Eiko Z10 Series Manual de usuario

EiKO Global | 18000 W. 105th St, Olathe, KS 66061 | (P) 1-800-852-2217
EiKO Canada | 81 King St, Barrie, Ontario L4N 6B5 | (P) 1-705-721-5189 eiko.com
INSTALLATION INSTRUCTIONS
Z10 Sensors
SEN5A/PIR/Z10
SEN5A/M/Z10
SEN5A/PC/Z10
SEN5A/CT
SPECIFICATIONS:
POWER SUPPLY 12V-24V DC, >30mA
DIM CONTROL OUTPUT 0-10V, MAX. 25mA SINKING CURRENT
REMOTE RANGE 50ft (15m) INDOOR, NO BACKLIGHT
DETECTION RADIUS 20%/50%/75%/100% | 3.3 to 26.3ft (1 to 8m)
MOUNTING HEIGHT 12m (40ft)
TIME SETTING 10S/1MIN/5MIN/10MIN/15MIN/20MIN/30MIN/60MIN
LIGHT-CONTROL 24H/10LUX/30LUX/50LUX | 24H/0.93fc/2.8fc/4.6fc
TEMPERATURE -4°F to 140°F (-20°C- to 60°C)
IP RATING IP65
• NOTE: WARM UP TIME IS 40 SECONDS. AFTER THE SENSOR CONNECTS INPUT POWER FIRST TIME, THE LIGHT
WILL KEEP ON 40 SECONDS, THEN GO TO DIMMING TO WORK NORMALLY.
• NOTE: FACTORY DEFAULT SETTING: 100% SENSITIVITY, HOLD ON TIME: 5 MIN, DAYLIGHT SENSOR IS ,
DIMMING LEVEL: 30%, DIMMING TIME: 60 MIN.
• NOTE: ANY SETTING CHANGED BY THE REMOTE CONTROL WIILL BE SIGNALED BY THE LED LIGHT THAT SENSOR
IS CONNECTED TO WILL FLASH ON/OFF.
SENSOR COVERAGE:
Z10 PIR MOTION SENSOR WITH BILEVEL DIMMING + PHOTOSENSOR
H
D
MINOR MOTION
MAJOR MOTION
Height Diameter Range (D)
H (ft) Sensitivity
100% (ft)
Sensitivity
75% (ft)
Sensitivity
50% (ft)
Sensitivity
25% (ft)
40 40 20 0 0
30 50 40 5 0
20 40 40 20 10
10 40 40 40 20
UNLOCKLOCK

EiKO Global | 18000 W. 105th St, Olathe, KS 66061 | (P) 1-800-852-2217
EiKO Canada | 81 King St, Barrie, Ontario L4N 6B5 | (P) 1-705-721-5189 eiko.com
SPECIFICATIONS:
POWER SUPPLY 12V-24V DC, >50mA
DIM CONTROL OUTPUT 0-10V, MAX. 25mA SINKING CURRENT
HF SYSTEM 5.8GHz ± 75MHz
REMOTE RANGE 50ft (15m) INDOOR, NO BACKLIGHT
TRANSMISSION POWER <0.2mW
DETECTION RADIUS 20%/50%/75%/100% | 3.3 to 26.3ft (1 to 8m)
MOUNTING HEIGHT 39.4ft (12m)
TIME SETTING 10S/1MIN/5MIN/10MIN/15MIN/20MIN/30MIN/60MIN
LIGHT-CONTROL 24H/10LUX/30LUX/50LUX | 24H/0.93fc/2.8fc/4.6fc
TEMPERATURE -4°F TO 140° F (-20°C- TO 60°C)
IP RATING IP65
• NOTE: WARM UP TIME IS 15 SECONDS. AFTER THE SENSOR CONNECTS INPUT POWER FIRST TIME, THE LIGHT
WILL KEEP ON 15 SECONDS, THEN GO TO DIMMING TO WORK NORMALLY.
• NOTE: FACTORY DEFAULT SETTING: 100% SENSITIVITY, HOLD ON TIME: 5 MIN, DAYLIGHT SENSOR IS ,
DIMMING LEVEL: 30%, DIMMING TIME: 60 MINUTES.
• NOTE: ANY SETTING CHANGED BY THE REMOTE CONTROL WIILL BE SIGNALED BY THE LED LIGHT THAT SENSOR
IS CONNECTED TO WILL FLASH ON/OFF.
