Envirco MAC 10 Manual

Version1
Updated 2.5.11
*** READ AND SAVE THESE INSTRUCTIONS ***
MAC 10 LE-AC FAN FILTER MODULE
INSTALLATION AND SERVICE MANUAL
STANDARD, RSR, RSRE MODELS
Mac 10 and VE5 are registered Trademarks of the
Envirco, U.S.A.
US Patents 4,560,395 and 5,470,363 Other patents issued and pending in foreign countries
R
RR

MAC 10 LE-AC SERVICE MANUAL
Critical operation conditions of the MAC 10
1. Touching of the HEPA filter will damage it, voiding the warranty on the
filter. The screen is only to protect against an accidental ‘touch’ of the
filter. Never place a hand or tool on the filter. Never lie filter face flat
down on a surface always have filter on its side or back to protect from
damage.
2. Prior to powering the unit, verify that the unit has been plugged into the
correct voltage. The serial number label on the top of the Mac 10 unit has
the required voltage.
3. For reorder prepossess the Mac 10 part number and serial number
should be recorded. This information is located on the serial number
label, located adjacent to the electrical box. If you can’t located the Sales
Order Number please contact Envirco for this information.
Part Numbers Covered by this Manual
Note: A ‘Z’ in the part number indicates that the unit is special. This may
indicate a size change from standard or a special filter. Please contact
the factory for part numbers if this is the situation.
CAUTION
TO REDUCE THE RISK OF INJURY TO PERSONS, INSTALL FAN AT
LEAST 2.1M (7 FEET) ABOVE THE FLOOR
11194-XXX Mac 10 LE AC 2x4 (600x1210mm) Standard Filter
Mac 10 LE AC 2x4 (600x1210mm) RSR/E Filter

MAC 10 LE-AC SERVICE MANUAL
2EGAP
READ AND SAVE THESE INSTRUCTIONS
WARNING!
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS,
OBSERVE THE FOLLOWING :
A. Installation work and electrical wiring must be done by qualified person(s) in
accordance with all applicable codes and standards, including fire-rated construction.
B. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other
hidden utilities.
C. If this unit is to be installed over a tub or shower, it must be marked as appropriate
for the application.
D. Use this unit only in the manner intended by the manufacturer. If you have any
questions, contact the manufacturer:
ENVIRCO
101 McNeill Road
Sanford, NC 27330
Tel: (919) 775-2201
Tel: (800) 884-0002
Fax: (800) 458-2379
ASIAN SALES
Building #1
200 Middle Suhong Road
Suzhou, Jiangsu
PRC 215021
Tel: (86) 512 6258 0031
Fax:(86) 512 6258 7180
Europe, Middle East & Africa (EMEA)
TRION Div of Ruskin Air Management Ltd
European Operations
The Cavendish Center Winnall Close
Winchester Hampshire
S023 OLB, UK
Tel: +44 (0) 1962 840465
Fax: +44 (0) 1962 828619
E. Before servicing or cleaning unit, switch power off at service panel and lock service
panel to prevent power from being switched on accidentally.

