FGD FlameSpec IR3-H2 Manual de usuario

FlameSpec IR3-H2 User Manual Doc. No. F150V0020.09
4222 E. La Palma Ave, Anaheim, CA 92807 USA T: (+1) 714-671-8500
www.fg-detection.com · [email protected]
FlameSpec IR3-H2

Information
FlameSpec-IR3-H2 Triple IR H2 Flame Detector User Guide, January 2023
Copyright © Fire & Gas Detection Technologies Inc. All rights reserved.
The owner or authorized user of a valid copy of this manual may reproduce this publication for the
purpose of learning to use the specified equipment. No part of this publication may be reproduced or
transmitted for commercial purposes, such as selling copies of this publication or for providing paid for
support services.
The Fire & Gas Detection Technologies logo is a trademark of Fire & Gas Detection Technologies Inc.,
registered in the U.S. and other countries.
Every effort has been made to ensure that the information in this manual is accurate. However, Fire &
Gas Detection Technologies Inc. is not responsible for any inaccuracy or omission in this document. The
information in this document is subject to change without notice.
Legal Notice
Hardware, software or documentation is forbidden to reproduced, transmitted, transcribed, stored in a
retrieval system or translated into any language or computer language, in any form or by any means.
While great efforts have been made to assure the accuracy and clarity of this document, FIRE & GAS
DETECTION TECHNOLOGIES INC. assumes no liability resulting from any omissions in this document, or
from misuse of the information obtained herein. The information in this document has been carefully
checked and is believed to be entirely reliable with all of the necessary information included.
FIRE & GAS DETECTION TECHNOLOGIES INC. reserves the right to make changes to any products
described herein to improve reliability, function, or design, and reserves the right to revise this
document and make changes from time to time in content hereof with no obligation to notify any
persons of revisions or changes. FIRE & GAS DETECTION TECHNOLOGIES INC does not assume any
liability arising out of the application or any use of any product or circuit described herein; neither does
it convey license under its patent rights or the rights of others.

FlameSpec IR3 H2 User Manual Doc. No. F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com iii
Table of Contents
1. Introduction .................................................................................................................... 1
Features ..............................................................................................................................1
Model Number Description ..................................................................................................2
Internal tests .......................................................................................................................2
Product Overview ................................................................................................................3
Accessories ..........................................................................................................................4
2. Installation ..................................................................................................................... 8
General Considerations ........................................................................................................8
Preparations for Installation ............................................................................................... 11
Required Tools ................................................................................................................... 11
Certification Instructions .................................................................................................... 11
Mounting the Tilt Mount .................................................................................................... 12
Mounting the detector ....................................................................................................... 14
Electrical Wiring ................................................................................................................. 15
Current Output (0-20mA) Wiring ........................................................................................ 17
4 Wire Relay Connection .................................................................................................... 19
RS-485 Communication Network ........................................................................................ 20
Cabling Recommendations ................................................................................................. 20
Earth/Ground Regime ........................................................................................................ 21
3. Configuration options ................................................................................................... 22
Sensitivity .......................................................................................................................... 23
Ultra-Fast Detection ........................................................................................................... 23
Alarm Delay ....................................................................................................................... 23
Alarm Latch ....................................................................................................................... 23
Enable Pre-Alarm 0-20mA .................................................................................................. 24
Enable dirty window warning 0-20mA ................................................................................ 24
Auxiliary Relay ................................................................................................................... 24

FlameSpec IR3 H2 User Manual Doc. No. F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com iv
Window Heater ................................................................................................................. 24
Modbus Address ................................................................................................................ 24
Manual BIT – Alarm Output Test (Full Loop test) ................................................................. 24
4. Operation ..................................................................................................................... 25
Output Signals ................................................................................................................... 25
Testing............................................................................................................................... 26
Flame Simulator ................................................................................................................. 26
5 Maintenance ................................................................................................................ 27
Cleaning Procedure ............................................................................................................ 27
6 Troubleshooting ............................................................................................................ 28
7 Servicing ....................................................................................................................... 29
8 FGD Communicator Software ........................................................................................ 29
9 Specifications ................................................................................................................ 30
Fire Detection .................................................................................................................... 30
Electrical Specifications ...................................................................................................... 30
Outputs ............................................................................................................................. 31
Mechanical Specifications .................................................................................................. 31
Environmental Specifications ............................................................................................. 31
Product Labeling ................................................................................................................ 32
Approvals .......................................................................................................................... 34
Electromagnetic Compatibility ........................................................................................... 34
10 Performance .............................................................................................................. 35
FLS-IR3-H2-ASX1 (Standard Model) ..................................................................................... 35
False Alarm Immunity ........................................................................................................ 36
11 Ordering Information ................................................................................................. 37
12 Warranty ................................................................................................................... 38
Appendix A .......................................................................................................................... 39

