De Nora Capital Controls CHLORALERT T17CA4000 Series Manual de usuario

- 1 - 325.6030.7
Instruction Manual
CHLORALERTTM
Series T17CA4000
Chlorine Gas Leak Detector CAPITAL CONTROLS®

325.6030.7 - 2 -
These instructions describe the installation, operation and maintenance of the subject equipment. Failure to strictly
follow these instructions can lead to an equipment rupture that may cause signicant property damage, severe
personal injury and even death. If you do not understand these instructions, please call De Nora Water Technologies
for clarication before commencing any work at +1 215-997-4000 and ask for a Field Service Manager. De Nora Water
Technologies, Inc. reserves the rights to make engineering renements that may not be described herein. It is the
responsibility of the installer to contact De Nora Water Technologies, Inc. for information that cannot be answered specically
by these instructions.
Any customer request to alter or reduce the design safeguards incorporated into De Nora Water Technologies
equipment is conditioned on the customer absolving De Nora Water Technologies from any consequences of such a
decision.
De Nora Water Technologies has developed the recommended installation, operating and maintenance procedures with
careful attention to safety. In addition to instruction/operating manuals, all instructions given on labels or attached tags
should be followed. Regardless of these eorts, it is not possible to eliminate all hazards from the equipment or foresee every
possible hazard that may occur. It is the responsibility of the installer to ensure that the recommended installation instructions
are followed. It is the responsibility of the user to ensure that the recommended operating and maintenance instructions are
followed. De Nora Water Technologies, Inc. cannot be responsible deviations from the recommended instructions that may
result in a hazardous or unsafe condition.
De Nora Water Technologies, Inc. cannot be responsible for the overall system design of which our equipment may be
an integral part of or any unauthorized modications to the equipment made by any party other that De Nora Water
Technologies, Inc.
De Nora Water Technologies, Inc. takes all reasonable precautions in packaging the equipment to prevent shipping damage.
Carefully inspect each item and report damages immediately to the shipping agent involved for equipment shipped“F.O.B.
Colmar” or to De Nora Water Technologies for equipment shipped“F.O.B Jobsite”. Do not install damaged equipment.
De Nora Water Technologies, Colmar Operations
Colmar, Pennsylvania, USA
is ISO 9001: 2008 Certied
READ THE ENTIRE MANUAL BEFORE OPERATING
USE ONLY IN ACCORDANCE WITH INSTRUCTION MANUAL
WARNING: HAZARDOUS VOLTAGES

- 3 - 325.6030.7
INSTRUCTION BULLETIN
CHLORINE GAS LEAK DETECTOR
"CHLORALERT"
Model T17CA4000
Rev. 1.2
IMPORTANT
The instructions given herein cover generally the description, installation, operation and maintenance of subject
equipment.
DNWT reserves the right to make engineering renements that may not be reected in this Bulletin.
Should any question arise which may not be answered specically by these instructions, they should be directed to
De Nora Water Technologies for further detailed information and technical assistance.
DNWT takes all possible precautions in packing each equipment item to prevent damage during shipment.
Carefully inspect each item and if damage has occurred report it immediately.
Do not install any equipment if damage is such that faulty operation is likely to result.
If plant engineering drawing are available at the installation site , locate, mount , pipe and wire thesubject equipment
in accordance with these drawings.
If plant engineering drawings are not available, refer to the Installation section for information concerning these
requirements.
Carefully inspect all packing material before discarding it to prevent loss of mounting hardware, accessories, spare
parts or instructions.
All instructions given on any attached tag should be followed.
WARNING
To assure safe operation this equipment carefully follow use and installation instructions
and recommendations illustrated in this Manual. Improper use of the equipment
may damage the equipment and endanger the safety
of the operating personnel.

325.6030.7 - 4 -
PAGE INTENTIONALLY LEFT BLANK

- 5 - 325.6030.7
TABLE OF CONTENTS
1 INTRODUCTION ............................................................................................................................................................ 6
1.1 General Description ............................................................................................................................................................................. 6
2 TECHNICAL SPECIFICATIONS ....................................................................................................................................... 7
3 MODEL NUMBER BREAKDOWN ................................................................................................................................... 9
3.1 Standard accessories............................................................................................................................................................................ 9
4 INSTALLATION .......................................................................................................................................................... 10
4.1 Location ..................................................................................................................................................................................................10
4.2 Mounting................................................................................................................................................................................................10
4.3 Sampling line ........................................................................................................................................................................................11
4.4 Electrical wiring....................................................................................................................................................................................11
5 OPERATION, MAINTENANCE AND TESTING.............................................................................................................. 12
5.1 Electrolyte lling at start up ............................................................................................................................................................12
5.2 Electrolyte renewal after operation .............................................................................................................................................12
5.3 Sample ow rate..................................................................................................................................................................................12
5.4 Gas Test 12
5.5 Circuit performance check...............................................................................................................................................................13
6 MAINTENANCE PROCEDURES.................................................................................................................................... 14
6.1 Measuring cell maintenance...........................................................................................................................................................14
6.2 Flowmeter ..............................................................................................................................................................................................14
6.2.1 For Model T17CA4100 ......................................................................................................................................................14
6.2.1 For Model T17CA4200 ......................................................................................................................................................14
6.3 Electronic circuit board .....................................................................................................................................................................14
6.4 Optical sensor (Only for Model T17CA4200)..............................................................................................................................14
7 CE DECLARATION........................................................................................................................................................ 15
FIGURES
1 CHLORALERT Internal View................................................................................................................................................................ 4
2 Outline Dimensions.............................................................................................................................................................................. 8
3 Typical Installation ..............................................................................................................................................................................10
4 Electrical Wiring....................................................................................................................................................................................11

