GEM 1441 cPos-X Manual de usuario

further information
webcode: GW-1441
GEMÜ 1441 cPos-X
Intelligent electro-pneumatic positioner
Features
•2-wire-connection technology
•Quick commissioning using well-balanced preconfiguration
•HART communication available upon request
•"Fail safe" and "Fail freeze" safety function available
•BLE communication for remote access and configuration
•Almost no air consumption when idle
Description
The GEMÜ 1441 cPos-X is an intelligent, digital electro-pneumatic positioner in 2-wire technology used to control pneumatically
operated process valves. It can be combined with single acting or double acting linear actuators or quarter turn actuators. This
means that it can be used, among other things, for diaphragm, globe and diaphragm globe valves as well as for ball valves and
butterfly valves, for instance. The positioner has a robust housing with a covered LCD display for status information. The posi-
tioner can be operated remotely using a mobile device in order to configure settings and to view detailed information.
Technical specifications
•Ambient temperature: -10 to 60 °C
•Operating pressure : 1.5 to 7 bar
•Mode of action: Double acting l Single acting
•Flow rate: 115 Nl/min
•Linear measuring range: 2 to 75 mm
•Radial measuring range: 0 - 90°
•Supply voltage: Via set value signal
•Electrical connection types: M16 cable gland l M12 plug
•Communication modes: BLE l HART
•Conformity: FCC
Technical data depends on the respective configuration

www.gemu-group.com2 / 19GEMÜ 1441
Product line
GEMÜ 1434
µPos
GEMÜ 1436 eco
cPos
GEMÜ 1435
ePos
GEMÜ 1436
cPos
GEMÜ 1441
cPos-X
Controller type Positioner Positioner Positioner Positioner and pro-
cess controller
Positioner
Supply voltage 24 V DC 24 V DC 24 V DC 24 V DC Via set value signal
Flow rate 15 Nl/min 150 l/min
200 l/min
50 Nl/min
90 Nl/min
150 l/min
200 l/min
300 l/min
115 Nl/min
Ambient temperature 0 to 60 °C 0 to 60 °C -20 to 60 °C 0 to 60 °C -10 to 60 °C
Housing material Housing cover:
PP / housing base:
Aluminium or stain-
less steel
Housing cover:
PSU / housing base
PP30
Aluminium Housing cover:
PSU / housing base
PP30
Housing parts: PA/
inspection glass:
PC
Control function of valve actuator
Double acting - - lll
Single acting lllll
Measuring range Max. 30 mm, linear Max. 30 mm, linear
Max. 50 mm, linear
Max. 75 mm, linear
Max. 90°, radial
Max. 30 mm, linear
Max. 50 mm, linear
Max. 75 mm, linear
Max. 90°, radial
Max. 30 mm, linear
Max. 50 mm, linear
Max. 75 mm, linear
Max. 90°, radial
Max. 75 mm, linear
Max. 90°, radial
Operating options none none Buttons on the
product
Buttons on the
product
app via bluetooth
Displays on the product LEDs LEDs LC display, backlit LC display, backlit LC display
Functions of the displays Status display Status display Configuration
Status display
Configuration
Status display
Status display
Set value signal 1)
0 - 10 V l-l- -
0 - 20 mA l-l l -
4 - 20 mA lllll
Analogue feedback signal
0 - 10 V l-l- -
0 - 20 mA l- - l-
4 - 20 mA lllll
Communication modes
BLE - - - - l
HART - - - - l
Digital inputs ---l l
Digital outputs - - lll
1) Versions depending on the product, see order data
Product line

GEMÜ 1441
www.gemu-group.com 3 / 19
Product description
Construction
2
3
4
C
1
Item Name Materials
1Housing cover Grivory PA 6.6
2Inspection glass PC
3Housing base Grivory PA 6.6
4Pneumatic panel Grivory PA 6.6
CConexo
Product description

www.gemu-group.com4 / 19GEMÜ 1441
GEMÜ CONEXO
The interaction of valve components that are equipped with RFID chips and an associated IT infrastructure actively increase
process reliability.
Thanks to serialization, every valve and every relevant valve component such as the body, actuator or diaphragm, and even auto-
mation components, can be clearly traced and read using the CONEXO pen RFID reader. The CONEXO app, which can be in-
stalled on mobile devices, not only facilitates and improves the "installation qualification" process, but also makes the mainten-
ance process much more transparent and easier to document. The app actively guides the maintenance technician through the
maintenance schedule and directly provides him with all the information assigned to the valve, such as test reports, testing doc-
umentation and maintenance histories. The CONEXO portal acts as a central element, helping to collect, manage and process
all data.
For further information on GEMÜ CONEXO please visit:
www.gemu-group.com/conexo
Ordering
GEMÜ Conexo must be ordered separately with the ordering option "CONEXO".
GEMÜ CONEXO

