Haes ESENTO MARINE Guía

Installation, Commissioning &
Operating Manual
MARINE APPROVED 2 - 4 ZONE CONVENTIONAL
CONTROL PANEL
Approved Document UI-ESEN4MAR-01 Issue 6.0
MED Ref: 0832/15

IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualied and authorised
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
this equipment.
This re alarm system requires periodic checks as specied in BS 5839 Part 1 It is the responsibility of the
system user to ensure it is regularly serviced and maintained in good working order.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this re alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
product specications at our discretion and without prior notice. E & O E.
IMPORTANT SAFETY NOTES
Haes Technologies Ltd, Unit 3, Horton Industrial Park, West Drayton, UB7 8JD
Model Number MED Ref No.
Esento Marine 2-4 zone conventional panel ESEN-2MAR/4MAR 0832-MED-1086
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for re detection and re alarm systems for buildings.
Provided Options (with requirements):
Output to re alarm devices, dependency type ‘A’, test condition
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for re detection and re alarm systems for buildings.
European Standard BS IEC60092-504 : 2001
Electrical installations in ships, special features, control and instrumentation.
European Standard BS IEC60533 : 1999
Electrical and electronic installations in ships, electromagnetic compatibility.
ATTENTION

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
1
CONTENTS
Page
ABOUT THIS PANEL 2
PRODUCT OVERVIEW 2
CABINET DETAILS 3
CIRCUIT BOARDS 4
MAIN PCB TERMINALS 5
TECHNICAL SPECIFICATION 6
POWER SUPPLY MODULE 7
DESIGN CONSIDERATIONS 8
GENERAL DETECTION CIRCUIT WIRIING SCHEMATIC 8
GENERAL SOUNDER CIRCUIT WIRIING SCHEMATIC 9
INSTALLATION 10
SAFETY 10
ESD PRECAUTIONS 11
GENERAL 11
MOUNTING THE CABINET 11
MAINS CONNECTIONS 12
CONNECTING THE BATTERIES 13
EARTH FAULT MONITORING 13
SETUP & PROGRAMMING 14
LEVEL 3 ENGINEERING OPTIONS 14
ZONE INTERFACE FUNCTION 21
OPERATING 22
PANEL CONTROLS & INDICATIONS 24
DISABLE MODE 24
TEST MODE 25
FAULT DIAGNOSIS 26
FUNCTIONALITY DURING A SYSTEM FAULT 27
USER INSTRUCTIONS 27
SERVICE & MAINTENANCE 28
THE NEED FOR MAINTENANCE 28
DUTIES OF THE RESPONSIBLE PERSON 28
ROUTINE MAINTENANCE & TESTING 28
SCHEDULE OF TESTING LOG BOOK 30
FALSE ALARMS, FAULTS & ENGINEER VISIT LOG BOOK 36

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
The Esento Marine 2 or 4 zone is a conventional control panel with integral power supply & space for
standby batteries.
Esento Marine panels are fully approved to European standards EN54-2 & 4, Fire Detection and Alarm
Systems – Control & Indicating Equipment.
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable
front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm
‘knockouts’ located at the top and rear of the cabinet.
An eight button keypad is used to control the system and allow access to the function options. The three
main buttons, ‘RESOUND’ (red), ‘SILENCE’ (blue) and ‘RESET’ (green) being much larger and colour
coded to assist the end users.
Two or four re zone circuits are provided plus two monitored sounder circuits. Fire & Fault VFCO relays,
Fire & Fault switched negative outputs, class change and an alert input are also included.
The panels are supplied with a 1.5 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Quiesecent and alarm current details for standby battery calculations
Model Standby Current Alarm Current
ESEN-2MAR 75mA 116mA
ESEN-4MAR 85mA 133mA

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
3
ABOUT THIS PANEL
CABINET
Fire Detection System
57mm 80mm
260mm
308mm
250mm
300mm

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
4
ABOUT THIS PANEL
CIRCUIT BOARDS
Esento Marine 2-4 zone panels comprise of two circuit boards
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3
ON
1 2 3 4 ENTER
RESOUND SILENCE RESET
TPCA01-E2MAR/E4MAR - 2 or 4 zone Master PCB
TPCA02 - LED Display & Controls PCB

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
5
ABOUT THIS PANEL
MAIN PCB TERMINALS
PSU
@ + +
- - + -
+ -
+ - + - + - + - + -
28V 0V
C NC NO C NC NO
FIRE FAULT FR FLT CC PUL
-OP -OP -IP -IP
SNDR1 SNDR2 ZONE1 ZONE2 ZONE3 ZONE4
BATTERY
1 2 3
ON
28v output fused @ 500mA
28v input for power supply
Temperature compensation voltage control link
Commmon re VFCO relay
unfused. Max 3A @ 30vdc
Commmon fault VFCO relay
maintained (fail safe) unfused.
Max 3A @ 30vdc
Common re O/P
Common fault O/P
Alert (pulses sounders)
Precint/class change (activates sounders)
Switched -ve inputs
Switched -ve outputs
Max load 40mA
To 0 volts
Relay Coil
Conventional monitored
sounder circuits, fused @ 500mA
Conventional re zone circuits, fused @ 500mA

