Dialight Medium Intensity Manual de instrucciones

Document No: 9100-127-1958-99 Rev F
Release Date: 10/8/15
1501 Route 34
South, Farmingdale, NJ 07727 Tel: (732) 919-3119 Fax:
(732) 751-5778 www.dialight.com
•DO NOT let any supply cords touch hot
surfaces higher than cord ratings.
•DO NOT mount near gas or electric heaters
•Equipment should be mounted in locations and
at heights where it will not be subjected to
tampering by unauthorized personnel.
•The use of accessory equipment not
recommended by the manufacturer may cause
unsafe conditions.
•DO NOT use this equipment for other than
intended use.
•DO NOT look into the Infrared (IR) LEDs. These
five IR LEDs on top of the unit (if applicable) will
not appear to be ON, but can be verified using
most digital cameras.
•Pictures are required for
commissioning the install. Failure to
provide could VOID all warranties
SAVE THESE INSTRUCTIONS!!
•The operation and maintenance must be carried
out by authorized personnel.
•Repairs and Installation must only be carried out
by a qualified electrician.
•Only genuine Dialight replacement parts must be
used when unforeseen repairs are required.
•Observe the national safety rules and regulations
during installation!
•Earth Grounding is required throughout the
install process. Failure to do so could void all
warranties!
•No alterations should be done without the
agreement from Dialight Corp. Alterations other
Than written in this manual will void all
warranties.
Instructions must be kept with the system installed
Introduction:
This manual is for orientation of the controller, configuration and definitions of the Dual
Strobe system or Dual Strobe + Infrared (IR) system.
Refer to the installation manual for the following information
•Installing the Controller and the pre drilled holes
•Dimensions of the Controller
•Securing the cables to the structure
•Connection of either AC or DC input voltages
•Connection of the Side lights and calibration
•Photocell connections
•Flashhead connections for both the 4 conductor and the 8 conductor versions
•Proper bonding of the Strobe cable
•Mounting the Flashhead.
Medium Intensity Quick Start Manual
READ AND FOLLOW ALL SAFETY INSTRUCTIONS

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
Included in this manual:
•System overview
•Installation Tips and requirements
•System Descriptions
•RS485 Communication Connections
•Installing the RS485 to additional power supplies
•Controller layouts
•Navigating the LCD Display oLCD startup display screens oSetup Screens
(Configuration) oMain Menu Screens oManual Lighting inspection test
•Controller Status LED’s
•Dry contact connections
•Controller electrical Parameters
•Resetting, ext sync option, and serial numbers
•Replacement part numbers
•Display Events and Alarm Descriptions
•Alarm list and possible causes
System Overview:

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
Installation Tips and requirements:
For the Mains cable, it is recommended that the electrician or installer calculate the wire
requirements based on the amount of Flash heads being installed. It is recommended
that no install utilizes less than 16AWG wire with at least a 90ºC temperature rating. See
electrical parameters.
For RS485 cabling; 3 cores of 18AWG, drain wire plus a shield and braid for adequate
grounding and signals are required. RS485 is only required for E1+1 and larger
structures where multiple Strobes are required.
Cable between the Flash head and the controller must be a minimum of 14AWG and 4
conductors with foil and braid. Maximum distance between the controller and the Flash
head is 630feet.
NOTE: Failure to do any of the above could void all factory warranties. If in doubt please
contact your sales agent or representative.
During installing on the tower proper grounding techniques should be utilized.
The system has built in Lightning and RF immunity at each section, but for it to be
effective proper ground connection techniques must be used. For more details or
contact your local sales rep.
System Descriptions that are covered in the manual:
D1RW-C13-009-CTR = consists of:
•D1RW-FH009 (Flash Head)
•D1RW-CTR009 (Controller/Supply)
Gen5 dual red/white with AC input , 48volt
sidelights and 8 conductor flash head cable
required
D1RW-C13-409-CTR = consists of:
•D1RW-FH409 (Flash Head)
•D1RW-CTR409 (Controller/Supply)
Gen5 dual red/white with AC input , 48volt
sidelights and 4 conductor flash head cable
required
D1RW-C14-009-CTR = consists of:
•D1RW-FH009 (Flash Head)
•D1RW-CTR049 (Controller/Supply)
Gen5 dual red/white with 48VDC input , 48volt
sidelights and 8 conductor flash head cable
required
D1RW-C14-409-CTR = consists of:
•D1RW-FH409 (Flash Head)
•D1RW-CTR449 (Controller/Supply)
Gen5 dual red/white with 48VDC input , 48volt
sidelights and 4 conductor flash head cable
required
D1RW-C17-009-CTR = consists of:
•D1RW-FH009 (Flash Head)
•D1RW-CTR079 (Controller/Supply)
Gen5 dual red/white with AC input , AC sidelights
and 8 conductor flash head cable required
D1RW-C17-409-CTR = consists of:
•D1RW-FH409 (Flash Head)
•D1RW-CTR479 (Controller/Supply)
Gen5 dual red/white with AC input , AC sidelights
and 4 conductor flash head cable required
D1CW-C13-409-CTR = consists of:
•D1CW-FH409 (Flash Head)
•D1CW-CTR409 (Controller/Supply)
Gen5 dual red/white + Infrared (IR) with AC input ,
48volt sidelights and 4 conductor flash head cable
required
D1CW-C14-409-CTR = consists of:
•D1CW-FH409 (Flash Head)
•D1CW-CTR449 (Controller/Supply)
Gen5 dual red/white + Infrared (IR) with 48VDC
input , 48volt sidelights and 8 conductor flash head
cable required

