Elsner 70122 Guía

EN
KNX W
Wind Sensor
Installation and Adjustment
KNX W 20...30 V DC
KNX W 230 V AC
No. 70122
No. 70123


1 Content
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Wind Sensor KNX W • from software version 1.00, ETS programme version 1.1
Status: 11.11.2021 • Errors excepted. Subject to technical changes.
1. Description ........................................................................................... 3
1.1. Deliverables .............................................................................................................. 3
1.2. Technical specifications ........................................................................................... 3
2. Installation and commissioning ........................................................... 4
2.1. Location ..................................................................................................................... 5
2.2. Mounting the sensor ................................................................................................ 6
2.2.1. Attaching the mount ..................................................................................... 6
2.2.2. View of rear side and drill hole plan ........................................................... 7
2.2.3. Preparing the sensor .................................................................................... 8
2.2.4. PCB layout ..................................................................................................... 9
2.2.5. Mounting the weather station ................................................................... 10
2.3. Notes on mounting and commissioning .............................................................. 11
3. Addressing of the device at the bus .................................................. 12
4. Maintenance ....................................................................................... 12
5. Disposal ............................................................................................. 12
6. Transmission protocol ....................................................................... 14
6.1. List of all communication objects ......................................................................... 14
7. Setting of parameters ........................................................................ 17
7.1. General settings ..................................................................................................... 17
7.2. Threshold values .................................................................................................... 17
7.2.1. Wind threshold value 1 / 2 / 3 .................................................................... 17
7.3. Logic ....................................................................................................................... 19
7.4. AND Logic 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 ......................................................................... 19
7.4.1. Linkage inputs of AND Logic ..................................................................... 20
7.4.2. OR Logic 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 ................................................................ 21
7.4.3. Linkage inputs of OR Logic ........................................................................ 21

2 Clarification of signs
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to-
date version of the manual is available.
Clarification of signs used in this manual
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER! ... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
WARNING! ... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
CAUTION! ... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
ATTENTION! ... indicates a situation which may lead to damage to property if it is
not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.

3 Description
Wind Sensor KNX W • Status: 11.11.2021 • Technical changes reserved. Errors reserved.
1. Description
The Wind Sensor KNX W measures wind speed and transfers the values to the KNX
system. Three switching outputs with adjustable threshold values as well as additional
AND and OR logic gates are available.The sensor system, the evaluation electronics
and the electronics of the bus connection are mounted in a compact housing.
Functions:
•Wind measurement: The wind strength measurement takes place
electronically and thus noiselessly and reliably, even during hail, snow and
sub-zero temperatures. Even turbulent air and anabatic winds in the vicinity of
the weather station are recorded
•Wind sensor monitoring: If the wind measurement value changes by less
than ± 0.5 m/s within 48 hours, the maximum measurement value of 35 m/s is
output as a fault message. All wind alarms with a limit value below 35 m/s
become active as a result
•3 threshold values can be adjusted per parameter or via communication
objects
•8 AND and 8 OR logic gates with each 4 inputs. Every switching incident as
well as 8 logic inputs (in the form of communication objects) may be used as
inputs for the logic gates. The output of each gate may optionally be configured
as 1 bit or 2 x 8 bits
Configuration is made using the KNX software ETS. The product file can be down-
loaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Ser-
vice” menu.
1.1. Deliverables
• Sensor with combined wall/pole mounting
• 2x stainless steel installation band for pole installation
1.2. Technical specifications
Housing Plastic material
Colour White / translucent
Mounting On-wall
Degree of protection IP 44
Dimensions approx. 96 × 77 × 118 (W × H × D, mm)
Weight 230 V AC version: approx. 240 g,
20...30 V DC version approx. 170 g
Ambient temperature Operation -30…+50°C, storage -30…+70°C
Operating voltage Available for 230 V AC or 20...30 V DC.
An appropriate power supply unit can be obtained from
Elsner Elektronik.
Cable cross-section Massive conductors of up to 1.5 mm² or conductors
with fine wires