325.6030.7 - 6 -
1 INTRODUCTION
1.1 General Description
The De Nora Water Technologies chlorine gas leak detector, CHLORALERT™ T17CA4000, continually monitors air
samples for the presence of chlorine. It is usually installed in chlorine usage and storage areas to protect personnel
and equipment.
A small internal air blower continually draws a sample of air into the Chloralert. The owmeter and valve enable a
xed amount of air to be passed over the surface of the special electrolyte, where the chemical reaction takes place
in presence of chlorine. Two platinum electrodes, half immersed in the electrolyte, pick up the electrochemical
current thus generated which is measured by the electronic circuit and used to trigger an alarm system.
The trip point may be factory set to 1 or 3 ppm chlorine in air by volume. The power on/alarm lamp commences
ashing in the alarm condition.
In the Model T17CA4100, a relay is also energized to enable external alarms, extractor fans etc. to be activated. The
alarm condition is generated, in addition to the presence of chlorine in air, also by power failures, when the power is
returned to the system.
In the Model T17CA4200, a relay is also de-energized to enable external alarms, extractor fans etc. to be activated.
The electrical circuits are designed such that power supply failure causes the alarm relay to go into the alarm state.
A ow sensor detects when there is no sample ow and causes the alarm relay to go into the alarm state. The
sample fan is stopped when the alarm condition is actuated, to prevent saturation of electrolyte with chlorine and
contaminated air to be discharged in safe area through the Chloralert™ itself.
The unit has an integral electrical test facility.
The alarm needs operator's acknowledgment to be reset.
Figure 1 - CHLORALERT Internal View

- 7 - 325.6030.7
2 TECHNICAL SPECIFICATIONS
Power supply: 120 Vac, 60 Hz
220 Vac, 50 Hz
110 Vac, 50 Hz
Detection level: 1 ppm (3 mg/m3), or 3 ppm (9 mg/m3)
Relay contacts: DPDT, 10 A. 240 Vac, resistive load or 28 Vdc
Cell response time: Instantaneous
Warm up time: Max 3 minutes
Sampling rate: 0.05 m3/min
Ambient temperature: -20°C (-4°F) to +65 °C (149°F)
Sample inlet connection: 1" NPT
Weight: approx. 2.8 kg
Mounting: Wall
Dimensions: 215 H x 162 W x 235 D (mm)
Material of construction: Housing: ABS
Cell: ABS
Electrodes: Platinum

325.6030.7 - 8 -
Figure 2 - Mounting and Outline Dimensions in inches (mm)
CHLORALERT
R
E
S
E
T
A
L
A
R
M
T
S
T
E
WHEN
FLASHING
C
C
NREVES
SERVICES
TR N
E T

- 9 - 325.6030.7
3 MODEL NUMBER BREAKDOWN
T17CA4 B
Basic CHLORALERT™
Alarm Design
1 - Standard
2 - Fail Safe
Electrical Requirement
10 - 120 Vac, 60 Hz
20 - 220 Vac, 50 Hz
30 - 110 Vac, 50 Hz
Design Level
Alarm Level
3 - 1 ppm, Fixed
4 - 3 ppm, Fixed
3.1 Standard accessories
1 kit P/N 614S071U0l including:
• 1 electrolyte bottle
• 1 spare oat
• 1 set of spare O-Ring
• 1 insect screen

325.6030.7 - 10 -
4 INSTALLATION
4.1 Location
The Chloralert™ should ideally be mounted outside the area to be monitored. However it can be mounted in the
contaminated area if it is considered absolutely necessary. The location should be such that the ambient temperature
never falls below -20 °C (-4°F) nor rises above 65 °C (149°F).
It should never be mounted in direct sunlight and should be protected from the weather if mounted outside.
4.2 Mounting
Securely mount the Chloralert™ at a convenient working height (approx. 1,3 - 1.5 m from the oor).
4.3 Sampling line
As the Chlorine weight is higher then the air, we recommend that the sample inlet point is located at
about 200 mm (8") from the oor. Use of frigid or exible 1” PVC tubing is recommended. It is
recommended to install the proper insect screen (supplied) at the terminal point of the sample line to
avoid dust suction.
WARNING
NEVER USE TUBES WITH A DIAMETER LOWER THAN 1" WHEN
THE SAMPLE PIPE LENGTH EXCEEDS 4 M
Figure 3 - Typical Installation
CHLORALERT
R
E
S
E
T
A
L
A
R
M
T
S
T
E
WHEN
FLASHING
C
C
NREVES
SERVICES
T R N
ET
Tabla de contenidos
Otros manuales de Detector de gas de De Nora
Manuales populares de Detector de gas de otras marcas

Macurco
Macurco GD-6 Manual de usuario

Evikon
Evikon E2632 Manual de usuario

Critical Environment Technologies
Critical Environment Technologies CGAS-A Series Manual de usuario

MSA
MSA altair 5 Manual de usuario

DOD Technologies
DOD Technologies ChemLogic CL96 Manual de usuario

DEGA
DEGA NS III LCD Series Manual de usuario