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
6
ABOUT THIS PANEL
General Specication
Enclosure Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Temperature range -5 deg C to +55 deg C max RH 95%
Vibration IEC 60068-2-6 Test F
Inclination IEC 60092-501 22.5o
Number of conventional detection circuits 2 or 4
Detector compatibility Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
TECHNICAL SPECIFICATION
Electrical Specication Inputs & Outputs - TPCA01-H2/H4
Cabling Fire resistant screened cable, minimum
size 1mm2. Max cable length 1Km (20
Ohm). FireBurn, FP200 or equivalent
(max capacitance 1uF, max inductance 1
millihenry).
Suitable cable glands must be used.
Terminal capacity 0.5mm2 to 2.5mm2solid or stranded wire.
PSU @ output Power supply voltage control line. For temperature compensation control.
PSU Input + - 28vdc supply input. Diode protected for
reversal and independent short circuit.
Max current 3 amps.
Max input current 3 amps. Input voltage
22vdc to 32vdc.
28v+, 0v- power output 28vdc supply output for re alarm
accessory relays etc. Max continuous
use = 400mA.
Fused @ 500mA. Fuse = 500mA
resettable fuse.
Common re relay Fire relay contact. Clean C/O.
Max 3A @ 30vdc
Unfused
Common fault relay Maintained fault relay contact. Clean
C/O. Max 3A @ 30vdc
Unfused
Outputs; FR, FLT Switched -ve voltage outputs for relay
control.
Overload voltage protected to 52vdc.
Current limited 680R. Max load = 40mA
Inputs; CC, PUL Switched -ve inputs, connect to 0v to
trigger. Max input voltage = 28vdc. Non
latching, max resistance 100R.
Protected via 10K Ohm impedance, 3v6
zener diode.
SNDR 1 - 2 28vdc polarity reversal monitored
sounder outputs to re alarm devices.
4K7 Ohm 5% 0.25W EOL resistor.
Monitoring current limit 28mA, fused @
500mA. Typical max load 22 devices @
18mA each per circuit. Ensure 0.9A is not
exceeded.
Zone 1 - 4 Fire alarm zone circuits. Conventionally
wired detection circuit. 4K7 Ohm 5%
0.25W EOL resistor.
Maximum detector load 3.5mA per zone,
Typical qty 40-50 Apollo marine optical
detectors, Note:- Max 32 detectors with
line continuity diode bases tted

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESENMAR-01 Issue 6.0
7
ABOUT THIS PANEL
POWER SUPPLY MODULE
Power Supply Specication
Mains supply 230vac +10% / -15% 50Hz max current
1A
Mains supply fuse 2 Amp (T2A 250V) Not accessible for servicing. Internal to
switch mode power unit
Internal power supply rating 1.5 Amps total including battery charging Maximum load shared between outputs
= 0.9A
Power supply output voltage 19.92 - 30.09vdc Tolerance +/- 0.1%
Max continuous load (ImaxA). Max
continuous load whilst battery charging
is not required (ImaxB).
ImaxA = 575mA ImaxB = ImaxA
Minimum current drawn by panel
(example)
4 Zone
I min = 85mA
2 Zone
I min = 75mA
Maximum ripple 1.0 V p-p Supply and charger fault monitored
Min/max battery size and type 2 x 3.2Ahr 12volt VRLA
Use Yuasa NP range batteries
Other equivalent batteries may be
used but have not been tested for the
purposes of EN54 approval.
Battery charging voltage 27.3 vdc nominal at 20 deg C Temperature compensated
Battery charging output current 1.5A PSU 630mA
Current limited 10 Ohms
Battery high impedance fault (Batt Hi Z) Resistance = 1 Ohm or greater 1 hour reporting time
Max current drawn from batteries 1.5 Amps with main power source
disconnected. Battery fuse 3A LBC
20mm.
V+
V-
E
N
L
24v +ve output
O/P Voltage adjust
(default setting 27v4 at 20oC)
24v -ve output
Earth
Neutral
Live
Mains input
Temperature compensation input
from @ terminal on main PCB

Esento Marine 2-4 Installation, Commissioning & Operating Manual Approved Document UI-ESEN4MAR-01 Issue 6.0
8
DESIGN CONSIDERATIONS
TYPICAL DETECTION CIRCUIT SCHEMATIC
Este manual sirve para los siguientes modelos
2
Tabla de contenidos
Otros manuales de Panel de control de Haes

Haes
Haes Excel-32 Series Guía

Haes
Haes ESENTO ESEN-8MAR Guía

Haes
Haes ESG-2001 Guía

Haes
Haes ELAN HS-5200 Instrucciones de montaje

Haes
Haes AlarmSense PLUS Manual de usuario

Haes
Haes FUSION 0832-CPD-1431 Manual de usuario

Haes
Haes MZAOV-1001 Guía

Haes
Haes FCPTEC-HS-4200 Guía

Haes
Haes AOV Series Guía

Haes
Haes ELAN HS-5000 Series Manual de usuario