The AUTOTRIP takes care of this for you by alternating the start point of
consecutive tests at any given setting. If for example you have selected atest
at the rated trip current (x1) of a30mARCD, the first press of the test button
will apply a30mA fault current starting on the positive half cycle (0°)
and display the result.Afurther press of the test button will carry out another
test at the same current but starting on the negative half cycle (180°).
RCD Test Procedure
Although fully protected against over voltage to 440V this tester should only be
used on a 240V AC supply.
Connect the 4mm plugs of the chosen test lead to the corresponding L, N&E
terminals of the AUTOTRIP and connect the other end to the socket or circuit
terminals under test.
If using the distribution board test lead set (TL-RGB) observe the correct polarity
by connecting the Red probe to the Live conductor, Black to Neutral and Green
to Earth.
Select the type and rating of the RCD to be tested with the rotary function
selector switch. (10mA, 30mA,100mA Type AC or 100mA Type S)
When first connected to a mains supply the AUTOTRIP will automatically conduct a
safety test to ensure that the Live, Neutral and Earth conductors are all
connected correctly and that the supply voltage is in the acceptable range
(195-253V).
If all is well the VOLTAGE/POLARITY warning LED will light Green and the
supply voltage will be displayed in the primary display area.
In the event of a problem with either the mains voltage supply or reversed
connections the VOLTAGE/POLARITY warning LED will light Red, a warning
tone will be sounded and testing will be inhibited.Do not proceed.
User Selected Manual Tests
x½
The recommended order of tests is firstly at x½ the rated current followed by a
x1 test at the rated current and finally, for 30mARCD’s onlyx5the rated current.
The default test parameter for the selected current
multiplier x½ is 0° for the phase polarity this
will be automatically selected for the first test. This will
be displayed on the LCD display along with the
Line-Neutral voltage.
Press the test button and atest will be conducted at the
selected settings. If successful and the RCD has failed
to trip asingle beep will sound and the main display
will be similar to figure 5.
Displaying 1st test result of x ½ test 0° (figure 5)