ENTRYPASS TECHNICAL –WIRING GUIDE
Version: 1.18
Last Updated: 18-07-2018
HCB WIRING GUIDE
EP.S3150 EP.N5150
EP.S3200 EP.N5200
EP.S3400 EP.N5400

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Notes:
N5150, N5200 and N5400 are network enabled controllers
S3150, S3200 and S3400 are serial enabled controllers
N5150 and S3150 have 4 inputs and 2 Outputs (2 Relays –Support 2 Doors, 2 Readers)
N5200 and S3200 have 8 inputs and 4 outputs (4 Relays -Support 2 Doors, 2 Readers). N5400
and S3400 have 8 inputs and 4 outputs (4 Relays –Support 4 Doors, 4 Readers)
N5200, S3200, N5400 and S3400 support unlimited access level
N5150 and S3150 not support unlimited access level
S3150, S3200, S3400, N5150, N5200 and N5400 support HID (AGK00, 09, 10, 11, 14, 19, 20),
Wiegand Multi-Bit, Keyed Card + Pin
N5150, N5200 and N5400 support AES Encryption
S3200, S3400, N5200, N5400 support event trigger
See http://www.entrypass.net/ for updates, revisions, and download the latest installation
manual
Platform1 version 3 support 6 and 10 digits format
For existing site, P1 will detect its card database to determine 6 or 10 digits; For new site, user
can change the digits as long as the card database is empty
Please refer to separate EntryPass Platform1 User Manual for detail operation help. The Official
EntryPass Platform1 User Manual can be downloaded from our website under “Download”
section or inside the Platform1 Server setup CD

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Technical Support
If you cannot find the answer to your question in this manual or in the Help files, we recommend you
contact your system installer. Your installer is familiar with your system configuration and should be able
to answer any of your questions.
Should you need additional information, please call our Technical Support Help desk, Monday to Friday
9:00 AM to 6:00 PM (GMT +8:00)
Method Details
Phone + 60 (3) -8068 1929
Fax + 60 (3) -8068 1922
Internet www.entrypass.net
Email support@entrypass.net
BEFORE YOU BEGIN

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
CAUTION
Battery may explode if mistreated. Do not recharge,
disassemble or dispose of in fire. To prevent a risk of explosion do
not pry the battery out with a metal or conductive tool.
Preparing Your EntryPass Controllers
EntryPass controller contains numerous delicate electronic circuits and components which can become
damaged as a result of electrostatic discharge (ESD). Thus, prior to installation, please follow the instruction
below:
•Observe precautions while handling the circuit board assembly by using proper grounding straps and handling
precautions at all
•Visually ensure no onboard parts is broken, damage or contains burn mark
•Do not turn on the power supply until you completed all wiring and external add on devices installations
Instances of Non-Warranty
•Damage due to natural disaster, accident or human cause.
•Damage as a result of violating the conditions recommended in the user manual
•Damage due to improper installation
•Damage due to use of uncertified components
•Damage due to use exceeding the permitted parameters
Considerations Prior to Installation

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
Relay
3Relay
4Supply Voltage
Selector Relay
LEDs
Supply
Voltage
Selector
Relay
LEDs
Buzzer Relay
1Relay
2Buzzer
ON/OFF MCU Battery
Address
Dip
Switch
Cold
Start
Switch
Reset
Switch
COM
Rx/Tx
LEDs
RS232
COMs
Heartbeat
LED
RS485
COMs
Network
Port
Cold Start,
Factory
Default
and AES
Hard reset
Selection
Jumper
Components Description