SENSOR COVERAGE:
Z10 MICROWAVE MOTION SENSOR WITH BILEVEL DIMMING + PHOTOSENSOR:
H
D
Height Diameter Range (D)
H (ft) Sensitivity
100% (ft)
Sensitivity
75% (ft)
Sensitivity
50% (ft)
Sensitivity
25% (ft)
40 40 30 5 0
30 60 50 20 0
20 40 40 30 10
10 40 40 40 20
UNLOCKLOCK

EiKO Global | 18000 W. 105th St, Olathe, KS 66061 | (P) 1-800-852-2217
EiKO Canada | 81 King St, Barrie, Ontario L4N 6B5 | (P) 1-705-721-5189 eiko.com
• THE Z10 PHOTOCELL IS DESIGNED TO CONTROL STREET LIGHTING, PASSAGE LIGHTING, AND DOORWAY
LIGHTING AUTOMATICALLY IN ACCORDANCE WITH THE AMBIENT LIGHTING LEVELS. EQUIPPED WITH ELECTRONIC
CIRCUITS, THE EASY-TO-TEST FEATURE WITH A TIME DELAY OF 5 SECONDS OFFERS A QUICK RESPONSE TO
LIGHTING LEVEL CHANGES. THE 5 SECOND TIME-DELAY PRESET PROTECTS AGAINST MALFUNCTION DUE TO
SPOTLIGHTS OR LIGHTNING DURING THE NIGHT.
Z10 PHOTOCELL:
UNLOCKLOCK
SPECIFICATIONS:
POWER SUPPLY 12V-24VDC
RATED FREQUENCY 50mA±5%
POWER CONSUMPTION 0.4Wmax
OPERATE LEVEL 16Lux On / 24Lux O | 1.5fc On / 2.2fc O
AMBIENT TEMPERATURE 99%RH
TEMPERATURE -40°F to 158°F (-40°C- to 70°C)
IP RATING IP65

OVERVIEW:
• THE WIRELESS IR COMMISSIONING TOOL IS A HANDHELD TOOL FOR REMOTE
CONFIGURATION OF IR-ENABLE FIXTURE INTEGRATED SENSORS. THE TOOL
ENABLES DEVICE TO MODIFY VIA PUSH BUTTON WITHOUT LADDERS OR
TOOLS, AND STORES UP TO FOUR SENSOR PARAMETER MODES TO SPEED
CONFIGURATION OF MULTIPLE SENSORS.
• USES BIDIRECTIONAL IR COMMUNICATION TO SEND AND RECEIVE SENSOR
SETTINGS AT MOUNTING HEIGHT UP TO 50 FEET. THE DEVICE CAN DISPLAY
PREVIOUSLY ESTABLISHED SENSOR PARAMETERS, COPY PARAMETERS, AND
SEND NEW PARAMETERS OR STORE PARAMETER PROFILES. FOR PROJECTS
WHERE IDENTICAL SETTINGS MAY BE DESIRED ACROSS A LARGE NUMBER
OF AREAS OR SPACES, THIS CAPABILITY PROVIDES A STREAMLINED METHOD
OF CONFIGURATION. SETTINGS CAN BE COPIED THROUGHOUT A SITE, OR IN
DIFFERENT SITES.
KEY: FUNCTION: KEY: FUNCTION:
ON/
OFF
DISP
SEND
OK
RESET
BRIGHTNESS:
SENSITIVITY:
HOLD TIME:
STANDBY
TIME:
AUTO
TEST
2S
PRESS THE ON/OFF BUTTON, THE LIGHT
GOES TO PERMANENT ON OR PERMANENT
OFF MODE, THE SENSOR IS LOCKED, MUST
PRESS "AUTO" TO QUIT FROM THIS MODE.
DISPLAY CURRENT PARAMETERS.
UPLOAD THE SELECTED PARAMETERS TO
SENSORS.
ENTER IN THE SETTING CONDITION AND
NAVIGATE TO UP AND DOWN.
NAVIGATE TO RIGHT AND LEFT.
CONFIRM SELECTED PARAMETERS AND
SAVING.
ADJUST THE BRIGHTNESS DURING HOLD
TIME.