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
RS485 Communication Connections:
NOTE: The below is common between all the controllers covered in the manual.
The connection of the RS485 cable is vitally important to the operation of the system.
This connection provides all the events and alarms to the Master controller that is being
used with the installation.
Factory connected wiring color code:
Boards are Labeled Description Color Code
Label “A”
Communications “A”
Grey
Common
Common for RS485
Yellow
Label “B”
Communications “B”
Blue
Option 1: RS485 consisting of 3 conductors, a drain wire and foil shield and braid.
Install Cable Connected to Description Color Code
Conductor 1
Label “A”
Communications “A”
Grey
Conductor 2
Common
Common for RS485
Yellow
Conductor 3
Label “B”
Communications “B”
Blue
Drain wire
Ground stud
Ground
Bare wire
Foil Shield and
Braid
Clamping terminal
Ground
Connected when
cable enters the
enclosure and must
be secured to the
plate
Option 2: RS485 consisting of 2 Conductors, a drain wire and either a shield or
braid is used.
Install Cable Connected to Description Color Code
Conductor 1
Label “A”
Communications “A”
Red
Drain Wire
Common
Common for RS485
Bare Wire
Conductor 2
Label “B”
Communications “B”
Black
Shield or Braid
Clamping Terminal
Ground
Connected when
cable enters the
enclosure and must
be connected to
plate
WARNING: For Color Codes not shown the installer must take note of the colors used
for these connections since it is required that all A, Common and B terminals be
connected the same throughout the system.

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
Installing the RS485 to additional power supplies
NOTE: For an E1 system there is no externally connected RS485.
NOTE: For structures lager than the above additional external communications need to
be added between the RS485 surge board and the translator boards in each of the
additional power supplies.
NOTE: For systems larger than E2 daisy chaining between the translator boards is
required.
NOTE: Translator boards are located in power supply enclosures NOTE:
The controller translator board is to be set to zero.
RS485
Located in
Controller
E2, D2 and A2
Translator
Board#1
Translator
Board#2
RS485
Junctio
n
Board
E1+1,
D1+1 and A1+1
RS485
Junction
Board
Translator
Board#1
Located in
power
supplies

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
D1xW-C13-x09-CTR Controller:
Requirements
NOTE: See electrical parameters for power consumption
Attach output of Photocell to side light monitor board (Marker) board J4
Connect the RS485 to the Junction Board when additional power supplies are
connected.

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
D1RWC17409CTR Controller:
Requirements
NOTE: See electrical parameters for power consumption
Attach output of Photocell to monitor board (Marker) board J4
Connect the RS485 to the Junction Board when additional power supplies are
connected.

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
LCD Start up Display Screens:
Once power is turned on the next 2 screens will be displayed automatically.
The Startup Screen displays:
Dialight MI Ctrl
REV. x Build: xx
NOTE: The Site manager and Installer should take a note of this screen including the
REV number and the Build number if any future troubleshooting is required. x’s indicate
revision levels and will appear as numbers on the display.
The Initializing Screen:
This screen shows a countdown for the initial 15 flashes for E and D type structures For
A red only systems the countdown starts at 45.
NOTE: In some cases this screen will go back to the Startup screen if synchronization
was faulty.
Initial 15 Flashes In
Process

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
Setup Screens:
These screens are used for properly configuring system based on the structure type that
is being installed. By using the “UP” and “DWN” buttons the user or maintenance
personnel can view and edit the configuration as applicable by pressing the “ENTR”
button after the selecting the desired choice the next screen will be entered.
Configuration Type Screen:
A) To change configuration of controller go to ‘Config Type’ screen’ and press
“ENTR”. This will enable you to select either an “E” “A” or “D” tower type. Sub
categories such as E1, E2 etc. will be addressed later in the configuration
menu.
CONFIG TYPE X
‘Enter to change’
B) Use the “UP” and “DWN” buttons to scroll and select tower style A, D, or E.
Then press “ENTR”.
NOTE: If ‘Tower Style D’ is selected, the system will automatically proceed to
step F, skipping steps D and E since side markers (L810) are not used in D style
configurations. Any information previously in the system as indicated in omitted
steps will be changed to “0” if switched back to an E or A style configuration and
will have to be re-entered to match what is installed on the tower.
NOTE: System will reset when tower style is changed.
Tower style = E
‘enter’ to change
C) Select for the presence of an External GPS using the “UP” and “DWN” buttons,
“YES” indicates an external GPS is being used, “NO” is the standard
configuration without an external GPS. Press “ENTR” after selection.
Ext GPS = NO
u/d=chg, enter=done

Document No: 9100-127-1958-99 Rev F
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
D) Select the number of Side Marker (L810 or RTO) Tiers that are connected to
the system. 0 through 4 can be selected; the number input shall represent the
number of tiers present. Press “ENTR”.
Num of 810 TIERS=0
u/d=chg, enter=done
E) Select the number of Side Marker s (L810’s, RTO’s) that will connected to P1
(Tier 1) 0 through 4 can be selected, then press “ENTR”
NOTE: Repeat for ports 2 through 4.
NOTE: Each port represents one tier.
NUM 810 P1/T1= 0
u/d=chg, enter=done
F) Select the number of beacons (864/5’s) that will be connected to the system. 1
through 9 beacons can be supported. Press “ENTR”
Number of 864/5 = 1
u/d=chg, enter=done
G) Select the number of side light boards that are connected to the system, 1
through 9 and the press “ENTR”.
NOTE: Additional sidelight monitor boards are available for special applications;
most configurations will only have one board and this will remain set to “1”
Number of SD BDs=1
u/d=chg, enter=done
Este manual sirve para los siguientes modelos