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
Lower Connector
Reader 1 Input 1,2 Relay 1 Relay 2 12V/5V
Voltage
supply
Reader 2 Input 3,4 RS485
Com3 RS485
Com2 RS485
Com1
O1D0 -Reader 2 Data 0 Input
O1D1 -Reader 2 Data 1 Input
LED2 -Reader 2 LED
BUZ2 -Reader 2 Buzzer
IN3 - Input 3
IN4 - Input 4
GND -Inputs Ground
C3- - RS485 COM3 (-) Connection
C3+ -RS485 COM3 (+) Connection
C2- - RS485 COM2 (-) Connection
C2+ -RS485 COM2 (+) Connection
C1- - RS485 COM1 (-) Connection
C1+ -RS485 COM1 (+) Connection
I1D0 -Reader 1 Data 0 Input
I1D1 -Reader 1 Data 1 Input
LED1 -Reader 1 LED
BUZ1 -Reader 1 Buzzer
IN1 - Input 1 (Default: Door Sensor)
IN2 - Input 2 (Default: Exit Push Button)
GND -Inputs Ground
NC1 -Relay 1 Normally Close Connection
COM1 -Relay 1 Common Input
NO1 - Relay 1 Normally Open Connection
NC2 -Relay 2 Normally Close Connection
COM2 -Relay 2 Common Input
NO2 - Relay 2 Normally Open Connection
VR1+ -Supply Voltage Positive Connection
(12V/5V)
GND -Supply Voltage Ground Connection
For VR1+ to supply 12V, please make sure JP6 is at 1-2 pins
For VR1+ to supply 5V, please make sure JP6 is at 2-3 pins
Legend Description

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
I2D0 I2D1 LED3 BUZ3 IN5 IN6 GND NC3 COM3 NO3 NC4 NO4COM4 VR2+ GND O2D0 O2D1 LED4 BUZ4 IN7 IN8 IN9 GND
Upper Connector - Only for EP.S3200, EP.S3400, EP.N5200, EP.N5400
Input 5, 6 Relay 3 Relay 412V/5V Voltage
supply Input 7, 8
Reader 3 Reader 4
I2D0 -Reader 3 Data 0 Input
I2D1 -Reader 3 Data 1 Input
LED3 -Reader 3 LED
BUZ3 -Reader 3 Buzzer
IN5 - Input 5
IN6 - Input 6
NC3 -Relay 3 Normally Close Connection
COM3 -Relay 3 Common Input
NO3 - Relay 3 Normally Open Connection
NC4 -Relay 4 Normally Close Connection
COM4 -Relay 4 Common Input
NO4 - Relay 4 Normally Open Connection
VR2+ -Supply Voltage Positive Connection
(12V/5V)
GND -Supply Voltage Ground Connection
O2D0 -Reader 4 Data 0 Input
O2D1 -Reader 4 Data 1 Input
LED4 -Reader 4 LED
BUZ4 -Reader 4 Buzzer
IN7 - Input 7
IN8 - Input 8
IN9 - Reserved
GND -Inputs Ground
Legend Description
For VR2+ to supply 12V, please make sure JP7 is at 1-2 pins
For VR2+ to supply 5V, please make sure JP7 is at 2-3 pins

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
+12V -Power Supply Positive 12V DC
-12V/GND -Power Supply Ground
ETH -Power Supply Earthing
ACC -AC Fail Monitoring
BAT/BS -Backup Battery Monitoring
+12V -12V/
GND ETH ACC BAT/
BS
Power Supply Connector
BAT/BS (Backup Battery Monitoring) point will monitor the backup battery
voltage which will supply power to the board when AC power is cut off
The minimum voltage for cutoff while using backup battery is 10.8V
Legend Description

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
ENTRYPASS
Power Supply Unit Specification:
•Switching Power Supply
•12V DC
•3 Amp (Minimum)
Power Supply Unit Specification

Copyright © Entrypass Corporation
ENTRYPASS TECHNICAL –WIRING GUIDE
-
+
NC1 COM1
Emergency
Breakglass
Emergency
Keyswitch
Electro-Magnetic Lock or Drop Bolt
–
+
Lower Connector
I1D0 I1D1 LED1 BUZ1 IN1 IN2 GND NC1 COM1 NO1 NC2 NO2COM2 VR1+ GND O1D0 O1D1 LED2 BUZ2 IN3 IN4 GND C3- C3+ C2- C2+ C1- C1+
+12V
GND
PSU
Diode(1N4002) must be installed at the locking devices in order to protect against back
EMF. It is advisable to connect EM lock COM to +12Vof PSU (Power Supply Unit)
Connecting the Lock (NC), Breakglass and Keyswitch