THE TIME OF LIGHT FIXTURE REMAINS AT
PROGRAMMED 70%/ 80%/ 100% LEVEL AFTER
MOTION IS NOT DETECTED.
SELECT STAND-BY PERIOD AT 1MIN/ 30MIN/
60MIN/ +∞
• NOTE: "+∞” MEANS BI-LEVEL DIMMING
CONTROL, FIXTURE NEVER SWITCHES OFF.
ADJUST SENSOR SENSITIVITY.
MODE
1
MODE
2
MODE
3
MODE
4
STANDBY
DIM:
DAYLIGHT
SENSOR:
PRESS "AUTO" BUTTON, THE SENSORS
STARTS TO WORK AUTOMATICALLY AND ALL
PARAMETERS REMAIN THE SAME AS THE LATEST
STATUS IN AUTO MODE.
THE BUTTON "TEST" IS FOR TESTING PURPOSE
SENSITIVITY ONLY. THE SENSOR GOES TO TEST
MODE (HOLD TIME IS ONLY 2S) AUTOMATICALLY
AFTER COMMISSIONING, MEANWHILE THE
STAND-BY PERIOD AND DAYLIGHT SENSOR ARE
DISABLED PRESS "AUTO" TO QUIT FROM THIS
MODE.
WHEN THE LIGHT LEVEL EXCEEDS THIS SETITNG,
THE LIGHTS WILL TURN OFF EVEN WHEN THE
SPACE IS OCCUPIED. ONCE THE LIGHT LEVEL
EXCEEDS THIS SETITNG, THE SENSOR WILL
WAIT AND MONITOR FOR 1 MIN IN ORDER TO
CONFIRM THE LIGHT LEVEL INCREASE IS NOT
TEMPORARY BEFORE FORCING THE LIGHTS TO
GO OFF. WHEN LIGHT LEVEL GOES
BELOW THE SETITNGS, THE LIGHT WILL TURN
ON EVEN WITHOUT MOTION DETECTION AFTER
1 MIN. THIS FEAUTRE IS DISABLED BY DEFAULT.
PRESS BUTTON TO CHOOSE
DAYLIGHT SENSOR SETPOINT ON/OFF.
FOUR MODES WITH EXISTING PARAMETERS
WHICH ARE AVAILABLE TO BE UPDATED AND
SAVED IN MODES.
SELECT /10LUX /30LUX /50LUX/X THRESHOLD
FOR SENSOR TO TURN LIGHT FIXTURE ON.
SELECT , CURRENT SURROUNDING LUX VALUE
AS DAYLIGHT LUX THREHOLD, SELECT , THE
BUILT-IN DAYLIGHT SENSOR STOPS WORKING,
AND ALL MOTIONS DETECTED COULD TURN THE
LIGHT FIXTURE ON, NO MATTER HOW BRIGHT
THE NATURAL LIGHT IS.
SELECT THE STAND-BY DIMMING LEVEL AT
0%/ 10%/ 30%/ 50%
• NOTE: "0%" MEANS ON/OFF CONTROL.
DEFAULT
SETTINGS:
COMMISSIONING TOOL:

COMMISSIONING TOOL SETTINGS:
1. PRESS BUTTON, THE REMOTE CONTROL LEDS WILL SHOW THE LATEST PARAMETERS YOU SET.
• NOTE: IF YOU PUSH BUTTON BEFORE, YOU MUST PUSH BUTTON TO UNLOCK THE SENSOR.
2. PRESS OR ENTER IN THE SETTING CONDITION, THE PARAMETER LEDS OF REMOTE CONTROL WILL
FLASH TO BE SELECTED, NAVIGATE TO THE DESIRED SETTING BY PRESSING TO SELECT THE NEW
PARAMETERS.
3. PRESS OK TO CONFIRM ALL SETTINGS.
4. AIM AT THE TARGET SENSOR AND PRESS TO UPLOAD THE NEW PARAMETER, THE LED LIGHT WHICH THE
SENSOR CONNECTS WILL ON/OFF AS CONFIRM.
• NOTE: THE SETTING WORKS KEY STEP IS BY PRESSING OR , ENTER IN THE SETTING CONDITION.
• NOTE: THE LED LIGHT WHICH THE SENSOR CONNECTS WILL FLASH ON/OFF AFTER GETTING THE NEW
PARAMETER AS CONFIRMATION.
