FXDQ-SPV1 EDTFVN391825
5
Model FXDQ50SPV1 FXDQ63SPV1
Powersupply 1phase,220-240V,50Hz 1phase,220-240V,50Hz
1 3Coolingcapacity
kcal/h 4,800 6,100
Btu/h 19,100 24,200
kW 5.6 7.1
2 3Heatingcapacity
kcal/h 5,400 6,900
Btu/h 21,500 27,300
kW 6.3 8.0
Powerinput Cooling kW 0.180 0.196
Heating kW 0.152 0.168
Casing/Colour Galvanizedsteelplate Galvanizedsteelplate
Dimensions:(H×W×D) mm 200×900×450 200×1,100×450
Fan
Type Siroccofan Siroccofan
Motoroutput×
Numberofunits W130×1 130×1
Airowrate
(HH/H/L)
m³/min 15.0/13.0/10.5 20.0/16.0/12.5
l/s 250/217/175 333/267/208
cfm 530/459/371 706/565/441
4 Externalstatic
pressure Pa 50-20 40-20
Drive Directdrive Directdrive
Temperaturecontrol Microprocessorthermostat
forcoolingandheating
Microprocessorthermostat
forcoolingandheating
Soundabsorbingthermalinsulationmaterial Foamedpolyethylene Foamedpolyethylene
Airlter — 5 — 5
Piping
connections
Liquidpipes mm φ6.4(Flareconnection) φ9.5(Flareconnection)
Gaspipes mm φ12.7(Flareconnection) φ15.9(Flareconnection)
Drainpipe mm VP20
(Externaldia.26,Internaldia.20)
VP20
(Externaldia.26,Internaldia.20)
Mass kg 20 23
6 7 8Soundpressurelevel
(HH/H/L) dB(A) 35/33/31 37/35/33
Safetydevices Fuse,Thermalprotectorforfanmotor Fuse,Thermalprotectorforfanmotor
Refrigerantcontrol Electronicexpansionvalve Electronicexpansionvalve
Standardaccessories
Operationmanual,Installationmanual,Drain
hose,Sealingpads,Clamps,Washers,
Insulationfortting,Metalclamp,Washerxing
plate,Screwsforductanges
Operationmanual,Installationmanual,Drain
hose,Sealingpads,Clamps,Washers,
Insulationfortting,Metalclamp,Washerxing
plate,Screwsforductanges
DrawingNo. Specication C:3D090326A C:3D090326A
Soundlevel C:4D090510A C:4D090511A
Notes:
1. Indoortemp.:27°CDB,19°CWB/outdoortemp.:35°CDB/Equivalentpipinglength:5m,leveldierence:0m.
2. Indoortemp.:20°CDB/outdoortemp.:7°CDB,6°CWB/Equivalentpipinglength:5m,leveldierence:0m.
3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.
4. Externalstaticpressureischangeabletosetbytheremotecontroller.Thispressuremeans“Highstaticpressure-
Standard”.(Factorysettingis10PaforFXDQ20-32SPmodelsand20PaforFXDQ40-63SPmodels.)
5. Airlterisnotstandardaccessory,butpleasemountitintheductsystemofthesuctionside.Selectits
colorimetricmethod(gravitymethod)50%ormore.
6. Anechoicchamberconversionvalue,measuredatapoint1.5mdownwardfromtheunitcentre.Duringactual
operation,thesevaluesarenormallysomewhathigherasaresultofambientconditions.
7. Valuesarebasedonthefollowingconditions:FXDQ20-32SP:externalstaticpressureof10Pa;FXDQ40-63SP:
externalstaticpressureof20Pa.
8. Thevaluesofoperationsoundlevelrepresentthoseforrear-suctionoperation.Soundlevelvaluesforbottom-
suctionoperationcanbeobtainedbyadding5dB(A).
Conversionformulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
l/s=m³/min×1000/60