fully. If this does not clear the message, the transducer and/or
controller should be replaced.
ERROR! ChECk
pREssuREsEnsOR!
Programming Mode
The controller has several user accessible menu’s. This menu “loop”
allows for adjustment of several variable parameters. The Controller
has 3 buttons below the display for these adjustments. In most
cases, a description of the button function is shown in the digital
display area.
Once you enter the programming mode, the controller will save your
last entry upon pressing ENTER. If an adjustment is made without
pressing ENTER, and the controller returns to the main screen and
the adjustment will not be saved. If a key is not depressed for about
25 seconds, the controller exits programming mode and returns to
the operational mode.
Press and hold any key for 3 seconds to enter programming mode.•
II – Press the middle key to advance to “FLUSH TIME: XXX S”•
screen. Press left or right key to advance to
“PRESSURE UOM: XXX” screen.
PRESSURE UOM: XXX -• This parameter determines whether PSI
or BAR will be the unit of measure used to display the storage
tank water pressure. Use the +/- keys to adjust this value. Press
ENTER to save the selected value and advance to the next screen.
TANK FULL P: XXX -• This parameter determines the pressure at
which RO water production will stop, or turn “off”. This setting is
normally 100 PSI (6.9 bar). Range is 70-100 PSI (4.8-6.9 bar) in 5
PSI (0.3-0.4 bar) increments. Use the +/- keys to adjust this value.
Press ENTER to save the selected value and advance to the next
screen.
START DIFF.: XXX -• This parameter determines the pressure
differential between the RO water production start (“on”)
pressure and stop (“off”) pressure. This setting is normally 20
PSI (1.4 bar). Range is 10-25 PSI (0.7-1.7 bar) in 5 PSI (0.3-0.4 bar)
increments. Use the +/- keys to adjust this value. Press ENTER to
save the selected value and advance to the next screen.
FLUSH DIFF.: XXX -• This parameter determines the pressure
differential between the RO water production start (“on”)
pressure and minimum allowable flush pressure. This setting is
normally 20 PSI (1.4 bar). Range is 0-25 PSI (0.0- 1.7 bar) in 5 PSI
(0.3-0.4 bar) increments. Use the +/- keys to adjust this value.
Press ENTER to save the selected value and advance to the next
screen.
FLUSH TIME: XXX S -• This parameter determines the flush
duration. Upon determining the recovery and reject flow (see
“RECOVERY ADJUSTMENT/CALIBRATION” section) a time value
in seconds is entered for this setting. Range is 0-990 seconds in
5 second increments. Use the +/- keys to adjust this value. Press
ENTER to save the selected value and advance to the next screen.
FLUSH INT: X.X H -• This parameter determines the flush interval.
If the system does not process water for the time value selected,
the system will enter DEEP FLUSHING mode. Range is 0.0 - 9.5
hours in 0.5 hour increments. Use the +/- keys to adjust this value.
The factory default setting of 1.5 hours is adequate in most
applications. Press ENTER to save the selected value and
advance to the next screen.
RESET COUNTER? -• This parameter allows resetting the total
run time in hours, which is displayed in the MAIN SCREEN VIEW.
Press YES to reset, NO to NOT reset. The Controller saves your
selection and goes to the next screen.
4
CONTROL SYSTEM OPERATION
The MRS-600HE system includes a micro-processor based control
system that monitors system conditions and controls the system
operation. A digital display panel provides operational information
and 3 buttons provide operator access. To follow is a list of modes
and a description of each function. Use this as a guide during
startup, normal operation and when service is required.
Operational Mode
INITIAL POWER-UP -• When power is first applied to the system,
the panel will display the system identification with software
version. After several seconds, it will automatically transition to
the MAIN SCREEN VIEW.
EnVI-RO 3.07
MAIN SCREEN VIEW -• When the system is in normal operation
and not operating in any of the following operational modes, the
panel will display the storage tank water pressure and total run
time in hours since start-up, or last counter reset.
pREssuRE XXXpsI(BAR)
TOTAl XXXX.XXhR
PRESSURIZE -• When pressure in the storage tank drops below the
pressure “on” setting, the system will start processing water and
refill the storage tank. Once the pressure in the storage tank rises
above the pressure “off” setting, the system will stop. Run time in
seconds and storage tank water pressure will be displayed.
pREssuRIZE...
XXXXs XXXpsI(BAR)
DEEP FLUSHING -• If the MRS-600HE System remains idle for the
programmed length of time, the control system will automatically
go into DEEP FLUSHING mode. During this time, there will be flow
to drain (reject). Remaining flush time in seconds and storage tank
water pressure will be displayed.
DEEpFlushIng...
XXXXs XXXpsI(BAR)
RE-PRESSURIZE -• At the start of the DEEP FLUSHING operation, the
system will re-pressurize to the normal tank full pressure, then begin
DEEP FLUSHING. Storage tank water pressure will be displayed.
Under normal conditions, the pressure in the storage tank will
remain above the minimum allowable flush pressure throughout
the DEEP FLUSHING operation. Once the DEEP FLUSHING
operation ends, the system returns to normal operation, but will
not PRESSURIZE until the storage tank water pressure drops
below the minimum allowable flush pressure. Once it runs and
fills, the system returns to operating within the normal “on” and
“off” pressure settings.
If the storage tank water pressure drops below the minimum
allowable pressure setting during DEEP FLUSHING, the control
will enter PRESSURIZE mode and refill the storage tank to the
normal “off” pressure, then resume normal operation.
RE-pREssuRIZE...
XXXpsI(BAR)
ERROR! CHECK PRESSURE SENSOR! –• This message indicates
a fault with the pressure sensing circuit. Check the electrical
connector at the pressure transducer to make sure it is inserted