• NOTE: IF YOU PRESS BUTTON, THE REMOTE LED INDICATORS WILL SHOW THE LATEST PARAMETERS WHICH
WERE SENT.
CHANGE MULTIPLE SETTING OF SENSORS WITH SMART PHOTOCELL SENSOR:
1. PRESS THE REMOTE LED INDICATORS WILL SHOW THE LATEST PARAMETERS.
2. PRESS OR ENTER IN THE SETTING CONDITION, THE PARAMETER LED INDICATORS OF REMOTE CONTROL
WILL FLASH TO BE SELECTED.
3. PRESS , 2 LED INDICATORS WILL FLASH IN DAYLIGHT SENSOR SETTINGS, SELECT DAYLIGHT
AS SETPOINT TO LIGHT ON AUTOMATICALLY, SELECT DAYLIGHT AS SETPOINT TO LIGHT OFF
AUTOMATICALLY.
4. PRESS TO CONFIRM ALL SETTING AND SAVING.
5. AIM AT THE TARGET SENSOR AND PRESS TO UPLOAD THE NEW PARAMETER. THE LED LIGHT WHICH THE
SENSOR CONNECTS WILL ON/OFF.
• NOTE: IS DISABLED BY DEFAULT.
• TO SET OR REMOVE THE SMART DAYLIGHT FUNCTION, PRESS WHEN REMOTE CONTROL IS IN SETTING
MODE.
• WHEN THE SMART DAYLIGHT FUNCTION IS ACTIVED, 2 LED INDICATORS WILL FLASH IN THE DAYLIGHT SENSOR
SETTING. SELECT DAYLIGHT AS SETPOINT FOR LIGHT TO SET AUTOMATICALLY, SELECT DAYLIGHT
AS SETPOINT TO TURN LIGHT OFF AUTOMATICALLY.WHEN SMART DAYLIGHT SENSOR CLOSE, LED
INDICATOR WILL FLASH IN THE DAYLIGHT SENSOR SETTING FOR CHOOSE DAYLIGHT SENSOR THRESHOLD.
• WHEN THE SMART DAYLIGHT SENSOR OPEN, THE STAND-BY TIME IS ONLY
• SMART DAYLIGHT SENSOR TAKES PLACE OF NORMAL PHOTOCELL SENOR AND WORKS INDEPENDENTLY.
• SEE DAYLIGHT SENSOR FUNCTION.
CORRIDOR FUNCTION:
• WITH SUFFCIENT
NATURAL LIGHT,
THE LIGHT DOES
NOT SWITCH ON
WHEN PRESENCE IS
DETECTED.
• THIS FUNCTION INSIDE THE MOTION SENSOR TO ACHIEVE TRI-LEVEL CONTROL, FOR SOME AREAS WHICH
REQUIRE A LIGHT CHANGE NOTICE BEFORE SWITCH-OFF. THE SENSOR OFFERS 3 LEVELS OF LIGHT: 100%
DIMMED LIGHT (NATURAL LIGHT IS INSUFFICIENT, OFF, AND 2 PERIODS OF SELECTABLE WAITING TIME:
MOTION HOLD-LIME AND STAND-BY PERIOD, SELECTABLE DAYLIGHT THRESHOLD AND FREEDOM OF
DETECTION AREA.
• WITH INSUFFICIENT
NATURAL LIGHT, THE
SENSOR SWITCHES
ON THE LIGHT
AUTOMATICALLY
WHEN PRESENCE IS
DETECTED.
• AFTER HOLD-TIME,
THE LIGHT DIMS TO
STAND-BY LEVEL IF
THE SURROUNDING
NATURAL LIGHT IS
BELOW THE DAYLIGHT
THRESHOLD.
• LIGHT SWITCHES OFF
AUTOMATICALLY AFTER
THE STAND-BY PERIOD
ELAPSES.

EiKO Global | 18000 W. 105th St, Olathe, KS 66061 | (P) 1-800-852-2217
EiKO Canada | 81 King St, Barrie, Ontario L4N 6B5 | (P) 1-705-721-5189 eiko.com
CORRIDOR FUNCTION VS DAYLIGHT SENSOR FUNCTION:
• IN THE CORRIDOR FUNCTION, TO ACTIVATE THE LIGHT THE NATURAL LIGHT LEVEL MUST BE LOWER THAN THE
DAYLIGHT SENSOR SETTING AND OCCUPANCY. WITH THE SMART DAYLIGHT SENSOR FUNCTION, THE NATURAL
LIGHT LEVEL MUST BE LOWER THAN THE DAY LIGHT SETPOINT TO ACTIVATE THE LIGHT EVEN IF THERE IS
VACANCY.
