System Manual ESM-F
6
Technical data
General technical data
Parameter Value Unit
Housing material Polyamide PA6.6
Dimensions ESM-F-B.. ESM-F-I.. ESM-F-O..
114 x 99 x 45 114 x 99 x 22.5 114 x 99 x 22.5 mm
Weight Approx. 0.26 Approx. 0.13 Approx. 0.18 kg
Connection type Plug-in connection terminals
Terminals 0.14 … 2.5 mm²
Ambient temperature
at UB= 24 V DC -15 ... +55 °C
Degree of protection to EN IEC 60529
IP 20
Degree of contamination
2
Mounting Expansion connector on DIN rail 35 mm
according to DIN EN 50022-35
Life Mechanical 1 x 107operating cycles
Electrical 1 x 105operating cycles
Connection data, base units ESM-F-B...
Parameter Value Unit
Operating voltage 24 ± 10% 1) V DC
Reverse polarity protection Yes
Power consumption Approx. 3.5 VA
Control voltage
at start button 18.6 … 26 V DC
Control cable length max.
(cross-section 0.75 mm²) 1000 m
Current consumption, max.
140without monitoring outputs mA
with monitoring outputs 320
External contact fuses
(safety circuit)
according to EN IEC 60269-1
10 AgG (T6A / F8A)
Rated impulse withstand voltage 2.5 kV
Leakage path and air gap acc. to
DIN VDE 0110-1:1997-04 4 kV
Cumulative therm. current for all
contacts 10 A
Safety contacts
Switching current, min., at 24 V DC
20 mA
Maximum switching voltage 50 V DC
250 V AC
Utilization category according to UeIeSIe
EN IEC 60947-5-1 AC-12 250 V 8 A
10 A
AC-15 250V 3 A
DC-12 50 V 8 A
DC-13 24 V 3 A
LEDs 13, diagnostics and status
Monitoring outputs (semiconductor)
Short circuit-proof Yes
Continuous current max. 30 mA
Output voltage 24 V DC
Inputs
Circuit ESM-F-BSN… 2 inputs, NC contact/NC contact, 2-channel
with short-circuit monitoring and earth fault monitoring
ESM-F-BMN… 2 inputs, NC contact/NO contact, 2-channel
with short-circuit monitoring and earth fault monitoring
1) All the electrical connections must either be isolated from the mains supply by a safety transformer according to EN IEC 61558-
2-6 with limited output voltage in the event of a fault, or by other equivalent isolation measures.
Ue= Switching voltage Ie= Maximum switching current per contact
SIe=
Maximum switching current per all safety contacts
(cumulative current)