Heiko CA100-A1 Manual de usuario

SYJS-2020.A Edition: 2020-03
R32 Super Match
Service Manual

CONTENTS
1 . General Information ..............................................................................................................1
1.1 Line up....................................................................................................................................1
1.2 Feature...................................................................................................................................2
2 . Indoor Units-4-Way Cassette Type.......................................................................................4
2.1 Feature...................................................................................................................................4
2.2 Specication ...........................................................................................................................6
2.3 Dimension.............................................................................................................................10
2.4 Wiring Diagram.....................................................................................................................13
2.5 Air Velocity and Temperature Distribution.............................................................................17
2.6 Sound Pressure level ...........................................................................................................21
2.7 Installation ............................................................................................................................24
3 . Outdoor Units ......................................................................................................................44
3.1 Feature.................................................................................................................................44
3.2 Dimension.............................................................................................................................50
3.3 Wiring Diagram.....................................................................................................................54
3.4 Wiring Connection ................................................................................................................58
3.5 Piping Diagram.....................................................................................................................61
3.6 Limitation Values on Pipe lnstallation ...................................................................................65
3.7 Combination and the Data....................................................................................................67
3.8 Performance data.................................................................................................................79
3.9 Sound Pressure level ...........................................................................................................85
3.10 Installation Instruction.........................................................................................................87
4 . Electric Control and Troubleshooting.............................................................................143
4.1 Indoor unit Dip Switch Setting ...........................................................................................144
4.2 Wired Controller Group Control.......................................................................................... 147
4.3 Indoor unit Function............................................................................................................ 148
4.4 Outdoor unit PCB Photo, Dip Switch Setting and Function................................................ 153
4.5 Dip Switch Setting .............................................................................................................. 156
4.6 Outdoor Unit Control........................................................................................................... 161
4.7 Diagnostic Code ................................................................................................................. 171
4.8 Trouble Shooting ................................................................................................................ 182

Indoor Unit
1
Model Apperance
Outdoor Unit
JZ070-A1
JZ100-A1
M3T070-D1
M5T100-D1
1 . General Information
1.1 Line up
Model Appearance
Indoor Unit 4-Way Cassette
CA035-A1
CA050-A1
CA070-A1
CA100-A1

2
1.2 Feature
Clean Design
High Comfort
High Efciency
The outdoor unit takes no screw clean design in the top cover, this design makes people comfort when they are
watching the outdoor unit;
New outdoor unit and indoor unit design to get a ultra high SEER/SCOP A++/A+ which is reaching the world
class energy efficiency (M3T070-D1)
The new outdoor unit takes 550mm diameter large fan design, multi split II outdoor unit can provide same air ow
but with lower fan rotation speed, then the sound level reduce 3-4 dB(A) comapred with rst generation multi split
outdoor unit;
550mm

Indoor Unit
3
Installation Friendly
External General Stop Valve
Easy Start Up & Maintenance
The outdoor unit takes external general stop valve in all outdoor unit design, installer can vaccum/charge just one
time with no extra dismantlement, save lots of time;
In start up & maintenance, PC monitor can connect with outdoor unit by TD-02, read all indoor unit & outdoor
unit running parameter, also with the function to show parameter & curve.
When malfunction happens, show failure code.
General
stop valve

4
2 . Indoor Units-4-Way Cassette Type
Appearance
Energy Efciency
DC Fan Motor
The new panel is very t for the standard decoration panel, won't cover other things like light, looks more beautiful;
Compared to conventional AC fan motor, DC fan motor is more efciency.
AC Motor Effciency DC Motor Effciency
The new panel
20
02004 00 6008 00 1000
40
60
80
100
45%
35%
25%
20
02004 00 6008 00 1000
40
60
80
100
90%
87.5%
85%
Torque(kgfcm)
Rev(r/min) Rev(r/min)
Torque(kgfcm)
2.1 Feature

Indoor Unit
5
Four aps can be controlled individually, airow can be controlled according to end user needs. Increase comfort;
Individual Flap Control
Comfort
Installation Friendly
Easy Access Electrical Box Design
The electrical box is located in the unit, you can just make maintenance by openning the panel .
Horizontal
Adjustable Downward
corner installation solution
Fixed

