Commissioning the System
Warning Firetrace® cylinders contain 12 bar pressure
This procedure shall be read in conjunction with system layout earlier in this booklet.
Do not turn integrated isolate valve until system is fully commissioned (pressurised)
Locate cylinder and firmly secure with bracket provided
Remove black cap from the top of the cylinder. Connect red Trace detection tube, tighten silver nuts and
secure with appropriate clips
Remove blank plug from pressure switch port
Fit Schrader adapter FT0172 and pressurise to 12 Bar / 175 psi using a nitrogen bottle
or air pump.
Remove Schrader adapter FT0172, remove gauge from gauge
port and fit into pressure switch port. (Fit blanking plug into
Gauge port to keep dust and debris out)
Using tape, mark the location of the needle on the pressure gauge (Mid Green) and leave system for a
minimum of ten minutes per metre of Trace detection tube to check for any leaks on the detection
tube.
When satisfied pressure is good and no leaks have occurred, remove blank plug and open isolate valve
slowly using the key provided. Remove gauge from pressure switch port and fit into gauge port.
System is now live
Optional FT0124 pressure switch can be fitted in gauge adapter
on head assembly or if not pressure switch supplied, replace the blank
plug
Please note system will not operate with isolate
valve in closed position