Halton EcoloAir 3000CFM Manual de usuario

Operators Manual
for Ecology
Manual provides
Operation, Maintenance and Service Instructions
Form#: OM020_ECOLOGY
Date: May 2017 - Rev 5
EcoloAir Unit
3000CFM, 4000CFM, 5000CFM, 6000CFM, 8000CFM,
10000CFM, 12000CFM, 15000CFM, 18000CFM,
20000CFM, 24000CFM, 28000CFM, 32000CFM,
36000CFM, 40000CFM
UL 1978 “Standard for Grease Ducts”, UL 710, “Exhaust Hoods for
Commercial Cooking Equipment”, ULC-S647-05 and/or UL197

2
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
GENERAL
The EcoloAir System should be installed, operated and maintained as illustrated in the Installation
Instruction Manual, and the Operation and Maintenance Instruction.
1
2

3
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
MAJOR COMPONENTS FOR ECOLOAIR
1. EcoloAir Control Panel 3. Exhaust Fan Module
2. Filter Module with Odor Reducing Module 4. Odor Control Cabinet
3
4

4
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
FILTER AND ODOR REDUCING MODULES
The filter and odor reducing modules are made up of the following:
1. A 2” (51mm) MERV 8 (Minimum Efficiency Reporting Value) 30/30 UL Class 1 disposable
pleated Pre-Filter
2. A 15” (381 mm) MERV 14 (Minimum Efficiency Reporting Value) Hi-Flo 95 Class 1 dispos-
able Bag Filter.
3. A 12” (305 mm) MERV 16 (Minimum Efficiency Reporting Value) Micretain UL Class 1 Final
Filter
4. Odor Reducing Module
5. Fire Damper
1Hinged Access Door (Pre Filter & Bag Filter)
2 Pre Filter
3 Bag Filter
4 Hinged Access Door (Final Filter)
5 Final Filter
6 Ecolo Odor Reducing Module
7 Screwed On Access Panel
8 Door Latch
9 Ecolo Support Bracket
10 Fire Damper
FILTER AND ODOR REDUCING MODULE PARTS
FILTER AND ODOR REDUCING
MODULE PARTS VIEW
Not to scale for reference only.
11 Insulation
12 Hanger or Lifting Bracket
13 16 Gauge Welded Fire Proof Panels
14 Hanging/Anchor Point
15 Stiffener Channels
16 Removable Pressure Tube Cover
17 Pressure Tube Ports
18 Final Filter Track
19 Bag Filter Track
20 Pre Filter Track

5
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
1Pressure Transducer Air Tube
2Pressure Transducer Air Tube Connecting Nut
3 Elbow
4 16 Gauge Top Panel
5 Elbow Lock Nut
6 Mullion
7 16 Gauge Bottom Panel
8 Structural Base
9 Fire Proof Door Gasket
10 Filter By-Pass Gasket
PRESSURE TRANSDUCER AIR TUBE PARTS

6
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
ECOLOAIR CONTROL PANEL
Features:
• Service connection to 120/1/60 Hz.
• Microprocessor based.
• User friendly touch screen for easy monitoring of parameters in the system.
• One control panel per system controls exhaust and MUA fan.
• Remote system status monitoring (Internet remote connection as an option).
• Setting of the hood airflows (calibration) through touch panel.
• Monitors each filter condition and maintains constant airflow in the system regardless of the
filter condition.
• Setting of odor control unit operation through the touch panel.
• Monitors system and displays text messages for all alarms in the system.
• Size 15” x 24” x 7”.
Main components of the control panel are:
1. Enclosure Panel
2. Control Transformer
3. (Not Used)
4. Power Supply 24 VDC
5. Fuse Holder (Midget Type)
6. Terminal Block ---- Ground
7. PLC Controller
8. HMI (Human Machine Interface) - Touch Screen
9. Control Relay
10. Wire Duct
11. Terminal Block ---- Distribution
12. Fuse Holder (Glass Type)
13. HMI Connection Cable
14. Glass Fuse
15. Fuse (Time Delay)

7
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
How EcoloAir system operates
The MC8 controller is used to read the analog signals from pressure transducers and to control
speed of exhaust fan motor in order to maintain the constant airflow. It also drives the operation of
ecolo compressor according to preset duty cycle or continuous run.
A small 7‘‘ touch screen is used to monitor the whole system. Screen will provide:
• Information on filters condition (remaining life of the filter (%)
• VFD actual speed (%)
• Features to operate ecolo compressor and to change the time settings on it
• Displays all alarms of the system
• HMI also provides calibration features for startup purpose
How to move around the screens in HMI
There are total of 6 screens used for this application. They are shown below in consecutive order.
Main screen Ecolo screen
Calibration screen Alarm screen

8
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
Moving between screens function is available through the labeled screen buttons at the top of each
screen. Press the ‘‘Fast Select’’ button at the lower left corner of the screen to display a pop up menu
of screen options. Press the ‘‘Fast Select’’ button again to remove the pop up menu.
The operator can go directly to the alarms screen in order to verify what alarm has occurred.
User Guide screen Security screen

9
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
The screen displays the value of the VFD speed of the exhaust fan, particular filters life remaining
(status) and alarms warning symbol. An off/on button to start/stop the operation of the system is also
displayed.
The first bar graph relates to the VFD speed.
The second bar graph relates to the DP (static pressure in inches of water column) for the pre filter.
The third bar graph relates to the DP for the bag filter.
The fourth bar graph corresponds to the DP for the final filter.
(The filter bar graph display shows percentage of life remaining in each filter. See the
Start Up Operating Instructions section for the specific static pressure range for each filter.)
Regular operation – Screen shows the current value of VFD speed.
All filters are at 100 % life remaining when new filters are installed, filters are all 100% clean, VFD
calibrated speed at certain percentage % (this relates to certain static pressure [“ WC] at main DP)
when filters are clean and last there are no alarms in the system.
To Determine Filter Life Remaining:
• Turn OFF Ecology Unit, wait 5 minutes. Turn ON Ecology Unit, wait 10 minutes, then
check the Filter Life.
• Ecology Unit checks Filter Life every time the unit is started. The system waits 10
minutes after start up for the exhaust fan speed to stabilize for an accurate reading,
then it checks and displays remaining Filter Life.
Touch screen operation
The size of the touch screen by default is 7‘‘.
Screens explanation:
1. Main screen - Filter screen

10
EcoloAir Operation, Maintenance & Service Manual
OM-020/052017/rev5/EN
2. Ecolo screen --- ecolo odor control screen
Ecolo odor control unit operation is enabled through the ecolo screen.
The three position selector switch (Off/ Cycle & Continuous) enables the operation of the
compressor.
Off - unit is not operational.
Cycle - unit runs in cycles (on and off).
Continuous - unit runs on all the time, until other command selected.
Numeric display ‘‘Ecolo ON time’’ sets the time in seconds for unit to be on.
Numeric display ‘‘Ecolo OFF time’’ sets the time in seconds for unit to be off.
Once these times are set, if selector switch is in cycle mode, unit will run for a preset time, when
this time has been elapsed, the operation of the compressor automatically stops and it will be off
for the preset time set in off mode. The status changes again to ‘‘on’’ state and goes in cycles as
previously described.