• IN THE CORRIDOR FUNCTION, TURN OFF THE LIGHT USING STAND-BY TIME END WITH VACANCY. TO TURN OFF
THE LIGHT WITH THE SMART DAYLIGHT SENSOR FUNCTION, THE NATURAL LIGHT LEVEL MUST BE HIGHER THAN
THE DAYLIGHT SETPOINT TO EVEN IF THERE IS OCCUPANCY.
• IN THE SMART DAYLIGHT SENSOR FUNCTION, NATURAL LIGHT LEVEL MUST BE HIGHER OR LOWER THAN THE
DAYLIGHT SETPOINT TO TURN THE LIGHT ON OR OFF. THESE PARAMETERS MUST BE KEPT FOR AT LEAST 1
MINUTE TO TURN THE LIGHT ON OR OFF AUTOMATICALLY.
DAYLIGHT SENSOR FUNCTION:
• THE LIGHT SWI TCHES
ON AT 100% WHEN
THERE IS MOVEMENT
DETECTED.
ALWAYS TURN OFF THE POWER SUPPLY FROM MAIN CIRCUIT BREAKER FIRST!
• OPEN THE DAYLIGHT SENSOR BY PUSH WHEN REMOTE CONTROL IS IN SETTING CONDITION.
• THE LIGHT DIMS TO
STAND-BY LEVEL
AFTER THE HOLD-
TIME.
• THE LIGHT REMAINS
IN DIMMING LEVEL AT
NIGHT.
• SETTINGS:
• HOLD-TIME: 30 MIN
• SETPOINT ON: 50LUX
• SETPOINTOFF:300LUX
• STAND-BY DIM: 10%
• STAND-BY PERIOD: +∞
(WHEN THE SMART
PHOLOCELL SENSOR
OPEN, THE SLAND-BY
TIME IS ONLY +∞)
• WHEN THE NATURAL
LIGHT LEVEL EXCEEDS
SETPOINT OFF TO
LIGHT. THE LIGHT
WILL TURN OFF EVEN
IF WHEN THE SPACE
IS OCCUPIED.
• THE LIGHT
AUTOMATICALLY
TURNS ON AT
10% WHEN
NATURAL LIGHT IS
INSUFFCIENT (NO
MOTION).
OFF
DIM
ON
EVERY 30
MIN
NO MOTION
MOTION
END OF
HOLD
TIME
ON
CHECK

EiKO Global | 18000 W. 105th St, Olathe, KS 66061 | (P) 1-800-852-2217
EiKO Canada | 81 King St, Barrie, Ontario L4N 6B5 | (P) 1-705-721-5189 eiko.com
RESET MODE:
• THE COMMISSIONING TOOL HAS 4 SCENE MODES WHICH ARE NOT DEFAULT. YOU MAY CREATE DESIRED
PARAMETERS AND SAVE AS THE NEW MODE (1,2,3,4) TO CONFIGURE THE INSTALLED SENSORS.
• RESET: ALL SETTINGS GO BACK TO SETTINGS OF DIP SWITCH IN SENSOR.
• SCENE MODES (1, 2, 3, 4):
APPLICATION SCENE OPTIONS BRIGHTNESS DETECTION AREA HOLD TIME STAND-BY
TIME
STAND-
BY DIM
LEVEL
DAYLIGHT SENSOR
INDOOR
INDOOR
INDOOR
OUTDOOR
MODE
MODE
MODE
MODE
UPLOAD AND DUPLICATE PARAMETERS TO SENSORS:
• THE UPLOAD FUNCTION ALLOWS YOU TO CONFIGURE THE SENSOR WITH ALL PARAMETERS IN ONE
OPERATION. YOU MAY SELECT CURRENT SETTING PARAMETERS OR THE MODE FOR UPLOADING. CURRENT
SETTING PARAMETERS OR THE MODE ARE DISPLAYED IN COMISSIONING TOOL.
