INSTALLATION MANUAL
AC Power Disconnector and Distributor

Datalogic S.r.l.
Via S. Vitalino, 13
40012 Calderara di Reno (BO)
Italy
Tel. +39 051 3147011
Fax +39 051 3147205
© 2018-2022 Datalogic S.p.A. and /or its affiliates
All rights reserved. Without limiting the rights under copyright, no part of this documentation may be
reproduced, stored in or introduced into a retrieval system, or transmitted in any form or by any means, or
for any purpose, without the express written permission of Datalogic S.p.A. and/or its affiliates.
Owners of Datalogic products are hereby granted a non-exclusive, revocable license to reproduce and
transmit this documentation for the purchaser's own internal business purposes. Purchaser shall not
remove or alter any proprietary notices, including copyright notices, contained in this documentation and
shall ensure that all notices appear on any reproductions of the documentation.
Electronic versions of this document may be downloaded from the Datalogic website (www.data-
logic.com). If you visit our website and would like to make comments or suggestions about this or other
Datalogic publications, please let us know via the "Contact" page.
Disclaimer
Datalogic has taken reasonable measures to provide information in this manual that is complete and accu-
rate, however, Datalogic shall not be liable for technical or editorial errors or omissions contained herein,
nor for incidental or consequential damages resulting from the use of this material. Datalogic reserves the
right to change any specification at any time without prior notice.
Trademarks
Datalogic and the Datalogic logo are registered trademarks of Datalogic S.p.A. in many countries, including
the U.S.A. and the E.U.
All other trademarks and brands are property of their respective owners.
Patents
See www.patents.datalogic.com for patent list.

INSTALLATION MANUAL
iii
TABLE OF CONTENTS
PREFACE ..................................................................................................................IV
About This Manual .......................................................................................................... iv
Manual Conventions ........................................................................................................................... iv
Technical Support ........................................................................................................... iv
Support Through the Website ............................................................................................................ iv
Reseller Technical Support ................................................................................................................ iv
Safety Regulations ........................................................................................................... v
Electrical Safety ...................................................................................................................................v
Product Label ......................................................................................................................................v
CE Compliance .....................................................................................................................................v
General View .................................................................................................................. vi
CHAPTER 1.
INTRODUCTION.....................................................................................1
CHAPTER 2.
INSTALLATION .....................................................................................2
Cabinet Mounting ............................................................................................................. 2
System Wiring: AC Output ................................................................................................ 3
System Wiring: OUT#1 and OUT#2 .....................................................................................................3
System Wiring: OUT#3 ........................................................................................................................4
System Wiring: OUT#4 ........................................................................................................................4
System Wiring: AC Input .................................................................................................. 5
DWS-SWITCH-MONO Electrical Diagram ........................................................................... 6
CHAPTER 3.
TECHNICAL FEATURES .........................................................................7

iv
DWS-SWITCH-MONO
PREFACE
ABOUT THIS MANUAL
This Instruction Manual is provided for users seeking advanced technical information,
including installation, connections, maintenance and specifications.
Manual Conventions
The symbols listed below are used in this manual to notify the reader of key issues or
procedures that must be observed:
TECHNICAL SUPPORT
Support Through the Website
Datalogic provides several services as well as technical support through its website. Log
on to (www.datalogic.com).
For quick access, from the home page click on the search icon , and type in the name of
the product you’re looking for. This allows you access to download Data Sheets, Manu-
als, Software & Utilities, and Drawings.
Hover over the Support & Service menu for access to Services and Technical Support.
Reseller Technical Support
An excellent source for technical assistance and information is an authorized Datalogic
reseller. A reseller is acquainted with specific types of businesses, application software,
and computer systems and can provide individualized assistance.
NOTE: This symbol draws attention to important details or procedures that
must be followed for the correct installation of the product.
INFORMATION: This symbol used on the label, refers the user to informa-
tion contained in this manual.
CAUTION: This symbol identifies a hazard or procedure that, if incorrectly
performed, may cause personal injury or result in equipment damage.
Operations carrying this symbol must be performed by qualified personnel
only.
HIGH VOLTAGE: This symbol alerts the user they are about to perform an
action involving, either a dangerous level of voltage, or to warn against an
action that could result in damage to devices or electrical shock.