MAC 10 LE-AC SERVICE MANUAL
Table of Contents
Title Page
1 INSTALLATION ................................................................................................................................. 4
FIGURE 1 – UNIT UNCRATING.............................................................................................................. 4
2 SERVICE: CLEANING THE MAC 10 LE-AC PREFILTER (FOAM)....................................... 5
FIGURE 2 – FOAM PREFILTER CLEANING....................................................................................... 5
3 SERVICE: CLEANING THE MAC 10 LE-AC PREFILTER (G4 PLEATED PREFILTER) .. 6
FIGURE 3 – G4 PREFILTER REPLACEMENT..................................................................................... 6
4 SERVICE: REMOVAL AND REPLACEMENT OF THE HEPA/ULPA FILTER
(STANDARD UNIT) .................................................................................................................................... 7
FIGURE 4 – STANDARD FILTER REPLACEMENT ........................................................................... 7
5 SERVICE: REMOVAL AND INSTALLATION OF THE ROOM SIDE REPLACEABLE
GEL SEAL FILTER (RSR/RSRE)............................................................................................................. 8
FIGURE 5 – RSR SHEET METAL FILTER REPLACEMENT............................................................ 9
6 SERVICE: REMOVAL AND INSTALLATION OF THE MOTOR (STANDARD AND RSR
MODELS) ................................................................................................................................................... 10
FIGURE 6 – MOTOR REPLACEMENT ................................................................................................ 11
7 SERVICE: REMOVAL AND INSTALLATION OF THE RSRE MOTOR.............................. 12
FIGURE 7 – RSRE MOTOR REPLACEMENT .................................................................................... 13
FIGURE 8 –MOTOR BLOWER COMPONENTS ................................................................................ 13
8 ON/OFF SWITCH - SPEED/AIRFLOW ADJUSTMENT ............................................................ 14
FIGURE 9 – ELECTRICAL BOX FACE................................................................................................ 14
9 TROUBLE SHOOTING: .................................................................................................................. 15
10 MAC 10 LE-AC WIRING DIAGRAMS ...................................................................................... 16
11 MAC 10 LE-AC REPLACEMENT PARTS LIST: .................................................................... 17
12 WARRANTY ...................................................................................................................... ............ 18

MAC 10 LE-AC SERVICE MANUAL
4EGAP
1INSTALLATION
Note: The MAC 10 LE-AC Fan Filter Unit is completely assembled at the factory with
the exception of the optional ¼” (0.64 cm)-20 eyebolts, which can be used
when hanging the unit from an overhead structure.
Step 1. Carefully remove the unit from the shipping carton and inspect for any damage
that may have occurred during transportation. (See Figure 1)
Step 2. Wipe down plastic bag and move unit into clean room. (Double bagging is
available upon request.)
Step 3. If using rigidly supported grid (usually 2” (50 mm) or wider), raise unit through
ceiling and lower onto the gasketed grid. If using a flexible grid (typically
supported with wires) the unit must be secured to an overhead structure with
eyebolts, s-hooks and chain or ¼-20 all thread. A roll of high-density gasket has
been provided for use with ungasketed grids. Note: special size units are
available to fit specific clean room grid systems.
Step 4. Have an electrician wire the unit to the appropriate voltage (115V, 220V, 277V
AC), according to the wiring diagram in section IX and local electric codes. If
optional power cord was purchased, plug unit into a grounded receptacle. The
optional power cord is not acceptable for plenum installations.
Figure 1 – Unit Uncrating

MAC 10 LE-AC SERVICE MANUAL
5 E G A P
2SERVICE: Cleaning the MAC 10 LE-AC Prefilter (foam)
WARNING!
Disconnect the unit from the electrical power source before attempting any
service.
Tools Required: None
Note: To keep the filter in top operating condition, washing the foam prefilter is
recommended every three to six months.
Step 1. To gain access to the prefilter, remove the ceiling panel next to the unit, if
applicable.
Step 2. Switch the ON-OFF switch to the off position.
Step 3. Remove the prefilter from the snap-in frame. (See Figure 2)
Step 4. Clean the prefilter by hand washing in water with a mild detergent or by using a
vacuum cleaner. Allow prefilter to dry completely before replacing.
Step 5. Reassemble by reversing the above steps.
ON/OFF Switch

MAC 10 LE-AC SERVICE MANUAL
6 E G A P
Figure 2 – Foam Prefilter Cleaning
3 SERVICE: Cleaning the MAC 10 LE-AC Prefilter (G4 Pleated
Prefilter)
WARNING!
Disconnect the unit from the electrical power source before attempting any
service.
Tools Required: None
Note: To keep the filter in top operating condition replacing the pleated prefilter is
recommended every twelve months or sooner.
Step 1. To gain access to the prefilter, remove the ceiling panel next to the unit, if
applicable.
Step 2. Switch the ON-OFF switch to the off position.
Step 3. Remove the prefilter from the snap-in frame. The beverage frame has slots
that have to be depressed to release the filter from the prefilter housing (See
Figure 3)
Step 4. After removing the new G4 pleated prefilter from the box, remove the die cut
slots from the beverage board frame and install on prefilter bracket.
Step 5. Reassemble by reversing the above steps.
Figure 3 – G4 Prefilter Replacement
ON/OFF Switch