Order data
The order data provide an overview of standard configurations.
Please check the availability before ordering. Other configurations available on request.
Note: Pneumatic connecting components (union and compressed air tube) for the connection between the process valve and
positioner are included with each positioner.
Note: A valve specific mounting kit is required for assembly. For designing the mounting kit, the valve type, nominal size, control
function and actuator size must be stated.
Order codes
1 Type Code
2-wire 1441 cPos-X 1441
2 Fieldbus Code
Without 000
HART HAR
3 Accessory Code
Automation product A
4 Action Code
Single acting (fail safe) 1
Double acting (fail safe) 3
Single acting blocking (fail freeze) 5
Double acting blocking (fail freeze) 6
5 Device version Code
Positioner SA2
6 Signal type Code
4...20mA A
7 Pneumatic connection Code
G1/8 with 6mm plug-in coupling 3
G1/8 with 1/4" plug-in coupling U
8 Option Code
Analogue output, digital input and output C
9 Electrical connection Code
M12 plug 1
M16 x 1.5 cable gland 2
10 Flow rate Code
115 Nl/min 2
11 Travel sensor version Code
Potentiometer, 75 mm length 075
Remote potentiometer,
M12 connector
S01
12 Type of design Code
Without
Media wetted area cleaned to ensure suitability for paint
applications, parts sealed in plastic bag
0101
Inversed direction,
for quarter turn valves control function NO (2)
6960
13 CONEXO Code
Integrated RFID chip for electronic identification and
traceability
C
Order example
Ordering option Code Description
1 Type 1441 2-wire 1441 cPos-X
2 Fieldbus HAR HART
3 Accessory A Automation product
4 Action 1 Single acting (fail safe)
5 Device version SA2 Positioner
6 Signal type A 4...20mA
7 Pneumatic connection 3 G1/8 with 6mm plug-in coupling
8 Option C Analogue output, digital input and output
9 Electrical connection 1 M12 plug
10 Flow rate 2 115 Nl/min
11 Travel sensor version 075 Potentiometer, 75 mm length
12 Type of design Without
13 CONEXO C Integrated RFID chip for electronic identification and traceability
Order data
GEMÜ 1441
www.gemu-group.com 5 / 19

www.gemu-group.com6 / 19GEMÜ 1441
Technical data
Medium
Working medium: Compressed air and inert gases
Dust content: Class 4, max. particle size 15 μm, max. particle density 5 mg/m³
Pressure dew point: Class 4 (10 K below the ambient temperature)
Oil content: Class 4, max. oil concentration 25 mg/m³
Quality classes to DIN ISO 8573-1
Temperature
Ambient temperature: -10 — 60 °C
Storage temperature: -10 — 60 °C
Pressure
Operating pressure: 1.5 — 7 bar
The applied pressure must not exceed the maximum control pressure of the process valve.
Flow rate: 115 Nl/min (@ 25°C; 6->5 bar)
Air consumption: ≤ 0.05 Nl/min (when idle)
Product compliance
EMC Directive: 2014/30/EU
Technical standards used:
Interference emission: DIN EN 61000-6-3:2007/A1:2011/AC:2012
DIN EN 61326-1 (industry) (07/2013)
Interference resistance: EN IEC 61000-6-1:2019
EN 61326-1:2013 (industry)
Class: B
Group: 1
Radio Equipment Direct-
ive (RED):
2014/53/EU
Technical standards used:
Standard regarding the use
of radio frequencies:
EN 300 328 V2.2.2 (2019-07)
Electromagnetic compatibil-
ity (EMC) for radio devices
and services:
EN 301 489-1 V2.2.3 (2019-11)
EN 301 489-17 V3.2.4 (2020-09)
Electrical safety: EN 61010-1:2010 + A1:2019 +
A1:2019/AC:2019
Technical data

GEMÜ 1441
www.gemu-group.com 7 / 19
FCC: This device complies with Part 15 of the FCC rules. Operation is subject to the following two condi-
tions:
•this device may not cause harmful interference, and
•this device must accept any interference received, including interference that may cause
undesired operation.
Changes or modifications made to this equipment to expressely approved by Gemü may void the
user´s authorization to operate this equipment.
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that in-
terference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be de-
termined by turning the equipment off and on, the user is encouraged to try to correct the interfer-
ence by one or more of the following measures:
•Reorient or relocate the receiving antenna.
•Increase the separation between the equipment and receiver.
•Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
•Consult the dealer or an experienced radio/TV technician for help.
Contains FCC ID: QOQ-GM220P
Contains IC: 5123A-GM220P
Technical data