FlameSpec IR3 H2 User Manual Doc. No. F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com v
List of Figures
Figure 1 - Front view of the FLS-IR3-H2 ........................................................................................................ 3
Figure 2 - Rear view of the FLS-IR3-H2 .......................................................................................................... 3
Figure 3 - Tilt mount ..................................................................................................................................... 4
Figure 4 - Weather COVER ............................................................................................................................ 4
Figure 5 - Pole Mount ................................................................................................................................... 5
Figure 6 - Air Shield ....................................................................................................................................... 5
Figure 7 - Flame Simulator Kit ....................................................................................................................... 6
Figure 8 - FLS-FSIM-IR3-H2 Flame Simulator Front View .............................................................................. 6
Figure 9 - Duct Mount DMX-S01 ................................................................................................................... 7
Figure 10 - Duct Mount DMW-S01 ............................................................................................................... 7
Figure 11 - Horizontal Field of View .............................................................................................................. 9
Figure 12 - Vertical Field of View .................................................................................................................. 9
Figure 13: Tilt Mount Base - Front View ..................................................................................................... 13
Figure 14: Tilt mount base – Side View ....................................................................................................... 13
Figure 15 - Detector on Tilt Mount – Side View.......................................................................................... 14
Figure 16 – Terminal View .......................................................................................................................... 15
Figure 17 – Source 4-Wire Scheme ............................................................................................................. 17
Figure 18 – Sink 4-Wire Scheme ................................................................................................................. 17
Figure 19 – Source 3-Wire Scheme ............................................................................................................. 18
Figure 20 – Sink 3-Wire Scheme ................................................................................................................. 18
Figure 21 - 4 Wire Relay Connection .......................................................................................................... 19
Figure 22: RS-485 Networking .................................................................................................................... 20

FlameSpec IR3 H2 User Manual Doc. No. F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com vi
List of Tables
Table 1: Terminal connections .................................................................................................................... 16
Table 2: Detector Configuration Options .................................................................................................... 22
Table 3: Sensitivity levels ............................................................................................................................ 23
Table 4: Output Signals ............................................................................................................................... 25

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 1
1. Introduction
The FlameSpec-IR3-H2 flame detector will detect hydrogen and other “energy transition” fires quickly
allowing actions to be initiated to minimize the extend of the fire. The detector addresses slow growing
fires as well as fast eruptions of fire using improved IR3 technology. The detector operates in all weather
and light conditions.
These features, along with a built-in event logger, provide additional means to study the cause and
development of fire events.
The detector is certified for use in hazardous area locations; it may also be used in other areas not
classified as hazardous. The two cable/conduit entries either side of the lower part of the detector
housing are for connecting power and outputs to associated signaling equipment.
During normal operation, the flame detector performs self-tests of its optics, electronics, and software.
These include a periodic BIT (Built-In-Test) in which the sensors and window cleanliness are tested.
Features
High sensitivity - up to 100ft (30m)
Ultra-fast detection mode - detection within 40 milliseconds for fireballs or explosions.
Detection of “energy transition” flames, like hydrogen, methane, syngas, and methanol
Extreme sensitivity: Up to 100 ft. (30m) for a 32” plume, 1.5secs response
Option: Improved speed of response for standard fires - (0.5s) for enclosed space protection, like spray
paint booths or printing presses
Built-in-Test (BIT) - Automatic and manual self-test of window cleanliness and detector operation.
Window heater to avoid condensation and icing.
Tilt mounting bracket for accurate detector positioning.

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 2
Model Number Description
Model No are defined as follows:
FLS-IR3-H2 - A S X X
0 Standard, no Hart and not SIL certified.
1 Standard
5 Design for, but not limited to, automotive spray paint applications
where compliance with 0.5 s response (per NFPA 33) is needed.
Generally used for enclosed spare protection.
1 M25
2 ¾” NPT
1.2.1 Enhanced performance options
Option 5: Design for, but not limited to, enclosed space protection like automotive spray paint applications
where compliance with 0.5 s response (per NFPA 33) is needed
Internal tests
During normal operation, the flame detector performs self-tests of its optics, electronics and software. These
include a periodic BIT (Built-In-Test) in which the sensors and window cleanliness are tested. Any detected
fault is indicated as shown in Table 4 (in section 4). During “Dirty Window” fault the detection sensitivity is
significantly reduced, while “Fault” refers to critical faults which totally prevent flame detection.

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 3
Product Overview
FIGURE 1 - FRONT VIEW OF THE FLS-IR3-H2
FIGURE 2 - REAR VIEW OF THE FLS-IR3-H2

FlameSpec IR3-H2 User Manual F150V0020.09
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com 4
Accessories
1.5.1 Mounting Bracket
The detector should be mounted using the
stainless-steel tilt mount part number FLS-
TMO-S01. This allows the detector to be
securely attached to a wall, pole or other
solid surface using appropriate fixings. See
section2.5 and 2.6 for further details.
F
IGURE
3
-
T
ILT MOUNT
1.5.2 Weather Cover
The weather
cover
P/N
FLS-WCO-S01
protect the detector from extreme
weather conditions such heat, rain and
snow
FIGURE 4 - WEATHER COVER
Otros manuales para FlameSpec IR3-H2
1
Tabla de contenidos
Manuales populares de Detector de gas de otras marcas

Macurco
Macurco GD-6 Manual de usuario