MAC 10 LE-AC SERVICE MANUAL
7EGAP
4 SERVICE: Removal and Replacement of the HEPA/ULPA
Filter (Standard Unit) WARNING!
Disconnect the unit from the electrical power source before attempting any
service.
WARNING!
The Standard Filter is protected with an expanded metal face screen. This is
never to be used to handle the filter. It is only for protection against an accidental
touch of the filter. Only handle the filter by the frame.
Tools Required: Phillips Head Driver, Battery Operated Drill with a 5/32 Drill
Bit, Rivet Hand Tool, Ø5/32 aluminum rivet grip range .126-
.187
Step 1. Remove unit from ceiling.
Step 2. Remove the 10 screws holding the HEPA/ULPA filter to the lid assembly.
Step 3. Lift the lid assembly off the HEPA/ULPA filter (see Figure 3). Remove Filter
deflectors using 5/32 drill bit. Keep filter deflectors to install in new filter.
Discard the used filter as per requirements of the applicable regulations.
Carefully install the filter deflectors into the new filter using the 5/32 rivets. Do
not touch or place the filter deflectors on the HEPA/ULPA media pack. This
could cause tears in the filter pack.
Note: Before replacing with a new HEPA/ULPA filter, carefully inspect the new filter for
any visible damage. Also inspect the gasket in the “tee” bar to insure a tight seal.
Replace as necessary.
Step 4. Replace with the new HEPA/ULPA filter and assemble by reversing the above
steps.
Figure 4 – Standard Filter Replacement
Lid Screw (10)
HEPA/ULPA
Filter
Lid Assembly
ON/OFF
Switch
#8 SCREWS
(
10X
)
Ø5/32 RIVET
(
6X
)
FILTER DEFLECTOR
Speed Control

MAC 10 LE-AC SERVICE MANUAL
8
5 SERVICE: Removal and Installation of the Room Side
Replaceable Gel Seal Filter (RSR/RSRE)
WARNING!
Disconnect the unit from the electrical power source before attempting any
service.
WARNING!
The RSR Filter is protected with an expanded metal face screen. This is never to
be used to handle the filter. It is only for protection against an accidental touch of
the filter. Only handle the filter by the frame.
Tools Required: Phillips Head Driver
3/16” hex head wrench
Manpower Required: 2
Step 1. Remove the diffuser screen by removing the 6 each 10-32x1/2 screws.
Step 2. Loosen the six 1/4x20 socket head screws far enough to rotate the filter clip
90°. The filter will not drop during this operation. Slowly pull the filter away
from the knife-edge seal, taking care not to touch the filter face during this
operation. It is important to pull the filter slowly away from the seal, so that the
gel remains in the filter gel track.
Step 3. Inspect filter for visible damage, if damaged set aside for replacement or repair.
Step 4. Inspect the gel seal, if reinstalling the removed filter. Determine if the gel has
lost its ability to seal, if so repair the gel.
Step 5. Place the filter against the filter-sealing surface of the RSR unit. Install filter
clips and screws. The clips can be rotated and angled into place. Using the
clips as a lever the filter can be seated. It is recommended to work either
clockwise or counter clock wise around the filter, raise the filter into the gel.
Step 6. Reinstall screen.
(Referenced by Figure 5 on page 9)

MAC 10 LE-AC SERVICE MANUAL
9EGAP
Figure 5 – RSR Sheet Metal Filter Replacement
Fan Filter Unit
Filter Clip and
Screw (typ 6)
Filter
Filter
Clip
Gel
Track
Perforated
Screen
¼ -20
Cap
Screw
Knife-edge
Seal
2-Piece Welded
Plenum Housing
Diffuser Screen
Screws (typ 6)
10-32 PHP