www.gemu-group.com8 / 19GEMÜ 1441
Mechanical data
Installation position: Optional
Weight: Approx. 970g
Travel sensor: Integrated for direct mounting, remote mounting possible
Travel sensor version
Detection range: 0–75 mm
Operating range: 0–75 mm
Resistance: 5 kΩ
Minimum travel sensor change: 3% (only relevant for initialization)
Correlation - Travel sensor
spindle/valve position
Retracted (top) ≙ 100% (valve open)
Extended (bottom) ≙ 0% (valve closed)
Acoustic data
Noise emission: > 85 dB (A)
Operating conditions
Ambient conditions: Use in indoor spaces
Height: Up to 2000 m (above sea level)
Relative air humidity: Maximum 95%, non-condensing
Protection class: IP 65 acc. to EN 60529
Degree of contamination: 3 (pollution degree)
Electrical data
Power supply/set value input
Supply voltage: Via set value signal
Note: A voltage of 30 V DC and an input current of 100 mA must not be exceeded. In total, a power
of 1 W must not be exceeded.
Power consumption: < 0.3 W
Short-circuit proof: Yes
Duty cycle: Continuous duty
Electrical protection
class:
III
Set value input: 4 - 20 mA
Input type: passive
Load impedance: 11.2 V DC
(corresponds to 560 Ω at 20 mA)
Accuracy/linearity: ≤ ±0.5% of full flow
Temperature drift: ≤ ±0.1% of full flow
Technical data

GEMÜ 1441
www.gemu-group.com 9 / 19
Resolution: 12 bit
Reverse battery protec-
tion:
Yes
Overload proof: Yes (up to 30 V DC)
Analogue output
Accuracy: ≤ ±1% of full flow
Signal: 4 - 20 mA
Supply voltage: 10 – 30 V DC
Output type: passive
Temperature drift: ≤ ±0.5% of full flow
Resolution: 0.1 %
Short-circuit proof: Yes
Overload proof: Yes (up to 30 V DC)
Digital input
Function: Can be selected using software
Input type: passive
Input voltage: Typically 24 V DC (10—30 V DC)
Logic level "1": 10 — 30 V DC
Logic level "0": 0–5 V DC
Input current: Typically 6 mA DC
Digital output
Note: Limit the current consumption to < 15 mA.
Function: selectable using software
Supply voltage: Typically 24 V DC (7–30 V DC)
Output type: passive
Logic level "1": conductive
Logic level "0": disabled
Travel sensor input (for travel length code S01 – remote potentiometer)
Note: Travel sensor input is not galvanically isolated from the supply voltage/set value input.
Input voltage
range:
0 to UP+
Supply
voltage UP+:
Typically 0.48 V DC
Resistance range of re-
mote potentiometers:
1.8–6 kΩ (ideal 5 kΩ ±20%)
Technical data

www.gemu-group.com10 / 19GEMÜ 1441
Positioner data
Note: The following diagram is valid for valves with a standard assignment of the spindle position to the valve position (see
“Mechanical data“, page8).
Control diagram: Default setting / The control characteristic is adjustable.
4 mA2016128
0
75
100
50
25
Valve opening degree [%]
During initialization, the 1441 cPos-X positioner automatically detects the control function of the
valve and is adjusted by default so that the valve is closed when the signal is 4 mA*.
The assignment can subsequently be changed using parameters. The close-tight function that is in-
tegrated as standard ensures that the valve is moved completely to the end position when the sig-
nal Open or Close valve is given.
* For double acting actuators, depends on the pneumatic actuator
Positioner information: Control error:
(Dead zone)
1% default setting
0.1–25.0% (can be set at fixed values)
0.1–25.0% (adaptive self-adjustment)
Parameterization: Via app or HART
Initialization: Automatic via magnetic switch, app, digital input
or HART
Close tight function: Closed: W ≤ 0.5% Open: W ≥ 99.5% (can be
changed via the app)
Interface: Bluetooth Low Energy HART
Function Parameterization, configuring,
diagnostics
Parameterization, configuring,
diagnostics
Device status via app 1) Protocol Version 7
Device status via EDD
Prerequisite Compatible smartphone/tablet with
Android or iOS 1)
•Apple iOS: Version 11 or higher
•Android: Version 7.0
("Nougat") or higher
•Bluetooth 4.0 LE or newer
-
1) The compatible GEMÜ app can be downloaded in the respective stores (Apple App Store or
Google Play Store).
Technical data
Otros manuales para 1441 cPos-X
1
Este manual sirve para los siguientes modelos
5
Tabla de contenidos
Otros manuales de Posicionador de válvulas de GEM

GEM
GEM C67 CleanStar Guía del usuario

GEM
GEM 543 eSyStep Manual de usuario

GEM
GEM 1434 mPos Manual de usuario

GEM
GEM Q40 Manual de usuario

GEM
GEM 1436 cPos Manual de usuario

GEM
GEM 1434 mPos Instrucciones de montaje

GEM
GEM 4242 Manual de usuario

GEM
GEM 543 eSyStep Manual de usuario

GEM
GEM 1435 ePos Manual de usuario

GEM
GEM 533 Manual de usuario