• UPLOAD THE CURRENT PARAMETERS TO SENSOR(S), AND DUPLICATE THE SENSOR PARAMETERS FROM ONE TO
ANOTHER.
1. PRESS BUTTON OR PRESS , ALL PARAMETERS ARE DISPLAYED IN COMISSIONING
TOOL.
2. AIM AT THE SENSOR AND PRESS BUTTON. THE LIGHT THAT SENSOR CONNECTS WILL FLASH ON/OFF AS
CONFIRMATION
• NOTE: IF OTHER SENSORS NEED THE SAME PARAMETERS, JUST AIM COMISSIONING TOOL AT THE SENSOR AND
REPEAT STEP 2.

EiKO Global | 18000 W. 105th St, Olathe, KS 66061 | (P) 1-800-852-2217
EiKO Canada | 81 King St, Barrie, Ontario L4N 6B5 | (P) 1-705-721-5189 eiko.com
INSTRUCCIONES DE INSTALACIÓN
Sensores Z10
ESPECIFICACIONES:
SUMINISTRO DE ENERGÍA 12V-24VCC, >30mA
SALIDA DE CONTROL DE ATENUACIÓN 0-10V MÁX. 25mA CORRIENTE DE ENTRADA
RANGO REMOTO 50PIES (15M) INTERIOR, SIN LUZ DE FONDO
RADIO DE DETECCIÓN 20%/50%/75%/100% |
3.3 to 26.3ft (1 to 8m)
ALTURA DE MONTAJE 40ft (12m)
AJUSTE DE TIEMPO 10S/1MIN/5MIN/10MIN/15MIN/20MIN/30MIN/60MIN
CONTROL DE LA ILUMINACIÓN
24H/10LUX/30LUX/50LUX | 24H/0.93fc/2.8fc/4.6fc
TEMPERATURA -4°FA60°F (-20°CA60°C)
CLASIFICACIÓN IP
IP65
• AVISO: EL TIEMPO DE PRECALENTAMIENTO ES DE 40 SEGUNDOS. DESPUÉS DE QUE EL SENSOR CONECTA EL INGRESO DE
ENERGÍA POR PRIMERA VEZ, LA LUZ SE MANTENDRÁ ENCENDIDA DURANTE 40 SEGUNDOS, Y LUEGO PASARÁ A ATENUARSE
PARA FUNCIONAR CON NORMALIDAD.
• AVISO: AJUSTE DE FÁBRICA PREDETERMINADO: 100% DE SENSIBILIDAD. TIEMPO DE PERMANENCIA: 5MIN, EL SENSOR DE
LUZ DIURNA ES , NIVEL DE ATENUACIÓN: 30%, TIEMPO DE ATENUACIÓN: 60MIN.
• AVISO: CUALQUIER AJUSTE CAMBIADO POR EL CONTROL REMOTO SE SEÑALARÁ POR LA LUZ LED A LA QUE ESTÁ
CONECTADO EL SENSOR, QUE SE ENCENDERÁ Y APAGARÁ DE FORMA INTERMITENTE.
COBERTURA DEL SENSOR:
SENSOR Z10 PIR DE ATENUACIÓN BINIVEL CON FOTOCÉLULA:
AL
D
MOVIMIENTO PEQUEÑO
MOVIMIENTO IMPORTANTE
Altura Rango de diámetro (D)
Al (pies) Sensibilidad:
100% (pies)
Sensibilidad:
75% (pies)
Sensibilidad:
50% (pies)
Sensibilidad:
25% (pies)
40 40 20 0 0
30 50 40 5 0
20 40 40 20 10
10 40 40 40 20
DESBLOQUEOBLOQUEO
SEN5A/PIR/Z10
SEN5A/M/Z10
SEN5A/PC/Z10
SEN5A/CT

EiKO Global | 18000 W. 105th St, Olathe, KS 66061 | (P) 1-800-852-2217
EiKO Canada | 81 King St, Barrie, Ontario L4N 6B5 | (P) 1-705-721-5189 eiko.com
ESPECIFICACIONES:
SUMINISTRO DE ENERGÍA 12V-24VCC, >50mA
SALIDA DE CONTROL DE ATENUACIÓN 0-10V,MÁX. 25mA CORRIENTE DE ENTRADA
RANGO REMOTO 50PIES (15M) INTERIOR, SIN LUZ DE FONDO
SISTEMA HF 5.8GHz±75MHz
ENERGÍA DE TRANSMISIÓN <0.2mW
RADIO DE DETECCIÓN 20%/50%/75%/100% | 3.3 - 26.3ft (1 - 8m)
ALTURA DE MONTAJE 39.4ft (12m)
AJUSTE DE TIEMPO 10S/1MIN/5MIN/10MIN/15MIN/20MIN/30MIN/60MIN
CONTROL DE LA ILUMINACIÓN 24H/10LUX/30LUX/50LUX | 24H/0.93fc/2.8fc/4.6fc
TEMPERATURA -4°FA60°F (-20°CA60°C)
CLASIFICACIÓN IP IP65
• AVISO: EL TIEMPO DE PRECALENTAMIENTO ES DE 15 SEGUNDOS. DESPUÉS DE QUE EL SENSOR CONECTA EL INGRESO DE
ENERGÍA POR PRIMERA VEZ, LA LUZ SE MANTENDRÁ ENCENDIDA DURANTE 15 SEGUNDOS, Y LUEGO PASARÁ A ATENUARSE
PARA FUNCIONAR CON NORMALIDAD.