4 Installation and commissioning
Wind Sensor KNX W • Status: 11.11.2021 • Technical changes reserved. Errors reserved.
The product conforms with the provisions of EU directives
2. Installation and commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
DANGER!
Risk to life from live voltage (mains voltage)!
There are unprotected live components inside the device.
• Inspect the device for damage before installation. Only put undamaged devic-
es into operation.
• Comply with the locally applicable directives, regulations and provisions for
electrical installation.
• Immediately take the device or system out of service and secure it against un-
intentional switch-on if risk-free operation is no longer guaranteed.
Current 230 V AC version max. 20 mA.
20...30 V DC version: max. 30 mA., max. 0,4 W.
Residual ripple 10%
Data output KNX +/- bus terminal plug
Group addresses max. 254
Allocations max. 255
Communication objects 80
Measurement range Wind 0...35 m/s
Resolution (wind) 0,1 m/s
Accuracy (wind) at ambient temperature -20…+50°C:
±22% of the measurement value when incident flow is
from 45…315°
±15% of the measurement value when incident flow is
from 90…270°
(Frontal incident flow corresponds to 180°)

5 Installation and commissioning
Wind Sensor KNX W • Status: 11.11.2021 • Technical changes reserved. Errors reserved.
Use the device exclusively for building automation and observe the operating instruc-
tions. Improper use, modifications to the device or failure to observe the operating in-
structions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition and
after conclusion of all installation and operational start-up tasks, and only in the sur-
roundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.1. Location
Select an assembly location at the building where wind speed may be collected by the
sensor unobstructedly.
At least 60 cm of clearance must be left all round the device.This facilitates correct wind
speed measurement without eddies. The distance concurrently prevents spray (rain-
drops hitting the device) or snow (snow penetration) from impairing the measurement.
It also does not allow birds to bite it.
Fig. 1
There must be at least 60 cm of space below,
to the sides and in front of the sensor left
from other elements (structures, construction
parts, etc.).
60 cm
Fig. 2
The wind sensor must be mounted on a verti-
cal wall (or a pole).
Wall
or
pole

6 Installation and commissioning
Wind Sensor KNX W • Status: 11.11.2021 • Technical changes reserved. Errors reserved.
2.2. Mounting the sensor
2.2.1. Attaching the mount
The sensor comes with a combination wall/pole mount. The mount comes adhered by
adhesive strips to the rear side of the housing. Fasten the mount vertically onto the wall
or pole.
Fig. 3
The wind sensor must be mounted in the
horizontal transverse direction (horizontally).
Horizontal
Fig. 4
When wall mounting: flat side on wall, crescent-
shaped collar upward.
Collar
Fig. 5
When pole mounting: curved side on pole, collar
downward.
Collar

7 Installation and commissioning
Wind Sensor KNX W • Status: 11.11.2021 • Technical changes reserved. Errors reserved.
2.2.2. View of rear side and drill hole plan
Fig. 6
Different mounting arms are available from Els-
ner Elektronik as additional, optional accessories
for flexible installation of the weather station on
a wall, pole or beam.
Example of the use of a mounting arm:
Due to flexible ball joints, the sensor can be
brought into ideal position.
Fig. 7
Example use of the hinge arm mounting:
Fitting to a pole with worm drive hose clips
Slot hole 7,5 x 5 mm
Fig. 8 a+b
Drill hole plan
Dimensions of rear side of
housing with bracket. Sub-
ject to change for technical
enhancement.

8 Installation and commissioning
Wind Sensor KNX W • Status: 11.11.2021 • Technical changes reserved. Errors reserved.
2.2.3. Preparing the sensor
The sensor cover snaps in on the left and right along the bottom edge (see Fig.). The
cover of the 230V model is also screwed on top. Remove the cover. Proceed carefully,
so as not to pull off the wire connecting the PCB in the bottom part with the cover (sol-
dered cable connection in case of 230 V AC version, cable with plug in case of 20...30
V DC version).
Fig. 9
1 Screw-on cover (230V device)
2 Cover Snaps
3 Bottom part of housing
2
3
Unsnap cover and
remove upwards
1