WARNING
WARNING
A. Installation must conform to the requirements
of the authority having jurisdiction in or, in the absence
of such requirements, to the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, and/or Natural Gas and
Propane Installation Code, CAN/CSA B149.1.
Where required by the authority having jurisdiction, the
installation must conform to the Standard for Controls
and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1.
for installation on combustible
C. Provide clearance between boiler jacket and
ordinance. Refer to Figure 2 for minimum listed
clearances from combustible material. Recommended
service clearance is 24 in. (610 mm) from left side,
front, top and rear of the boiler. Recommended front
clearance may be reduced to the combustible material
clearance providing:
1. Access to boiler front is provided through a door or
removable front access panel.
2. Access is provided to the condensate trap located
underneath the heat exchanger.
3. Access is provided to thermal link located at boiler
rear.
D. Protect gas ignition system components
from water (dripping, spraying, rain, etc.) during
boiler operation and service (circulator replacement,
condensate trap, control replacement, etc.).
E. Provide combustion and ventilation air in
accordance with applicable provisions of local building
codes, or: USA - National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and Ventilation;
Canada - Natural Gas and Propane Installation Code,
CAN/CSA-B149.1, Venting Systems and Air Supply for
Appliances.
WARNING
F. The boiler should be located so as to minimize
the length of the vent system. The combustion air
piping must terminate where outdoor air is available for
combustion and away from areas that may contaminate
combustion air. In particular, avoid areas near chemical
paint removers, cleaning solvents and detergents.
dry wall dust etc.
G. General.
1. Phantom boilers are intended for installations in an
prevent any leaks or safety relief valve discharge
resulting in property damage.
2. Phantom boilers are not intended to support external
piping and venting. All external piping and venting
must be supported independently of the boiler.
3. Phantom boilers must be installed level to prevent
condensate from backing up inside the boiler.