6
2.2 Specication
Item Model CA035-A1
Function —— Cooling Heating
Capacity W 3500 4000
Sensible heat ratio W 0.71 /
Dehumidifying capacity 10-³xm³/h
Indoor unit
Power supply
Fan
Type × Number ——
Speed(H-M-L) r/min
Fan motor output/input power W
Air-ows (H-M-L) m³/h
Heat
exchanger
Type / Diameter mm
1.5
1PH, 220~240V~, 50/60Hz
Centrifugal*1
690/620/560/500
10/15
620/520/450
Inner grooved pipe/φ7.0
Row —— 2
Total area m² 0.544
Temp.scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 570*570*260
Package mmxmmxmm 718*680*380
Drainage pipe (Material,I.D/O.D) mm PVC 26/32
Control type(Remote/Wired) Remote YR-HRC01(O)
Wired YR-C01(O)
Fresh air hole dimension mm 95
Electricity Heater kW None
Noise level
(H-M-L)
Sound power level dB(A) 52
Sound pressure level dB(A) 36/33/30
Weight(Net/Shipping) kg/kg 18.5/22
Panel
Panel model(Color) PB-700HE4
Dimension External(L*W*H) mmxmmxmm 700/700/60
Package(L*W*H) mmxmmxmm 740/750/115
Weight(Net/Shipping) kg/kg 2.8/4.8
Piping
Refrigerant Type R32
Pipe Liquid mm Φ6.35(1/4)
Gas mm Φ9.52(3/8)
Connecting method Flared
Norminal condition: indoor temperature (cooling): 27°CDB/19°CWB, indoor temperature (heating): 20°CDB
Outdoor temperature(cooling): 35°CDB/24°CWB, outdoor temperature(heating): 7°CDB/6°CWB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter.

Indoor Unit
7
Item Model CA050-A1
Function —— Cooling Heating
Capacity W 5000 5500
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 2.2
Indoor Unit
Power Supply 1PH, 220~240V~, 50/60Hz
Fan
Type × Number —— Axial Fiow*1
Speed (H-M-L) r/min 800/700/600
Fan Motor Output/Input
Power W33/50
Air-Flows (H-M-L) m³/h 700/620/500
External Static Pressure pa 0
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/φ7.0
Row —— 2
Total Area m² 1.25
Dimension
(LxWxH)
External mmxmmxmm 570x570x260
Package mmxmmxmm 718x680x380
Drainage Pipe (Material, I.D/O.D) mm PVC 27/31
Control Type (Remote/Wired) Remote YR-HRC01(O)
Wired: YR-C01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level
(H-M-L)
Sound Power Level dB (A) 55
Sound Pressure Level dB (A) 42/37/35
Panel
(Optional)
Weight (Net/Shipping) kg/kg 19/22
Panel Model (Color) PB-700HE4
Dimension External (L*W*H) mmxmmxmm 700/700/60
Package (L*W*H) mmxmmxmm 740/750/115
Weight (Net/Shipping) kg/kg 2.8/4.8
Piping
Refrigerant Type R32
Pipe Liquid mm Φ6.35 (1/4)
Gas mm Φ12.7 (1/2)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27℃DB/19℃WB, indoor temperature (Heating): 20℃DB
Outdoor temperature (Cooling): 35℃DB/24℃WB, outdoor temperature (Heating): 7℃DB/6℃WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter.

8
Item Model CA070-A1
Function —— Cooling Heating
Capacity W 7100 8000
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220~240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*2
Speed (H-M-L) r/min 650/600/550/500
Fan Motor Output/Input
Power W45/50
Air-Flows (H-M-L) m³/h 1260/1070/820/680
External Static Pressure pa 0
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/φ7.0
Row —— 2
Total Area m² /
Temp.Scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 840*840*204
Package mmxmmxmm 990*990*310
Drainage Pipe (Material, I.D/O.D) mm PVC 26/32
Control Type (Remote/Wired) Remote YR-HRC01(O)
Wired: YR-C01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise Level
(H-M-L)
Sound Power Level dB (A) 55
Sound Pressure Level dB (A) 42/40/38/35
Weight (Net/Shipping) kg/kg 27/32
Panel
(Optional)
Panel Model (Color) PB-950HE4
Dimension External (L*W*H) mmxmmxmm 950/950/50
Package (L*W*H) mmxmmxmm 1000/1000/110
Weight (Net/Shipping) kg/kg 6.5/9
Piping
Refrigerant Type R32
Pipe Liquid mm Φ9.52 (3/8)
Gas mm Φ15.88 (5/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27℃DB/19℃WB, indoor temperature (Heating): 20℃DB
Outdoor temperature (Cooling): 35℃DB/24℃WB, outdoor temperature (Heating): 7℃DB/6℃WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter.
Otros manuales para CA100-A1
1
Este manual sirve para los siguientes modelos
1
Tabla de contenidos
Otros manuales de Bomba de calor de Heiko
Manuales populares de Bomba de calor de otras marcas

Mitsubishi Electric
Mitsubishi Electric PUZ-SWM60VAA Manual de usuario

Dimplex
Dimplex LI 16I-TUR Guía del usuario

Carrier
Carrier WSHP Open v3 Guía de configuración rápida

TGM
TGM CTV14CN018A Manual de usuario

Carrier
Carrier 38MGQ Series Manual de usuario

Kokido
Kokido K2O K880BX/EU Guía de solución de problemas

Viessmann
Viessmann VITOCAL 300-G PRO Type BW 2150 Guía rápida

Carrier
Carrier 48EZN Manual de usuario

Viessmann
Viessmann KWT Vitocal 350-G Pro Series Instrucciones de funcionamiento

Ariston
Ariston NIMBUS Manual de usuario

Weishaupt
Weishaupt WWP L 7 Guía del usuario

GE
GE Zoneline AZ85H09EAC Manual de usuario