• AVISO: AJUSTE DE FÁBRICA PREDETERMINADO: 100% DE SENSIBILIDAD. TIEMPO DE PERMANENCIA: 5 MIN, EL SENSOR DE
LUZ DIURNA ES , NIVEL DE ATENUACIÓN: 30%, TIEMPO DE ATENUACIÓN: 60 MINUTOS.
• AVISO: CUALQUIER AJUSTE CAMBIADO POR EL CONTROL REMOTO SE SEÑALARÁ POR LA LUZ LED A LA QUE ESTÁ
CONECTADO EL SENSOR, QUE SE ENCENDERÁ Y APAGARÁ DE FORMA INTERMITENTE.
COBERTURA DEL SENSOR:
SENSOR DE ATENUACIÓN BINIVEL DE MICROONDAS Z10 CON FOTOCÉLULA:
AL
D
Altura Rango de diámetro (D)
Al (pies) Sensibilidad:
100% (pies)
Sensibilidad:
75% (pies)
Sensibilidad:
50% (pies)
Sensibilidad:
25% (pies)
40 40 30 5 0
30 60 50 20 0
20 40 40 30 10
10 40 40 40 20
DESBLOQUEOBLOQUEO

EiKO Global | 18000 W. 105th St, Olathe, KS 66061 | (P) 1-800-852-2217
EiKO Canada | 81 King St, Barrie, Ontario L4N 6B5 | (P) 1-705-721-5189 eiko.com
ESPECIFICACIONES:
• LA FOTOCÉLULA Z10 ESTÁ DISEÑADA PARA CONTROLAR EL ALUMBRADO PÚBLICO, LA ILUMINACIÓN DE LOS
PASILLOS Y LA ILUMINACIÓN DE LAS ENTRADAS DE FORMA AUTOMÁTICA DE ACUERDO CON LOS NIVELES
DE ILUMINACIÓN AMBIENTAL. EQUIPADO CON CIRCUITOS ELECTRÓNICOS, LA FUNCIÓN FÁCIL DE PROBAR
CON UN RETARDO DE TIEMPO DE 5 SEGUNDOS OFRECE UNA RESPUESTA RÁPIDA A LOS CAMBIOS DE NIVEL
DE ILUMINACIÓN. EL PREAJUSTE DE TIEMPO DE RETARDO DE 5 SEGUNDOS PROTEGE CONTRA EL MAL
FUNCIONAMIENTO DEBIDO A FOCOS O RAYOS DURANTE LA NOCHE.
Z10 FOTOCÉLULA:
DESBLOQUEOBLOQUEO
SUMINISTRO DE ENERGÍA 12V-24VDC
FRECUENCIA NOMINAL 50mA±5%
EL CONSUMO DE ENERGÍA 0.4WMÁX.
NIVEL DE OPERACIÓN 16Lux ENCENDIDO / 24Lux APAGADO | 1.5fc EBCEBDIDO / 2.2fc APAGADO
TEMPERATURA AMBIENTE 99%RH
TEMPERATURA -40°F A 158°F (-40°C- A 70°C)
CLASIFICACIÓN IP IP65