DS-DA-700-1400
T22 199 1A

Helvar |Helvar Oy Ab, Keilaranta 5 FI-02150 Espoo, Finland. Data is subject to change without notice. www.helvar.com
Amplitude dimming technology
Quantity of drivers per miniature circuit breaker 16 A Type C
CONVERSION TABLE FOR OTHER TYPES OF
MINIATURE CIRCUIT BREAKER I (A)
T (ms)
Ipeak
Δt
½ Ipeak
MCB
type
Relative quantity of
LED drivers
B 10 A 37 %
B 16 A 60 %
B 20 A 75 %
C 10 A 62 %
C 16 A 100 % (see table above)
C 20 A 125 %
LC60DS-DA-700-1400 LED driver implements amplitude dimming technology across whole dimming range. Amplitude dimming offers
the best available technology for dimming the light output in an accurate and flicker-free way to ensure high quality lighting in even
the most demanding situations such as camera recording applications. Amplitude dimming technology complies with IEEE 1789-2015
recommendations of current modulation to mitigate health risks to viewers.
1 % 100 %
1 %
100 %
LED current
Brightness
Amplitude
dimming
Dimming range Dimming technology
1 % –100 % Amplitude (DC)
CONTINOUS CURRENT
Based on inrush current Ipeak Typ. peak inrush current Ipeak 1/2 value time, Δt
39 pcs 30 A 195 µs
Total continous current of the drivers and installation environment must always be considered and taken into calculations when installing drivers behind
miniature circuit breaker. Example calculation of total drivers amount limited by continous current: n(Icont)= (16 A (Inom,Ta) / “nominal mains current with full
load”) x 0.76). This calculation is an example according to recommended precautions due to multiple adjacent circuit breakers (> 9 MCBs) and installa-
tion environment (Ta30 degrees); variables may vary according to the use case. Both inrush current and continous current calculations are based on
ABB S200 series circuit breakers. More specific information in ABB series S200 circuit breaker documentation.
NOTE! Type C MCB’s are strongly recommended to use with LED lighting. Please see more details in “MCB information” document in each driver product
page in “downloads & links” section.
LC60DS-DA-700-1400
03.11.2021 3/5T22 199 1A

Helvar |Helvar Oy Ab, Keilaranta 5 FI-02150 Espoo, Finland. Data is subject to change without notice. www.helvar.com
Connections
Dimensions (mm)
Connections and Mechanical Data
Wire size 0.5 mm2 –1.5 mm2
Wire type Solid core and fine-stranded
Wire insulation According to EN 60598
Maximum driver to LED wire length 1.5 m
Weight 357.3 g
IP rating IP20
Dip-switch combinations, output currents and voltage ranges (Nominal Iout (±5 % tol.))
Note:
• Not suitable for load side switching operation
In LC60DS-DA-700-1400, the current can be set with dip-switches. With each combination of switch setup, a different output current
value can be set. The maximum value can be reached with the all dip-switches set to "1" (pushed towards to the label, see connections
picture above) and minimum with all switches set to "0". The output current values according to the dip-switch settings are presented
below.
N
L
DA
Push to Fade
110
64.5
74
102
30
Dip-Switch combination 1111 0111 1011 0011 1101 0101 1001 0001
Iout (mA) 1400 1350 1300 1250 1200 1150 1100 1050
Voltage range 9 - 43 V 9 - 44 V 9 - 46 V 9 - 48 V 9 - 50 V 9 - 52 V 9 - 52 V 9 - 52 V
Dip-Switch combination 1110 0110 1010 0010 1100 0100 1000 -
Iout (mA) 1000 950 900 850 800 750 700 -
Voltage range 9 - 52 V 9 - 52 V 9 - 52 V 9 - 52 V 9 - 52 V 9 - 52 V 9 - 52 V .
03.11.2021 4/5
LC60DS-DA-700-1400
T22 199 1A