SAFETY REGULATIONS
INSTALLATION MANUAL
v
SAFETY REGULATIONS
Electrical Safety
This product conforms to the applicable requirements contained in the following Euro-
pean Standards:
• EN 61439-1
• EN 60204-1
Product Label
The Product data label is located on the outside door panel.
Figure 1 - Product Data Label
CE Compliance
CE marking states the compliance of the product with essential requirements listed in
the applicable European directive. Since the directives and applicable standards are
subject to continuous updates, and since Datalogic promptly adopts these updates,
therefore the EU declaration of conformity is a living document. The EU declaration of
conformity is available for competent authorities and customers through Datalogic
commercial reference contacts. Since April 20th, 2016 the main European directives
applicable to Datalogic products require inclusion of an adequate analysis and assess-
ment of the risk(s). This evaluation was carried out in relation to the applicable points of
the standards listed in the Declaration of Conformity. Datalogic products are mainly
designed for integration purposes into more complex systems. For this reason, it is
under the responsibility of the system integrator to do a new risk assessment regarding
the final installation.

PREFACE
vi
DWS-SWITCH-MONO
GENERAL VIEW
Figure 2 - DWS-SWITCH-MONO General View
6
1
24 5
7
8
3
2
1 Key Lock 5 AC Ouput Cable Compression Connectors
2 Main Switch 6 AC Line Input Terminals and Protection Earth
3 Product Data Label 7 AC Line Fuses
4 AC Input Cable Compression Connector 8 AC Line Output Terminal Block

INSTALLATION MANUAL
1
CHAPTER 1
INTRODUCTION
The DWS-SWITCH-MONO is an AC Power Disconnector and Distributor cabinet that can
be used as first functional block in Dimensioning, Weighting and Barcode Scanning
(DWS) systems.
This document describes the DWS-SWITCH-MONO used to power a system composed
of four electrical loads: a Datalogic PWR-480W electrical panel, a Scale (digital section),
a Datalogic PWR-2400 electrical panel and a Datalogic PWR-480B, PWR-240B; or PWR-
120 electrical panel.
The following chapter can be used as a checklist to verify all the steps necessary to com-
plete installation of the DWS-SWITCH-MONO.
CAUTION: Read all information in this manual before installation, paying
particular attention to all Caution and Warning notes.

2
DWS-SWITCH-MONO
CHAPTER 2
INSTALLATION
CABINET MOUNTING
The cabinet must be mounted to the reading station frame using the brackets and bolts
provided in the package
1. Mount the bracket to
the cabinet.
2. Mount the cabinet to
the frame.
Figure 3 - Mounting Brackets
Figure 4 - DWS-SWITCH-MONO cabinet max. height
IMPORTANT: The cabinet must be installed vertically in such a way that the
main switch is no higher than 1.90 m from the ground (see Figure below).
max. 190 cm

SYSTEM WIRING: AC OUTPUT
INSTALLATION MANUAL
3
Please note that the cabinet door can be unlocked and opened by using the key pro-
vided along with the product
SYSTEM WIRING: AC OUTPUT
System Wiring: OUT#1 and OUT#2
Figure 5 - Terminal Block for Out#1 and Out#2
The terminal block for Out#1 (PWR-480W) and for Out#2 (Scale) is highlighted in the
picture above.
Use cables 3 X yy mm2, where "yy" is a value between 2.5 - 4 mm2.
Out#1 and Out#2 are protected by Fuse QF01, 8A gG.
HIGH VOLTAGE: When the main switch is in the OFF position, the outputs
#1, #2, and #3 are disconnected, but not the AC Line Input Terminals!

INSTALLATION
4
DWS-SWITCH-MONO
System Wiring: OUT#3
Figure 6 - Terminal Block for Out#3
The terminal block for Out#3 (PWR-2400) is highlighted in the picture above. Use cables
3 X yy mm2, where "yy" is a value between 2.5 - 4 mm2.
Out#3 is protected by Fuse QF02, 16A gG.
System Wiring: OUT#4
Figure 7 - Terminal Block for Out#4
The terminal block for Out#4 (PWR-480B or PWR-240B or PWR-120) is highlighted in
the picture above. Use cables 3 X yy mm2, where "yy" is a value between 2.5 - 4 mm2.
Out#4 is protected by Fuse QF03, 4A gG.
CAUTION: Output cables can be max. 12 m long.
NOTE: When not used, keep the compression connectors sealed with their
appropriate plugs.