Helvar |Helvar Oy Ab, Keilaranta 5 FI-02150 Espoo, Finland. Data is subject to change without notice. www.helvar.com
LC60DS-DA-700-1400 LED driver is suited for built-in usage in luminaires. With external strain relief (LC-SRC) independent use is possible
too. In order to have safe and reliable LED driver operation, the LED luminaires will need to comply with the relevant standards and
regulations (e.g. IEC/EN 60598-1). The LED luminaire shall be designed to adequately protect the LED driver from dust, moisture and
pollution. The luminaire manufacturer is responsible for the correct choice and installation of the LED drivers according to the application
and product datasheets. Operating conditions of the LED drivers may never exceed the specifications as per the product datasheet.
Installation & operation
Maximum ambient and tctemperature:
• For built-in components inside luminaires, the taambient
temperature range is a guideline given for the optimum
operating environment. However, integrator must always
ensure proper thermal management (i.e. mounting base of the
driver, air flow etc.) so that the tcpoint temperature does not
exceed the tcmaximum limit in any circumstance.
• Reliable operation and lifetime is only guaranteed if the
maximum tcpoint temperature is not exceeded under the
conditions of use.
Current setting via dip-switch
LC60DS-DA-700-1400 LED driver features a constant current output
adjustable via Dip-switch combinations
• For the combination/current values, refer to the table on page 4.
Emergency use
• The product can be continuously operated only with AC, the DC is
reserved only for emergency usage.
Miniature Circuit Breakers (MCB)
• Type-C MCB’s with trip characteristics in according to EN 60898
are recommended.
• Please see more details in “MCB information” document in each
driver product page in “downloads & links” section.
Installation site
• The general preferred installation position of LED drivers for
independent use is to have the top cover facing upwards.
Lamp failure functionality
No load
When open load is detected, driver goes to standby and recovers
through mains reset.
Overload
When overload is detected, driver goes to standby mode and recover
after mains reset.
Short circuit
Driver can withstand output short circuit and after resolving the
fault, driver recovers after mains reset.
Push to Fade
Push to Fade solution includes additional fading behavior, which
provides smooth transition between on and off states. Please note
that Push to Fade is not compatible to be installed in the same circuit
with Helvar Switch-Control or Switch-Control 2 devices.
Always before installation and for troubleshoot and guidance,
refer to the user guide at www.helvar.com.
Use of Push to Fade functionality
• Maximum numbers of LED drivers to be connected to one
switch is 30.
• Ensure that all components connected to Push to Fade circuitry
are mains rated.
• The transition between 0 to 100% (when turned ON / OFF) is ~
1 second.
Conformity & standards
General and safety requirements EN 61347-1: 2015
Particular safety requirements for DC
or AC supplied electronic control gear
for LED modules
EN 61347-2-13: 2014 +
A1: 2017
Additional safety requirements for AC
or DC supplied electronic controlgear
for emergency lighting
EN 61347-2-13: 2014 +
A1:2017, Annex J
Thermal protection class EN 61347, C5e
Mains current harmonics EN 61000-3-2: 2014
Limits for voltage fluctuations and
flicker
EN 61000-3-3: 2013
Radio frequency interference EN 55015: 2013
Immunity standard EN 61547: 2009
Performance requirements EN 62384: 2006+
A1:2009
Digital addressing lighting interface:
General requirements for DALI system
Requirements for DALI control gear
Requirements for control gear of LED
modules (DALI Device Type 6)
EN 62386-101 (DALI-2)
EN 62386-102 (DALI-2)
EN 62386-207 (DALI-2)
Recommended Practices for
Modulating Current in High-Brightness
LEDs for Mitigating Health Risks to
Viewers
IEEE 1789-2015
Compliant with relevant EU directives
RoHS / REACH compliant
ENEC and CE / UKCA marked
Label symbols
Safety isolating control gear with short circuit protection
(SELV control gear).
Double insulated control gear suitable for built-in use.
Thermally controlled control gear, incorporating means
of protection against overheating to prevent the case
temperature under any conditions of use from exceeding
110 °C.
DALI-2 certified control gear.
03.11.2021 5/5
Information and conformity
T22 199 1A
Este manual sirve para los siguientes modelos
1
Tabla de contenidos
Otros manuales de Accionamiento de CC de HELVAR
Manuales populares de Accionamiento de CC de otras marcas

Vincent Associates
Vincent Associates UNIBLITZ ED12DSS Manual de usuario

EKSMA OPTICS
EKSMA OPTICS DQ-100-4 Manual de lista de piezas

Chamberlain Garog
Chamberlain Garog D Series Manual de usuario

Parker
Parker PDS Series Manual de usuario

Festo
Festo DGC G Series Guía de configuración

Binks
Binks QS-5012-1-CE Manual de usuario

ABB
ABB RSYC-01 Manual de usuario

Rockwell Automation
Rockwell Automation PowerFlex 700S Manual del propietario

WEG
WEG DeviceNet CFW500 Manual de usuario

Siemens
Siemens SINAMICS G Hoja de datos

Siemens
Siemens SINAMICS SM150 6SL3815-7NP41-0AA1 Instrucciones de funcionamiento

SOMFY
SOMFY JR RU 30 Manual de usuario